
34
Mounting the Remote Interface Controller (Wireless)
Fig. 1
Fig. 2
Fig. 3
1.
Plan on mounting the remote interface controller on a solid
surface away from doors, corners, air outlets, drafts or heat
generating equipment. Do not mount the remote interface
controller directly on an outside wall, a wall adjacent to a boiler
room, or other hot area. Use a piece of foam insulation behind
the sensor to insulate it from a hot or cold surface. The
recommended height is 5ft to 6ft (1.5m to 1.8m) above the
finished floor.
2.
Locate the Mounting Template upon the wall where the
Controller will be mounted (Fig. 1). Using the crosses on the
template to assist in levelling the template.
3.
Drill two
1/8” holes and insert anchors within the mounting
surface. Anchors may not be required if securing to a wall stud
or racking system. Insert the screws into the holes and test fit
the backing plate for mounting to ensure it mounts easily onto
the two screws and slides down onto the slotted openings
freely (Fig. 2)
4.
Insert the three AA batteries.
(Only applicable with wireless installations)
5.
The system will automatically acknowledge a wireless device
(Remote Interface or Remote Sensor). Go to Setting “30” to
define the Remote User Interface use.
6.
Attach controller to the wall (Fig. 3).
Содержание WINE GUARDIAN DS025
Страница 13: ...13 Overview of the Evaporator Fig 1...
Страница 14: ...14 Overview of the Condenser Fig 2...
Страница 15: ...15 Refrigeration Illustration Fig 3...
Страница 16: ...16 Wiring Diagram for DS025 WGS40 Fig 4...
Страница 17: ...17 Wiring Diagram for DS025 WGS40 cont Fig 5...
Страница 18: ...18 Wiring Diagram for DS025 WGS40 cont Fig 6...
Страница 19: ...19 Wiring Diagram for DS025 WGS40 cont Fig 7...