
26
ELECTRICAL SHOCK HAZARD
RISK OF SERIOUS INJURY OR DEATH
The electrical outlet and wiring installation must
meet the
national and local building codes.
Drain Line
Splice the drain line onto the drain outlet with a short piece of ½” copper tubing and
secure the drain line to the unit with a hose clamp. The drain l
ine’s interior diameter
should be ½” (12.7mm). The drain line must extend from the unit to an open floor drain
or condensate pump. Do
NOT
install an external trap on the drain line, every ducted
Wine Guardian unit is built with an internal trap. Allow enough height for the drain line to
function properly. If draining into a nearby sink, the unit must be elevated higher than
the rim of the sink in order for the water to drain by gravity. Install with a
¼” (6.35mm)
per linear foot of pitch.
Do not
tie the condensate drain line directly into the sanitary
sewer system.
The internal drain trap primes itself automatically once the unit has run
for a period of time and after the unit cycles off. This is confirmed by water dripping from
the drain.
Wiring the Fan-Coil
Match the Electrical Wiring to the cord provided on the Wine Guardian fan coil. Provide
dedicated circuit and wiring for the system. Match the wiring and breaker size to the
rated load as shown on the serial plate and in this guide. Please see the sample serial
plate illustration.
Содержание WINE GUARDIAN DS025
Страница 13: ...13 Overview of the Evaporator Fig 1...
Страница 14: ...14 Overview of the Condenser Fig 2...
Страница 15: ...15 Refrigeration Illustration Fig 3...
Страница 16: ...16 Wiring Diagram for DS025 WGS40 Fig 4...
Страница 17: ...17 Wiring Diagram for DS025 WGS40 cont Fig 5...
Страница 18: ...18 Wiring Diagram for DS025 WGS40 cont Fig 6...
Страница 19: ...19 Wiring Diagram for DS025 WGS40 cont Fig 7...