43
quarter inch, a vibration eliminator should be installed close to the motor compressor in a
horizontal parallel to the compressor, crankshaft or in a vertical position 90 degrees to
compressor crankshaft.
NOTE: The suction line should be clamped near the inlet end of the vibration
eliminator. The vibration eliminator is located between the clamp and the
compressor.
Split System Interconnecting Line Sizing Chart
Table 3
Model
Liquid
Line(OD)
Liquid
connection
at
evaporator
(OD)
Suction
line (OD)
Min.
Suction line
insulation
thickness
(in)
Suction
connection
at
evaporator
(OD)
Maximum
“total” l
ine
length
Maximum
lift
(height)
DS025
1/4”
1/4”
3/8”
3/8”
3/8”
50’
15’
DS050
1/4”
1/4”
1/2
”
3/8”
*
3/8”
50’
15’
DS088
3/8”
*1/4”
5/8”
5/8”
*1/2”
50’
15’
DS200
3/8”
3/8”
¾”
5/8”
*1/2”
50’
15’
*Interconnecting tube must be reduced down at evaporator connection
50Hz Models
Model
Liquid
Line(OD)
Liquid
connection
at
evaporator
(OD)
Suction
line (OD)
Min.
Suction line
insulation
thickness
(in)
Suction
connection
at
evaporator
(OD)
Maximum
“total” line
length
Maximum lift
(height)
WGS40
0.635cm
0.635cm
0.952cm
0.952cm
0.952cm
15.24 meters
4.57 meters
WGS75
0.635cm
0.635cm
1.27cm
0.952cm
0.952cm
1
15.24 meters
4.57 meters
WGS100
0.952cm
0.635cm
1.59cm
1.59cm
1.27cm
2
15.24 meters
4.57 meters
WGS175
0.952cm
0.952cm
1.905cm
1.59cm
1.27cm
3
15.24 meters
4.57 meters
Notes:
•
Line lengths are expressed in equivalent feet = actual run fitting
allowances (i.e.
~5’ for each bend/elbow allowance).
•
Use only refrigeration grade dehydrated tubing.
60Hz Models
1
Use ½” (1.27cm) to 3/8” (0.952cm) reducer at evaporator
2
Use 5/8” (1.59cm) to ½” (1.27cm) reducer at evaporator
3
Use ¾” (1.91cm) to 1/2” (1.27cm) reducer at evaporator
Содержание 99H0360-10
Страница 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Страница 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Страница 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Страница 16: ...16 Magnified Image of the Condensing Unit...
Страница 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Страница 18: ...18 Wiring Diagram for DS088 and WGS100...
Страница 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Страница 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Страница 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Страница 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Страница 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Страница 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Страница 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Страница 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Страница 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...