Installing the Fan Coil Unit
Wine Guardian fan coil units are typically installed indoors located near the cellar to minimize the
duct runs. Each unit is provided with one entering or return air inlet and five possible supply air
outlets. A maximum cumulative total length of flexible ductwork, for both supply and return
ducts (including bends) of 25 feet (7.62 meters) is recommended. If longer runs are needed, use
more than one supply opening to reduce the airflow in each duct by one-half, or install rigid
ductwork that is typically less restrictive. Do not exceed 50 feet (15.2 meters) of total ductwork
without using of booster fans.
See Recommended Flexible Ductwork Sizing Chart on page 37.
Provide a three-foot clearance around the unit for removal of ductwork, or access for unit
maintenance. If the humidifier is used, provide access space in front of it for service. (See
separate humidifier manual.)
The fan coil unit can be located either above, or below the condensing unit in height. Wine
Guardian strongly suggests that any height difference be kept as minimal as possible.
The fan coil unit is equipped with an On/Off switch, two communication ports, and an optional
humidifier connection. One communication port is always used for the factory-supplied remote
interface controller and is supplied with 50 feet (15.2) of communication cable (RJ-9). The
second communication port can be used for other factory options, such as remote
temperature/humidity sensors
.
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Check supporting structure for load bearing capacity to support the Wine Guardian. All
supports must be designed to meet applicable local codes and ordinances. If in doubt, consult a
qualified architect, engineer or contractor.
NOTE: Review Fig. 1 through Fig. 4 on the following pages before mounting the
unit.
Floor Mounting
Mount the Wine Guardian fan coil on a plywood surface at least 12 inches (30.4cm) above the
floor to keep it away from water. Allow adequate space for the external drain.
Wall Mounting
If the unit is mounted onto a wall, provide adequate support on both ends of the unit to
accommodate the weight of the system. Use knee braces to transfer the load of the unit to the
wall. A shelf can be constructed to support the unit or a wall mount kit can be purchased
through a Wine Guardian distributor
.
Содержание 99H0360-10
Страница 12: ...12 Xtreme Low Ambient Illustrations Fig 1 Fig 2 Pressure cutout timer 33c0185 00...
Страница 14: ...14 Condensing unit dimensions DS050 COND NO OPTIONS...
Страница 15: ...15 Refrigeration Illustration of the system See next page for magnified image...
Страница 16: ...16 Magnified Image of the Condensing Unit...
Страница 17: ...17 Wiring Diagram for DS025 DS050 WGS40 WGS75...
Страница 18: ...18 Wiring Diagram for DS088 and WGS100...
Страница 19: ...19 Wiring Diagram for DS200 and WGS175 Units...
Страница 20: ...20 Wiring Diagram for Replacement Fan Motor XR 115 230 Models...
Страница 21: ...21 Wiring Diagram for DS025 and WGS40 Condensing Unit...
Страница 22: ...22 Wiring Diagram for DS050 and WGS75 Condensing Unit...
Страница 23: ...23 Wiring Diagram for DS088 and WGS100 Condensing Unit...
Страница 24: ...24 Wiring Diagram for DS200 and WGS175 Condensing Unit...
Страница 25: ...25 Ducted Split Systems Specifications 60Hz Models DS025 DS050 DS088 DS200...
Страница 26: ...26 Ducted Split System Specifications 50 Hz Models WGS40 WGS75 WGS100 WGS175...
Страница 44: ...44 Install refrigeration piping per local codes and ASHRAE guidelines...