MAINTENANCE

The  minimum  maintenance  recommended  for a detector c onsists  of an annual cl eaning  of dust from the head of the

detector, by making use of an air compressor, and cleaning a ll the air inlets to the chamber.  For more thorough cleaning,

send the detector to the manufacturer.

Do not dismantle the detector or the optical chamber.  Opening the detector signifies loss of the guarantee.

DETECTOR CODING

All  algorithmic  detectors  must  be c oded  with  a  number  as  corresponds  to  their  personalization.    The  recording o f  the

detector numbering can be carried out from:

1.

AE/SA-PRG manual address programming. See the programmer’s manual for their coding.

2.      Algorithmic Panel.  See operations manual of the algorithmic panel for their coding.

Program a number between

1

and

 125

 as corresponds for their personalization.

The identification number of the unit, as well as the operation pilot, is stored in EEPROM memory.

Before connecting the module to the algorithmic loop,

verify the coding is correct

.

INHIBITION OF FLASHING OF THE OPERATION PILOT

The operation pilot m ode can be altered b y the AE/SA-PRG  programmer or through the c oding mode of the Algorithmic

Panel.  By default, the operating mode is activated.

From the Algorithmic Panel, the flashing of the operation pilot can be disconnected generally.

TECHNICAL CHARACTERISTICS

Power supply voltage:

18 ~- 27 V (AE/SA-CTL Algorithmic loop card).

Consumption when idle:

1.9 mA

Consumption in alarm state:

4 mA

Wiring

2-wire. Recommended cross-section 1.5 mm

2

Temperature range:

-10º -  +50º C  (ambient temperature)

Humidity range:

Relative humidity 10% - 90% without condensation.

Casing material:

ABS

Luminous indicator:

Operation pilot:   

green flash (can be inhibited).

Alarm:

red permanent

Size:

diam.   

106 mm.

Height:     52 mm with low base.

Remote alarm output:

80 mA max.

Compatible bases:

AE/SA-Z    low base

AE/SA-ZA  supplement.

CERTIFICATIONS

ALGORITHMIC OPTICAL SMOKE DETECTOR

MOD.: AE/SA-OPI

Optical  smoke  detector  that  operates  according  to the  light  scattering principle (T yndall  effect).    It  is  suitable  for

detecting fires in their first smoke phase, before flames are formed or dangerous increases in temperature take place.

Formed by a dark chamber that incorporates a transmitter and a  receiver that detect the presence of particles in the

interior and fitted with a microcontroller in which the operating parameters are set.

Fabricated and certified according to the standard EN 54-7:2001.

Due to the detection method of this type of detector it is recommended for installation in clean surroundings.

OPERATION

The detector works by measuring the relative decrease of visibility in the surrounding atmosphere.

1.  When connected, it adapts to the surrounding conditions, inside maximum and minimum limits.

2.  Readings  are  taken  every  second  and  compared  with  the  reference  measurements  when  idle.    When  the

difference exceeds the programmed level, the detector goes to the pre-alarm or alarm state.

3.  The variations  are  analysed  with  regard  to the idle values  in  order  to provide  compensation,  if  necessary, and

adapt to the new environmental conditions.

4.  It  monitors th e  pollution  level  in  its  environment  or  the  fouling  parameters  in  its  interior,  if  they  surpass  the

programmed values and are maintained for a certain time, it passes to the maintenance state.

It monitors two alarm levels:

1.  It goes to the pre-alarm  state when the environmental  darkening surpasses  the programmed level,  but without

reaching the alarm level.

2.  It  goes  to  the  alarm  state  when  the  detected  level  reaches the  level  set  during  the  time  fixed  for  alarm

confirmation.

Maintenance level:

1.  It  warns wh en  the d egree  of  pollution  in  its e nvironment  or  the  fouling  parameters  in its inte rior,  surpass  the

programmed values and are maintained for a certain time.

2.  It monitors the detector adjustment level inside maximum and minimum limits.  These values can be affected by

height, pressure, humidity, etc. It checks they are inside the correct operating range and reports any anomaly.

It includes:

Operation pilot:  It indicates it is operating correctly, giving green-colored flashes through the alarm  LED.  If the

flashing is a nuisance in specific cases, it can be i nhibited on an individual basis from the detector itself, or in

general from the Algorithmic Fire Control Panel.

Maintenance  and  alarm  levels:    These  levels are  programmed  from  the  panel,  individually,  by  sectors or

collectively for each type.  They always take a default value to assure their correct operation.

Remote  alarm output:  T hey  have  a remote alar m  output  for connecti on  of  action  indicators,  etc, which is

activated when the detector reaches the programmed alarm level.

 

Individual identification:  Each detector is identified individually with a number inside the installation loop.   This

number is stored in EEPROM  memory whereby it remains even though the detec tor is without power for a long

period.

0099

05

0099/CPD/A74/000046

Smoke Detector

AE/SA-OPI

Technical Documentation: See Ae-man-838-0.0 v1.0

UNE-EN 54-7: 2001 (EN 54-7:2000)

UNE-EN 54-7/A1:2002 (EN 54-7:2000/A1:2002)

Aguilera Electrónica S.L.

C/Julián Camarillo 26 - 28037 MADRID - ESPAÑA