AGS Merlin 1250X Скачать руководство пользователя страница 1

Installation, Operation & Maintenance Manual

   Merlin1250X 

 

Rev: 1

 

Merlin 1250X 

Gas & Ventilation Interlock System 



Installation, Operation & Maintenance Manual 

Please read this manual carefully and retain for future use. 

The Merlin 1250X is a ventilation interlock panel for up to 2 fans. It has built-in current monitoring and is 
designed for use with fans up to 18A running current (0.1A minimum) and also has the ability to receive 
connections from external current monitors or air pressure differential switches. 

Information contained within this manual should be referenced for typical installation and operation only. 
For specific requirements that may deviate from the information in this guide – contact your supplier! 

Exhaust Fan

Intake Fan

Содержание Merlin 1250X

Страница 1: ...p to 2 fans It has built in current monitoring and is designed for use with fans up to 18A running current 0 1A minimum and also has the ability to receive connections from external current monitors o...

Страница 2: ...Mounting 4 Board Connections 5 Board Connections Overview 5 Access Configuration Settings 6 Configuration Settings Explained 6 Fan Calibration 7 Fan Dropout Threshold Values 7 Specification 8 OPERATI...

Страница 3: ...ccident unreasonable use neglect tampering or other causes not arising from defects in material or workmanship This warranty extends to the original consumer purchaser of the product only Warranty dis...

Страница 4: ...ing including diagnostics Please refer to your manufacturer s instructions for important information regarding coverage location and positioning including areas and conditions to avoid Mounting Unpack...

Страница 5: ...120Vac power output is supplied from the GAS VALVE OUT terminal using a 3 core cable can be connected to a gas solenoid valve The gas valve will shut off the supply in any error condition Refer to yo...

Страница 6: ...gas supply if high concentrations of Carbon Monoxideis detected Refer to your manufacturers CO monitor instructions Access Configuration Settings On the front fascia circuit board you ll find a SETTI...

Страница 7: ...he Fan Switch FS123 relay will stay ON Fan Calibration Select FANS CALIB In the settings menu 1 Press OK to switch to intake INT or exhaust EXTR fan Fan selection highlighted yellow 2 Wait for the cur...

Страница 8: ...ingle phase AC current monitor calibration range 0 1 18 Amps Single phase AC current monitor display 0 22Amps Power Consumption 4 6 W Panel 5W max fully loaded Internal Fuse 3 15A Ingress Protection I...

Страница 9: ...be reset before restarting the system CO2 High If the concentration of CO2 in the air is at alarm level relevant detector required the LED will illuminate and the gas supply is isolated Intake Fan Und...

Страница 10: ...tem in good working order follow these basic principles Remove any dust debris from the outer enclosure regularly using a slightly damp cloth Never use detergents or solvents to clean your gas detecti...

Страница 11: ...Installation Operation Maintenance Manual Merlin1250X Rev 1 11 ENGINEERING NOTES Blank Page...

Страница 12: ...system owner or system user Date of Installation Installation Location Organisation Stamp Signature of the installer CONTACT US AGS Head Office Tel 727 608 4375 Fax 727 538 4237 info americangassafety...