TANK MATERIAL  

 

Tank Shell Material Thickness 

Model 

Primary Shell 

Secondary Shell 

Thickness Range 

HFV50 

12 GA 

12 GA 

 

12 GA: 

2.46mm (MIN) to 

2.85mm (MAX) 

 

10GA: 

3.20mm (MIN) to 

3.61mm (MAX) 

 

3/16”: 

4.47mm (MIN) to 

5.03mm (MAX) 

 

HFV100 

12 GA 

12 GA 

HFV300 

12 GA 

12 GA 

HFV500 

12 GA 

12 GA 

HFV1000 

12 GA 

12 GA 

HFV8500 

10 GA 

12 GA 

HFV11000 

10 GA 

12 GA 

HFV15000 

3/16” 

10 GA 

HFV25000 

3/16” 

10 GA 

 

 

 

VFV2500 

12 GA (SHELL),  

10GA (ROOF & FLOOR) 

12 GA (SHELL), 

10 GA (FLOOR) 

VFV5000 

10 GA (SHELL & ROOF), 

3/16” (FLOOR)  

10 GA (SHELL) 

3/16” (FLOOR) 

 

 

 

RFV 1100 

12 GA 

12 GA 

RFV 2400 

12 GA 

12 GA 

RFV 5000 

10 GA 

10 GA 

Table 1

 

 

Steel Specification:  

a.

 

All gauge sheet: ASTM A1011 Commercial Quality 

b.

 

All plates: G40.21.44W 

 

Pipe Specification: ASTM A53 Grade B Schedule 40 

Flange Specification: ASTM A105 #150 

Threaded Fitting Specification: ASTM A105 (3000#) or ASTM A865 (150#) 

  

 

DESIGN TEMPERATURE: 

 

The tank is designed to operate in Canadian Outdoor Temperatures.  

 

NOTE: At elevated temperatures, increased risk of corrosion or flammability may occur. 

Westeel recommends consulting with a materials / Fire Code expert for these applications. 

The tank purchaser must rely on the expertise of their own consultants when determining the suitability of 

a ULC storage tank for conditions other than ambient. 

 

 

Содержание FUEL-VAULT

Страница 1: ...GRAL CONTAINED DUAL WALL TANK OWNERS AND USERS MANUAL READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE INSTALLATION AND USE OF TANK Contact Info www westeel com Toll Free 1 800 665 2099 Email l...

Страница 2: ...Warranty 4 DISCLAIMERS 4 EXTERNAL CORROSION 4 INTERNAL CORROSION 4 GENERAL 5 KNOW YOUR TANK 6 TANK SERIAL NUMBER 6 TANK FUEL COMPATIBILITY 6 TANK MATERIAL 7 DESIGN TEMPERATURE 7 CORROSION ALLOWANCE 8...

Страница 3: ...of which are found to Westeel s satisfaction to be defective Westeel is not responsible for direct indirect special consequential or anyotherdamagesof anykind including personal injury to any individu...

Страница 4: ...ory or otherwise are subsumed and replacedby it and are of no legal effect If any provision of the warranty is held by a court of competent jurisdiction to be void or unenforceable in whole or in part...

Страница 5: ...ner user to check for foreign debris inside the tank at the time of deliveryas well as before commencing use of the goods and regularly during use of the goods Moisture can cause irreparable damage to...

Страница 6: ...Y WARRANTY CLAIMS A PICTURE OF THE ULC NAMEPLATE ALONG WITH THE SERIAL NUMBER OF THE TANK MUST BE PROVIDED TANK FUEL COMPATIBILITY All steel tanks are compatible with all blends of fuels meeting ASTM...

Страница 7: ...RFV 2400 12 GA 12 GA RFV 5000 10 GA 10 GA Table 1 Steel Specification a All gauge sheet ASTM A1011 Commercial Quality b All plates G40 21 44W Pipe Specification ASTM A53 Grade B Schedule 40 Flange Spe...

Страница 8: ...Liquid 1 Cleaned for all contamination 2 Surface Blast to SSPC SP 6 commercial Grade NACE 3 3 Apply D T M Two Component Acrylic Urethane White Gloss paint a 3 0 5 0 Total DFT WCS PC1 2 Powder 1 All Ex...

Страница 9: ...required 2 Order necessary replacement parts immediately to ensure that installation will not be held up by missing parts All parts will be charged for and credit will be issued by the party at fault...

Страница 10: ...nd moving of the materials 5 Tanks shall be carefully handled to prevent damage to the tank coating The use of nylon straps is preferred to prevent damage to the tank coating When using cables or chai...

Страница 11: ...ergo the appropriate inspection prior to relocation 2 The primary tank shall be inspected monthly for the presence of water at the lowest possible points inside the primary tank Remove any water found...

Страница 12: ...Tank Installation and Maintenance decal affixed to the tank...

Страница 13: ...tank designs that are installed in a manner that would allow an accidental overfill of the normal vent pipe This is not to be considered as a condition NOTE ULC tanks must be operated with a minimum...

Страница 14: ...ULC standards and the tank user or installer should refer to electrical codes governing the installation of electrical equipment attached to the tank Use of a dielectric sealant not provided by Westee...

Страница 15: ...3 Care should be taken when placing a tank close to buildings to ensure that snow does not build up on the tank The buildup of snow and ice may also cause failure of the tank emergency and normal ven...

Отзывы: