APPLICATION

DESCRIPTION

APPROVALS AND CERTIFICATES

Drawing 1. Construction

3-way rotary valves are mainly used as mixing valves, where the desired temperature is achieved by mixing the hot 

water from the boiler and the cold water from the system return, in appropriate proportions. 3-way valves can also 

be used as switching or separating valves, when changing the flow direction between two outlets (e.g. central he-

ating and domestic hot water preparation) is required. The 3-way ARV ProClick valves can be utilized in cooling and 

d.h.w. systems.

3-way rotary mixing valves ARV ProClick with inner threads are made out of brass. The connections have octagonal sha-

pe. The valves have knobs for manual operation and rotation angle limiters. The scale on top of the knob is printed with 

“from 0 to 10” on one side and on the other “from 10 to 0”, so one can mount the valve in various positions. The thicker 

knob part shows the sleeve position inside the valve. The knob itself is made from a non-slip material. The durable 

plastic parts under the knob are used to mount the ARM ProClick actuator on the valve. The ProClick system does not 

require any tools. ARV ProClick valves require low torque.

The rotary mixing valves ARV ProClick comply with the Pressure Directive PED 2014/68/EU and according to artic-

le 4.3 (sound engineering practice) must not wear the CE mark.

DN15 ÷ DN25

DN32

DN40 ÷ DN50

3-way rotary mixing valves 

ARV ProClick 

 

Art.-No 13 381 10, 13 388 10, 13 382 10,  

             13 384 10, 13 385 10, 13 386 10,  

             13 387 10

 INSTRUCTION MANUAL

953.001.0063 1

TECHNICAL DATA

Parameter / piece

Value / description

Working temperature

5-110˚C

Working pressure

max 10 bar

Differential pressure

max 1 bar

Body

brass CW617N

Sealing

EPDM

Leak rate (

Δ

p=100 kPa)

max 0,2% for DN15-DN32

max 0,5% for DN40-DN50

Rotation angle

90˚

Required torque

max 0,5 Nm for DN15-DN25, max 2 Nm for DN32,  

max 3 Nm for DN40-DN50

Glycol concentration

max 50%

MOUNTING

Notice! 

The flattening on the spindle of the valve and on the adapter mounted on it (

Drawing 1

) indicates the posi-

tion of the sleeve inside the valve (

Drawing 2

). 

The ARV ProClick valve is delivered with mounted knob, blue ring and scale. Not to damage the plastic elements,  

we suggest to disassemble the scale, knob and blue limiting ring before mounting the valve. These parts are moun-

ted on latch. When having trouble with dismounting the knob, one can gently pry it up with a flat screwdriver.  

Next mount the valve in the system. When the valve is in place, set it and assemble the plastic components,  

as follows:

1. 

Determine the working range of the sleeve inside and the closing direction (

Drawing 2

). First determine  

the hot and cold water inlets after the valve is mounted. The sleeve should rotate by 90˚ between these two 
inlets. Next set the sleeve exactly in the middle between the hot and cold water inlet (

Drawing 2

). Learn also 

the direction of closing (closing the hot water inlet) and opening (opening the hot water inlet) of the valve.

2. 

Choose the right side of the scale. A double-sided scale is delivered with the ProClick valves. It is printed “from 
0 to 10” on one side and “from 10 to 0” on the other. Apply the scale to the vale and choose the side on which 
“0” will coincide with the cold water inlet and simultaneously “10” will coincide with the hot water inlet,  
as shown on 

Drawing 2

You can follow also another simple rule: 
- if the valve is closed turned right (clockwise) choose the scale “from 0 to 10”, 
- if the valve is closed turned left (counter-clockwise) choose the scale “from 10 to 0”.

3. 

Put on and latch the blue limiting ring on the valve, which was set according to point 1. The indicator should 
point directly on the middle of the sleeve inside the valve (

Drawing 3a

 or 

3b

), as well as the flattening on the 

spindle and adapter. The indicator should find itself between the hot and cold inlets.

4. 

Lock the knob on the adapter. It fits only in one position (

Drawing 4

).

5. 

Put the lid with the chosen scale (

Drawing 5

) on the knob. To lock the lid first put the smaller inset in the hole 

inside the knob and then press the lid down.

6. 

Check if the valve works properly.

valve body DN40-50

 valve body DN32 

valve body DN15-DN25 with plastic part for 

ProClick actuator 

adapter with f attening, for 

ARM ProClick actuators 

adapter f xing screw  

knob with a thicker part showing the valve sleeve position

double-sided scale

limiting ring with indicator

f attening on the valve spindle

AFRISO Sp. z o.o.