AFRISO ARM ProClick Скачать руководство пользователя страница 1

Electric actuators ARM ProClick

Art.-No 14 323 10, 14 343 10, 14 343 11

NOTICE!

This instruction manual is also available on www.afriso.pl.

MOUNTING ON AN ARV ProClick VALVE

The 

ARM ProClick 

valve is factory set on 50% (position “5” on the scale). To mount the actuator pro-

perly on the valve, the valve must also be set on 50%.

WARNING!

The product may only be mounted, commissioned and disposed of by quali-

fied, specially trained staff.

Alterations performed by unauthorized staff may cause a threat and are for-

bidden for safety reasons.

The product is powered by 230 V AC voltage. This may cause severe injuries  

or death.

Do not let the product go into contact with water.

Before mounting the product please read the manual of the mixing valve.

APPLICATION 

SCOPE OF DELIVERY

INSTRUCTION MANUAL

Electric actuators 

ARM ProClick 

are designed to operate on 3-/4-way rotary mixing valves, which requ-

ire a maximum turning torque of 6 Nm. They have a turning angle of 90˚. The 

ARM ProClick

 actuator 

should be connected to a 3-point controller with a 230 V AC supply voltage. One can operate the actu-

ator also manually using the knob. The 

ARM ProClick

 actuators are mainly used to mix two streams via 

the mixing valve, to obtain a set temperature on the outlet connection of the valve.

One can mount the actuator in 4 positions on the valve. The blue ring with indicator must point 

upwards. If it does not, pull off the knob and blue ring. Then mount it back with the indicator pointing 

upwards. The blue ring has a special hole inside to lift it with a flat screwdriver. 

1. Take off the knob and blue limiting ring from the 

ARV ProClick

 valve (

Drawing 1

). To do this, just   

    pull the parts along the spindle axis. The knob construction allows to lift it with a flat screwdriver.  

    There are special holes on two sides of the knob.

2. Set the valve on 50%, so that the sleeve inside the 3-way valve will be right in the middle between  

    the hot and cold inlets (

Drawing 2

 or 

Drawing 3

Drawing 5

) or just in the middle of the outlet  

    connections in a 4-way valve (

Drawing 4

Drawing 6

).

3. Slide the actuator on the mixing valve, so that the 4 pins of the 

ProClick

 mechanism find themselves  

    in the appropriate holes on the back of the actuator and the mechanism locks on them (

Drawing 7

).  

    The 

ProClick

 mechanism requires no tools.

4. Insert the double-sided scale in the correct position according to the opening/closing direction  

    (“from 0 to 10” or “from 10 to 0). Follow the rules below:

     - if turning the knob right (clockwise) closes the valve, choose the scale “from 0 to 10”,

     - if turning the knob left (counter-clockwise) closes the valve, choose the scale “from 10 to 0”.

The blue indicator should point at “5” on the scale. If not, please return to point 2.

5. Connect the actuator to the controller according to the scheme  

    (

Drawing 10

). The electric cable of the actuator can be detached. 

    This makes mounting and electrical connections easier. To take  

    out the plug, one must lift the lever of the cover and slide it out  

    (

Drawing 11

). Next detach the plug (

Drawing 12

). The plug fits  

    into the socket only in one position.

Drawing 1. View on the 

ARV ProClick

 valve with removed knob

Drawing 7. Mounting the 

ARM ProClick

 actuator

Drawing 9. View on two sides of the scale

Drawing 10. Electrical scheme

Drawing 11. Detaching the cover

Drawing 12. Electrical plug

Drawing 8. Possible mounting positons

ARV ProClick 

valve

4 pins of the 

ProClick 

mechanism

flattening on the adapter

pushbutton of the 

ProClick

 mechanism

ARM ProClick

 actuator

ring with indicator

double-sided scale

knob

     Drawing 2. 3-way, position 1           Drawing 3. 3-way, positon 2                 Drawing 4. 4-way

Drawing 5. 3-way    

 

 

       Drawing 6. 4-way

1. Electric actuator 

ARM ProClick

 with a knob, double-sided scale (“from 0 to 10” and “from 10 to 0”)   

    and an electric cable with plug.

2. Mounting set for 

ARV

 valves without 

ProClick

 system (first generation) – 

not included in Art.-No 14 343 11

.

3. Instruction manual.

953.001.0061 1

AFRISO Sp. z o.o.

Szałsza ul. Kościelna 7 

42-677 Czekanów 

Poland 

www.afriso.pl

Customer service

 

Tel. +48 330 33 55 

Fax: +48 330 33 51 

[email protected]

mixed 

 

stream

mixed 

 

stream

mixed 

 

stream

hot 

stream

hot 

stream

cold 

stream

cold 

stream

closing 

direction

closing 

direction

Connect the controller to the power supply according to the producer’s manu-

al or guidelines.

Connect the neutral wire N direct to the mains supply or to the controller,  

if it gives such a possibility.

3-point 

controller

actuator 

wires

1

2

4

3