Mounting and commissioning
12
Unimes E
6.2
Mounting the wall bracket for the remote indicator
Mount the wall bracket to the wall where you want to position
the remote indicator using the enclosed screw (4 x 30 mm) and
a dowel, if required (6 mm).
6.3
Adjusting the float
A free connection G1½ or G2 is available at the tank.
The float wire has three lead seals. Lead seal 1 is located at the end,
lead seal 2 is located 15 cm higher. The moving lead seal 3 is lo-
cated between these two lead seals.
1
Lead seal 1: fixated
2
Lead seal 2: fixated
3
Lead seal 3: moving
Fig. 2: Float wire
Tank without manhole or flange connection piece
Push the float up to lead seal 2 and press lead seal 3 together
to fixate the float.
Tank with manhole or flange connection piece
1.
Deduct the excess length of the manhole or the flange connec-
tion piece with reference top the wire length from probe 2 to-
wards probe 1.
2.
Mark the point, push the float up to the mark and press lead
seal 3 together to fixate the float
6.4
Adjusting the tank height at the direct indication gauge
The direct indication gauge is factory-adjusted to the maximum
height which corresponds to a tank height or diameter or 200 cm.