SE-Power FS STO-manual vers. 1.6 en.12.08.2015
27
Time
Description
Value
T_STO-A/B_OFF
STO-A/B
– Switching time from High to
Low
Section 9.1.4, Table 21
T_STO-A/B_ON
STO-A/B
– Switching time from Low to
High
Section 9.1.4, Table 21
T_DIN5_LOW
Time for which the DIN5 must be Low before
STO-A/B is switched on again
0ms
T_DIN5_SU
Time for which the DIN5 must be Low
after switching on STO-A/B again and
status change of the STO module
20ms
T_DRIVE_V
Delay of the SE-Power FS
0 … 10ms
T_BRAKE_V_ON Switch off delay of the holding brake
Dependent on the brake
1)
T_BRAKE_V_OFF Switch on delay of the holding brake
Dependent on the brake
2)
1)
Physical delay until the brake closes.
2)
Minimum time: Physical delay until the brake opens. This time can be parameterised in
the servo drive via a large value.
Table 5: