NOTE
EtherCAT cabling
When constructing the EtherCAT network, follow the advice of the
current literature or the following information and instructions without
fail, to get a stable and fault-free system. In case of cabling not
having been done properly, faults can occur on the EtherCAT during
operation, which can result in the servo controller getting switched
off with an error message, for reasons of safety.
7.1.7 Bus cable for EtherCAT
Only use Ethernet cables to connect EtherCAT devices which comply at least with
category 5 (CAt5) according to EN 50173 or ISO/IEC 11801. EtherCAT uses 4 leads
of the cable for signal transmission.
The following cables of the company Beckhoff should be used for the EtherCAT
connection:
EtherCAT cable M12 plug, straight, d-coded, 4 pole M12 plug, straight, d-coded, 4 pole
Beckhoff EtherCAT cable
EtherCAT cable
Order No.
Length in m
ZK1090-6161-0005
0,5
ZK1090-6161-0020
2
ZK1090-6161-0025
2.5
ZK1090-6161-0050
5
ZK1090-6161-0100
10