HUMIDITY AND TEMPERATURE 
AMBIENT AIR SENSOR 

INSTALLATION AND OPERATING INSTRUCTIONS

ENGLISH

S-RH/T

Содержание S-RH

Страница 1: ...TF5710_B v1 web HUMIDITY AND TEMPERATURE AMBIENT AIR SENSOR INSTALLATION AND OPERATING INSTRUCTIONS ENGLISH S RH T ...

Страница 2: ... calibrated The user can choose between two outputs 0 10 V or PWM APPLICATIONS HVAC Demand Controlled Ventilation fan control damper control air conditioning control Indoor Air Quality level indicator etc BMS Indoor Air Quality level indicator Indoor Air Quality monitoring etc Specially suitable for rooms where variations of humidity or temperature are relatively important and can be used to drive...

Страница 3: ...stallation and electrical connections must be carried out by a qualified technician according to the manufacturer s instructions and in compliance with the characteristics of the product Before carrying out any operation on the appliance unplug or disconnect it from the power supply and ensure it can not be accidentally restored Power cable modification or replacement must only be carried out by q...

Страница 4: ...wing recommendations keep the sensor away from any direct solar radiation keep the sensor away from draughts door window supply etc avoid placing the sensor in dead zones behind curtains furniture keep the sensor away from heat sources and from occupants if the sensor is located at the ceiling keep it away from any air supply unit C D B A C D B A ...

Страница 5: ...V PWM output 2 wires PWM RH n 1 PWM Temp n 1 PWM Temp n 2 PWM RH 0 10 V output 2 wires 10 V RH 10 V Temp 0 V PWM output RH 0 0 RH 100 100 RH PWM output T 0 0 C 100 50 C 0 10 V output RH 0 V 0 RH 10 V 100 RH 0 10 V output T 0 V 40 C 10 V 125 C PWM and 0 10 V output can be use simultaneously 5 Clip the electronic card B with the plastic protection D inside the base C 6 Put the cover A on the base C ...

Страница 6: ...esive tapes and stickers or out gassing packaging material such as bubble foils foams etc shall be avoided Manufacturing area shall be well ventilated Never connect the 12 VDC supply to S1 or S2 and the 0 V supply to GND otherwise S1 and S2 output will be crashed A protection is implemented to protect the product in case of wrong connection when the following mistakes occur Inversion of the supply...

Страница 7: ... 0 3 C Measuring time interval 60 s Supply voltage 12 V DC 10 Average power consumption 15 mA Peak current max 1 A use for fuse sizing Enclosure Protection IP 20 Storage conditions 10 50 C 0 60 RH PWM digital output Output data 0 to 100 0 0 RH 100 100 RH 0 0 C 100 50 C Voltage S1 and S2 12 VDC 10 Frequency S1 and S2 1 KHz 0 10 V analog output Output data 0 to 10 V 0V 0 RH 10 V 100 RH 0V 40 C 10 V ...

Страница 8: ...X 3 FRANCE www aereco com MAINTENANCE Check frequently that the product is clean and remove dust if needed No calibration required Caution Never touch the sensing element otherwise the detection may be damaged WARRANTY The product is guaranteed two years Its validity is submitted to conformed installation use and maintenance ...