Electronic Control "QRCE" User Manual
firmware 0.27
Rev.09
EN 13/ 23
ENG
5.4.
Night (
)
Night
Night mode enable
Off-On
Start time night mode
22:00
End time night mode
07:00
Fan speed
50%
Night Cooling set point
26.0°C
Night Heating set point
20.0°C
5.5.
Service (
)
password
Plant configuration (password= 1)
Defrost parameter (password= 1)
Fan parameter (password= 1)
Heating / cooling parameter (password= 1)
Test mode
par 5.12
OEM parameter (password= OEM)
Function status
5.6.
Input/output (
)
input / output visualization
Return air temperature
°C
Supply air temperature
°C
Fresh air temperature
°C
Exhaust temperature
°C
Supply air pressure sensor
Pa
CO
2
sensor
ppm
Cooling / changeover valve status
%
Exhaust fan actual speed
%
Supply fan actual speed
%
Electric heater status (post-heater)
%
Electric heater status (pre-heater)
Off/On
By-pass status
Off/On
Software version
5.7.
Alarm history (
)
(password)
Alarm position
0-19
Alarm date (day.month)
0.00
Alarm time
00:00
Alarm code
(When display shows
no alarm)
9999
Alarms number
0