13
Installer menu
1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating
It allows to set the Bypass operation parameters
Press Ok to enter.
Use
or
to choose “Desired Temperature”, “Tmax Free Heating”, “Tmin Free
Cooling”
For definitions see “Bypass” (paragraph 7.3)
Press Ok to select.
The setting ranges are:
Desired Temperature: 15°C ÷ 30°C
Tmax Free Heating: 25°C ÷ 30°C
Tmin Free Cooling: 15°C ÷ 20°C
Use
or
to increase or decrease the temperature.
Press Ok to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) are:
Desired Temperature: 23°C
Tmax Free Heating: 28°C
Tmin Free Cooling: 18°C
Installer menu
1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating
To be selected only in case an external heating element (not supplied) is present.
Press Ok to enter.
Use
or
to choose NO/PRE/POST.
Press Ok to select.
The factory setting (DEFAULT) is NO.
NO: HEAT output (Fig. 5.g) is never activated
PRE: the heating element is intalled at “intake air side” (Fig. 7.a - ).
HEAT output (Fig. 5.g) is activated and heating icon displays on LCD when
T21 < HEATING THRESHOLD (Fig. 7.a)
POST: the heating element is intalled at “supply air side” (Fig. 7.a - ).
HEAT output (Fig. 5.g) is activated and heating icon
displays on LCD when
T11 < HEATING THRESHOLD (Fig. 7.a)
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
This option displays only if “Heating” is set on PRE or POST.
It allows to set the heating threshold in case of PRE or POST heating.
Press Ok to enter.
Use
or
to set the temperature.
Press Ok to select.
Setting ranges:
PRE: -20°C ÷ 0°C
POST: +15°C ÷ +25°C
The factory settings (DEFAULT) are:
PRE:-10°C
POST:+20°C
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
To be selected only in case an external dehumidifier (not supplied) is present.
Press Ok to enter.
Use
or
to choose NO or YES.
The factory setting (DEFAULT) is NO.
The DH relay output is activated when the HY input is activated (Fig. 5.g) and the icon
is displayed.
Note: in case dehumidifier is installed, the BST input (Fig. 5.g) is used as alarm output.
A
C
Содержание QR280ABP
Страница 22: ...22 NOTE ...
Страница 23: ...23 NOTE ...