OPERATION 
Making Measurements with the AC Current Probe Model MN113 

• 

Connect the terminals to the 2 V range of your DMM or instrument. The MN113 has a ratio of 10:1. This 
means that for 10 A AC in the conductor around which the probe is clamped, 1 V AC will come out of the 
probe leads to your DMM or instrument. The output is 100 mV AC per Amp AC. Select the range on your 
DMM or instrument which best corresponds to the measured current. If the magnitude is unknown, start 
with the highest range (2 V AC) then work down until the appropriate range and resolution is reached. 
Clamp the probe around the conductor. Take the reading on the meter and multiply it by 10 to obtain the 
measured current. (e.g., 59 mV reading: 59 x 10 = 590 mA or 0.59 A). 

Meter Reading 

10 mV 

120 mV 

1200 mV 

Measured Value 

100 mA = 0.1 A 

1200 mA = 1.2 A 

12000 mA = 12.0 A 

• 

For best accuracy, avoid if possible, the proximity of other conductors which may create noise. 

Tips for Making Precise Measurements 

• 

When using a current probe with a meter, it is important to select the range that provides the best 
resolution. Failure to do this may result in measurement errors. 

• 

Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air gaps 
between the jaws, increasing the phase shift between primary and secondary. It is very critical for power 
measurement. 

MAINTENANCE: 
Warning

 

• 

For maintenance use only original factory replacement parts. 

• 

To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so. 

• 

To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into the 
probe 

Cleaning 

To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times. 
Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine 600) 
to avoid scratching the jaw, then gently clean with a soft oiled cloth. 

REPAIR AND CALIBRATION 

You must contact our Service Center for a Customer Service Authorization number (CSA#). This will ensure 
that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# on the 
outside of the shipping container. If the instrument is returned for calibration, we need to know if you want a 
standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus recorded 
calibration data).  

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

 

15 Faraday Drive 

 Dover, NH 03820 USA 

Tel: 

(800) 945-2362  (Ext. 360) 

 

 

(603) 749-6434  (Ext. 360) 

 

Fax: 

(603) 742-2346 or (603) 749-6309 

 [email protected] 
(Or contact your authorized distributor) 
Costs for repair, standard calibration, and calibration traceable to N.I.S.T. are available. 

NOTE: All customers must obtain a CSA# before returning any instrument. 

TECHNICAL AND SALES ASSISTANCE 

If you are experiencing any technical problems, or require any assistance with the proper use or application 
of this instrument, please call our technical hotline: 

(800) 343-1391 • (508) 698-2115 • Fax (508) 698-2118 

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

[email protected] 
www.aemc.com 

AC Current Probe 
Model MN113 

User Manual

 

 

DESCRIPTION 

The MN113 (Catalog #2114.99) is a high accuracy voltage output current probe for tight areas such as 
crowded wiring. Extends DMM AC measurements to 10A

AC

. The Model MN113 offers a 4mm banana 

jack. 

WARNING 

These safety warnings are provided to ensure the safety of personnel and proper operation of the 
instrument. 
•  Read the instruction manual completely and follow all the safety information before attempting to 

use or service this instrument. 

•  Use caution on any circuit: Potentially high voltages and currents may be present and may pose a 

shock hazard. 

•  Read the Safety Specifications section prior to using the current probe. Never exceed the 

maximum voltage ratings given. 

•  Safety is the responsibility of the operator. 

•  ALWAYS connect the current probe to the display device before clamping the probe onto the 

sample being tested. 

•  ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use. Replace 

any defective parts immediately. 

•  NEVER use the current probe on electrical conductors rated above 600V in overvoltage. Use 

extreme caution when clamping around bare conductors or bus bars. 

INTERNATIONAL ELECTRICAL SYMBOLS 

This symbol signifies that the current probe is protected by double or reinforced insulation. 
Use only specified replacement parts when servicing the instrument. 

This symbol signifies CAUTION! and requests that the user refer to the user manual before 
using the instrument. 

RECEIVING YOUR SHIPMENT 

Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your 
distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the 
carrier and notify your distributor at once, giving a detailed description of any damage. 

PACKAGING 

The AC Current Probe MN113 is shipped with this instruction manual and a product warranty and 
registration card. 

INSTRUMENT COMPATIBILITY 

The Model MN113 is compatible with any voltmeter, multimeter, or other voltage measuring instruments 
with an input impedance greater than 100 K

. To achieve the stated accuracy, use the MN113 with an 

voltmeter having an accuracy of 0.75% or better. 