ii: Fiber Dual Ended Set Reference
Mandrel Wrap for
Multi-Mode (if required)
Mandrel Wrap for
Multi-Mode (if required)
Up to 2 meters
No connectors in the paths
Tx
Rx
Tx
Rx
Main
Remote
Attach the single mode or multi mode fiber adapter
to the TestPro main and remote units.
Connect one end of a 2-meter reference cord to the
TestPro main unit’s Tx port and connect the other end
of that cord to the TestPro remote unit’s Rx port.
Connect another 2-meter reference cord to the
TestPro main unit’s RX port, and the other end of that
cord to the TestPro remote unit’s Tx port.
•
•
•
On the TestPro main screen select [Fiber Certification].
Select [Tools].
Select [Set Reference].
•
•
•
Note: Wait for 5 minutes for the fiber components to
warm up before performing the set reference. Doing
this will help to produce more stable & consistent
results.
Select [One Jumper] and then select [Set Reference].
Select [Ok] on the dialog box.
TestPro will start the set reference process. Once it is
complete, the set reference values will be displayed.
Select [Accept] to continue.
•
•
•
Note: For multimode the acceptable value is -24dBm
and higher and for single mode the acceptable value
is -4dBm and higher.
iii: Fiber Loopback Set Reference
Mandrel Wrap
for Multi-Mode
(if required)
2 meter reference
Tx
Rx
Attach the single mode or multi mode fiber adapter
to the TestPro main unit.
Connect one end of a 2-meter reference cord to the
TestPro main unit’s Tx port and connect the other
end of that cord to the TestPro main unit’s Rx port
forming a loopback connection.
•
•
On the TestPro main screen select [Fiber Certification].
Select [Tools].
Select [Set Reference].
•
•
•