APPLICATION HINTS FOR THE AUXILIARY TERMINALS

                                                                                                                                                   

(A) TAMPER N.C.

The tamper switch is Normally Closed while the 

keypad is secured on gang box. It is open when 

the keypad is removed from the gang box. To 

prevent sabotage, connect these terminals in 

series with a 24 hour N.C. protection zone of an 

alarm system if required. 

(B) OUTPUT 2 (DK-2891A ONLY)

( i ) Shunting an N.C. Zone

Put Output 2 jumper to N.O.
Use the Normally Open (N.O.) output contact to shunt a Normally Closed (N.C.) protection zone of an 

alarm system.
Set output contact to Start / Stop Mode (Programming Option 52, Output Mode=0).

Use the (N.O.) or (N.C.) output contact to make arm-disarm control of an alarm system.
Consult your alarm control panel manual for the appropriate output contact for arm-disarm control.
Usually set output 2 to Momentary mode (Programming Option 521, Location 52, Output Mode=1) for 

multi station systems and Start / Stop mode (Programming Option 520, Location 52, Output Mode=0) 

for single station systems.

( ii ) Alarm System Arm-Disarm Control



Remark:

The suffix letter “S” stands for standard version and “A” stands for advanced version. The advanced 

version possesses the standand features and also provides Wiegand and RS-232 data outputs for the 

custom projects with external controller and PC.

 Please contact your local agent for the optional devices.

OPTIONAL DEVICES FOR SYSTEM EXPANSION

The Optional Decoders Available for Split-decoded Operation

DA-2800

 – Full Feature Decoder with RF Remote Control

DA-2801

 – Full Feature Decoder

The Auxiliary Reader / Keypad Available for Multi-station Operation

AR-2802S or A

 – EM Card Reader

AR-2806S or A

 – EM Card Reader with Digital Keypad

AR-2807S or A

 -- EM Card Reader with Digital Keypad

AR-2809S    

    

 

-- EM Card Reader with Digital Keypad

2. PINK

1. GREY

4. ORANGE

4. ORANGE

3. PURPLE

3. PURPLE

Содержание DK-2891A

Страница 1: ...DK 2891 User Manual MK II FOR ELECTRIC LOCK AND SECURITY SYSTEMS VANDAL RESISTANT BACK LIT WEATHERPROOF RFID ACCESS CONTROL KEYPAD DK 2891B DK 2891A...

Страница 2: ......

Страница 3: ...freshing Master Code Super User Code Operation and Functions of The Super User Code Common User Codes for Output 1 2 User Codes Card For Output 1 2 Examples Programming And Operation Visitor Codes For...

Страница 4: ...ne Lock APPLICATION EXPANSIONS The Axiliary Readers Keypad The Split decoders 1 Dual station Access Control Door Lock 2 Multi station Access Control Door Lock 3 Split decoded Access Control Door Lock...

Страница 5: ...mes with Output 1 for door strike and Output 2 for door bell activation DK 2891A Output Relay 1 2 Controlled by User Codes Cards DK 2891B Output Relay 1 Controlled by User Codes Cards Output 2 by Bell...

Страница 6: ...ct your local agent for the optional devices OPTIONAL DEVICES FOR SYSTEM EXPANSION The Optional Decoders Available for Split decoded Operation DA 2800 Full Feature Decoder with RF Remote Control DA 28...

Страница 7: ...ime limit Timings for Code Entry and Card Reading 10 seconds waiting for next digit entry 30 seconds waiting for code entry after card reading The Timer 1 99 999 Seconds Over 24 Hours possible Program...

Страница 8: ...stallation Check carefully all the wirings are correct before applying power to the system for testing 1 Prevent Interference The EM Card reader is working at the frequency of 125Khz Installation prec...

Страница 9: ...r is separated from the box Connect this N C terminal to the 24 hour protection zone of an alarm system if necessary 3 4 OUTPUT 2 Version A OR DOOR BELL Version B A relay output dry contact with maxim...

Страница 10: ...r Start Stop toggle mode or Momentary timing mode See programming Location 51 for the details THE ON BOARD LED INDICATORS MAINS AMBER It flashes in Standby It shows the system status in synchronizatio...

Страница 11: ...wner s selection of security level See programming Location 10 20 1 EM Card Only Operation Media 1 A general way for access control just simply read a card to open the door Security level is moderate...

Страница 12: ...ogram the user codes and cards smoothly and to trace them afterwards in the future Here is a suggested format of the list List of Users See page 19 22 for reference 5 EM Card Proprietary Secondary Use...

Страница 13: ...e Mains LED amber is ON after the keypad confirms it in programming mode with 2 beeps d DO NOT turn off power while the keypad is in programming mode Otherwise it may cause error to the data in memory...

Страница 14: ...e program of the desired values are necessary DIRECT ACCESS TO PROGRAMMING MODE WITH DAP CODE 2 8 2 8 In case the Master Code is forgotten apply the following procedures precisely to set keypad into p...

Страница 15: ...ry DK 2891A only 5 6 Start Stop Time Nil User Program Required 5 5 System Real Time Clock Nil User Program Required 9 4 Operation Modes Code 0 Keypad Mode 6 0 Personal Safety Lock out Code 1 10 False...

Страница 16: ...in Split decoded operation 2 1 3 Press key once Two beep confirms the entry Example Set a Master Code 2 2 3 3 SUPER USER CODE Location 02 The Super User Code has TWO functions It is prepared to opera...

Страница 17: ...is Un locked Start Stop in Toggle NOTE 3 Pause The Scheduled Daily Inhibition for Output 1 Temporarily Disable The Inhibition The scheduled inhibition can be programmed and applied to Output 1 with da...

Страница 18: ...door lock control is inhibited all the User Codes Cards for it become invalid and those people holding the User Code or Card are refused This function Starts Stops in toggle with the following code en...

Страница 19: ...mon User Code alone can NOT operate the Outputs directly LOCATIONS COMMON USER CODE VALIDATION 1 LOCATIONS Location Stores The Common User Code for Output 1 Location Stores The Common User Code for Ou...

Страница 20: ...Cards in User Group 2 Output 2 4 CARD USER CODE Read EM Card or key in User Code into each assigned User ID 5 VALIDATION Press the key once Two beep confirms the entry NOTE a The Secondary User Code i...

Страница 21: ...a Read the EM card Two beep confirms the card is read and Output 1 activates 2 Example 2 Private User Code Only i Programming a b c d e a The Private User Code is programmed for operating Output 2 b T...

Страница 22: ...h the key Output 1 activates Read Card Read Card 4 Example 4 EM Card Common User Code i Programming a b c d e a The card is programmed for operating Output 1 b The operation medium is EM Card Common U...

Страница 23: ...in 5 that is the Command Code for making a deletion c Read the EM card One beep confirms the reading Read the Card only also makes a valid deletion to the Card working with the Common User Code or the...

Страница 24: ...tem automatically after use Time Limit in Hour s 4 VISITOR CODES NOTE All Visitor Codes will be cleared after power down to prevent extension confusion of their valid time limit 5 VALIDATION Press key...

Страница 25: ...is valid for three hours a b c d e a Visitor Code Programming b The Visitor ID c Valid for 3 Hours d The Visitor Code e Example 3 Delete a Visitor Code from Vistor ID 02 in the memory a b c a Visitor...

Страница 26: ...an User Code and or Card is entered read the output Stops when an User Code and or Card is entered read again Seconds Momentary Default Momentary 5 Seconds The output can be set in Momentary Mode with...

Страница 27: ...e setting and the clock starts to count in 24 hour basis from the programmed current time Programming Examples a Set the current time of 10 30 AM to the keypad b Set the current time of 6 45 PM to the...

Страница 28: ...on 2 START TIME Set the real time inhibition starting time in Hour and Minute The allowed time figure is 00 00 23 59 The starting time is based on 24 hours daily with the first two digits for hours an...

Страница 29: ...r Code Programming and Operation Examples i Set the starting and stopping time for the real time inhibition period a Set Inhibition Period from 12 30 PM today 1 30 PM same day for lunch time b Set Inh...

Страница 30: ...d locks during 60 seconds Default Selection of after 5 to 10 successive Card User Code trials the keypad locks during Example Release the lock up Disappearance of all the above lock up securities 3 VA...

Страница 31: ...ION Key in Location 2 FUNCTION MODES FOR PACIFIER TONES Pacifier Tone is the Beep Tones from the keypad which include the tones of Successful Key entry 1 beep and the Unsuccessful User Code Card entry...

Страница 32: ...d the flashing light of the status LED the amber LED is annoying during standby especially at the night time The standby flashing can be ON OFF with the setting here Standby Flashing ON Default The St...

Страница 33: ...it on its default values WHERE AND WHY GOING OUT NEEDS ATTENTION Examples for some areas may need an Intelligent Egress Button Hospital Some of the patients are not allowed to leave the ward without...

Страница 34: ...ergency case only It is usually closed and watched by guards The egress button of this keypad can be programmed to offer exit delay with warning beeps and even gives alarm output to trigger an alarm s...

Страница 35: ...activates the door is released when the delay time reaches CONFIGURATIONS VALIDATION DELAY TIME LOCATION or 2 4 3 1 Press and hold the Button No warning or alarm is given during the Egress Delay Good...

Страница 36: ...Entry confirmation Example 3 Set Egress Button in Momentary contact without delay This is the default setting a b c d a Egress function programming b Momentary contact without delay c Release door ins...

Страница 37: ...for multi station expansion Server Mode Server Mode sets the keypad to compatible with both the decoder for split decoded operation and the auxiliary readers keypads for multi station expansion A spl...

Страница 38: ...ing Mode Note If the Master Code is forgotten use the DAP Code to set the system into programming mode See DAP CODE 2828 in page 13 for the details 2 Change The Factory Set Master Code to Owner s Priv...

Страница 39: ...first Common code can be used for all the EM Cards in this operation mode REMARK If more User Codes and Cards are required for Output 1 repeat the procedures 3 4 5 or 6 above with other User IDs such...

Страница 40: ...R CODE 4 8 Digits CODE1 CODE2 CODE3 NIL 5 1 O P Mode for O P 1 OUTPUT MODE TIME 0 Start Stop 1 99999 Seconds START TIME 00 00 23 59 STOP TIME 00 00 23 59 5 6 Start Stop Times for Inhibition STOP TIME...

Страница 41: ...9 9 REFRESH CODE Refresh the system and set all its function back to default values All programmed data are cleared and back to the default values except the Master Code 2 8 2 8 DAP CODE Direct access...

Страница 42: ...quired if the electric lock is AC operated To avoid Electro Static Discharge from interfering with the operation of the keypad always ground the terminal of the keypad to earth 12V DC POWER SUPPLY AD...

Страница 43: ...he external keypad s A Split decoded system is also compatible with the auxiliary keypads for multi station operation It is a perfect system for overall higher security and user convenience The applic...

Страница 44: ...LLECTOR OUTPUT OPEN COLLECTOR OUTPUT 1A RELAY DRY CONTACTS FOR AUXILIARY CONTROL 1A RELAY DRY CONTACTS FOR AUXILIARY CONTROL 5A RELAY DRY CONTACTS FOR DOOR STRIKE OPEN COLLECTOR OUTPUT OPEN COLLECTOR...

Страница 45: ...rds and user codes like the master keypad Note Keep Operation Mode setting of the keypad in Keypad Mode default with Location COMMON GND POWER SUPPLY DATA I O BUS DK 2891 MASTER KEYPAD AR 2802 S or A...

Страница 46: ...ult with Location COMMON GND POWER SUPPLY DATA I O BUS DK 2891 MASTER KEYPAD AR 2802S OR AR 2802A AR 2802S OR AR 2802A AUXILIARY READER ELECTRIC LOCK COMMON GND POWER SUPPLY DATA I O BUS 6 5 4 3 2 1 L...

Страница 47: ...D 12 24V DC N O ELECTRIC LOCK 1N4004 CATHODE OUTPUT RELAY 1 N O Output for Fail secure Lock N C Output for Fail safe Lock N C OUTPUT 1 OUTPUT 2 OUTPUT 3 DIGITAL KEYPAD EGRESS BUTTON MORE EGRESS BUTTON...

Страница 48: ...tem Connection 6 5 4 3 2 1 LED DATA I O TAMPER N C 12 24V DC AR 2802 06 07 09 AUXILIARY READER OR KEYPAD READER DK 2891 SERVER ALARM O P KEY ACT O P N O COM N C N O COM N C N O COM N C TAMPER GND DOOR...

Страница 49: ...contact to shunt a Normally Closed N C protection zone of an alarm system Set output contact to Start Stop Mode Programming Option 52 Output Mode 0 Use the N O or N C output contact to make arm disarm...

Страница 50: ...PURPLE The output 2 of the DK 2891B is prepared for triggering a low power door chime DO NOT use it as a high voltage power path for a door bell The maximum power rating of the contact is 24V DC 1 Am...

Страница 51: ...It is open circuit when active N O Normally Open the contact is open circuit at normal status It is closed circuit when active TRANSISTOR OPEN COLLECTOR OUTPUT An open collector output is equivalent...

Страница 52: ...AEI PROTECT ON SYSTEMS LIMITED www apo hk com...

Отзывы: