7 Package, Transportation and Storage
IST6
Series (200K-600K) Modular UPS
User Manual
108
All rights reserved ©
Allis Electric
Co., Ltd.
7 Package, Transportation and Storage
This chapter mainly introduces the package, transportation and storage of the UPS.
7.1 Package
During packing, please pay attention to the place direction requirements. At the side of the package,
there is afraid of wet, handle with care, upward, stack layer limit, etc. alarm marks. And also,
the device model is printed on the package. At front of the package
AEC
the LOGO of
AEC
Company and device name is printed.
7.2 Transportation
During transporting, pay attention to the warning marks and avoid severe impact on the device. Place
the device according to the marked direction, which is to avoid damage the component. Any
inflammable, explosive, corrosive object is not allowed to shipping with the device. While midway
transportation, do not put the device in the open air. The device cannot suffer any rain, snow or liquid
material or mechanical damage.
7.3 Storage
When storing the device, place the device according to the marked direction. The package box should
be far away from ground for 200mm, and keep at least 500mm from wall, eat source, cold source,
window or air inlet.
Storage temperature: -25~55
℃
. If the device is transported or stored out of the storage temperature,
before installation and startup, put the device aside and let the device temperature recover to normal
range for more than 4h. In the warehouse, any inflammable, explosive, corrosive object or harmful
gas is not allowed, and also, strong mechanical shake, impact or magnetic field is forbidden. The
storage period of these requirements, generally, is 6 months. If the device stored more than 6 months,
it is necessary to check again. If the device is stored for a long time, please charge the battery every 3
months.