WISE-750 User Manual
36
C.1
Modbus Mapping
*The value includes 2-digit decimal. To retrieve the actual value, a division of 100
should be performed. For example, if the value read back is 1000, the actual value
would be 1000/100 = 10.
Table C.1: Modbus Mapping
Available
Mode
Tag Name
Type
Modbus Address
Remark
Ch0 Ch1 Ch2 Ch3 Global
Feature
Extraction
Rule-base Result INT 30001 30101 30201 30301
0: Pass, 1: Fail
MAX
INT 30003 30103 30203 30303
2 digit decimal*
MIN
INT 30005 30105 30205 30305
2 digit decimal*
MEAN
INT 30007 30107 30207 30307
2 digit decimal*
Peak
INT 30009 30109 30209 30309
2 digit decimal*
Peak To Peak
INT 30011 30111 30211 30311
2 digit decimal*
RMS
INT 30013 30113 30213 30313
2 digit decimal*
Intelligent
Inference Result INT 30015 30115 30215 30315
0: Pass, 1: Fail
Score
INT 30017 30117 30217 30317
2 digit decimal*
Score Threshold INT 30019 30119 30219 30319
2 digit decimal*
All
Running Mode
INT
30401
0: Datalogger,
1: Feature,
2: Intelligent
Running Status
INT
30403 0: Idle,
1: Running
Cycle Start/Stop INT
40401 0: Stop, 1: Start
Содержание WISE-750
Страница 1: ...User Manual WISE 750 Intelligent Vibration Sensing Gateway...
Страница 4: ...WISE 750 User Manual iv...
Страница 10: ...WISE 750 User Manual 4...
Страница 11: ...Chapter 2 2 Installation...
Страница 14: ...WISE 750 User Manual 8...
Страница 22: ...WISE 750 User Manual 16...
Страница 34: ...WISE 750 User Manual 28...
Страница 35: ...Appendix A A Specifications...
Страница 38: ...WISE 750 User Manual 32...
Страница 39: ...Appendix B B Algorithms...
Страница 41: ...Appendix C C I O Ranges...
Страница 43: ...37 WISE 750 User Manual Appendix C I O Ranges...