27
WISE-4000 User Manual
Chapter 2
P
roduct
Specifications
2.7
WISE-4050
2.7.1
I/O Specification
Digital Input
–
Channel: 4
–
Logic level
–
Dry Contact 0: Open
1: Close to DI COM
–
Wet Contact 0: 0~3 V
DC
or -3~0 V
DC
1: 10~30 V
DC
or -30~-10 V
DC
(3 mA min.)
–
All 4 channels should be configured to dry contact or wet contact in the
same time
–
Isolation: 3,000 V
rms
–
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
–
Keep/Discard Counter Value when Power-off
–
Supports Frequency Input Function (Maximum frequency 3 kHz)
–
Supports Inverted DI Status
Digital Output
–
Channels: 4
–
Open collector to 30 V, 500 mA max. for resistance load
–
Inductive loads require an external diode to eliminate back-EMF when the
DO is turned off
–
Isolation: 3,000 V
rms
–
On Resistance (R
DS(ON)
): 0.7
Ω
(max.) @ 500mA, 25°C
–
Supports 5 kHz Pulse Output
–
Supports High-to-Low and Low-to-High Delay Output
Содержание WISE-4000 Series
Страница 1: ...User Manual WISE 4000 Series IoT Ethernet I O Module ...
Страница 9: ...Chapter 1 1 Product Overview ...
Страница 17: ...Chapter 2 2 Product Specifications ...
Страница 42: ...WISE 4000 User Manual 34 2 9 4 Block Diagram Figure 2 35 WISE 4060 Block Diagram ...
Страница 43: ...Chapter 3 3 Hardware Installation ...
Страница 48: ...WISE 4000 User Manual 40 3 2 3 Stack Mounting Figure 3 8 Stack Mounting Figure 3 9 Finished Stack Mounting ...
Страница 51: ...Chapter 4 4 System Configuration ...
Страница 100: ...WISE 4000 User Manual 92 ...
Страница 101: ...Appendix A A I O Modbus Mapping Table ...
Страница 124: ...WISE 4000 User Manual 116 ...
Страница 125: ...Appendix B B REST for WISE 4000 Series ...