SNMP-1000-B1 User’s Manual

2

Chapter 1  Introduction

1.1  Introduction

Introduction

The SNMP-1000-B1 is a platform independent server and PC-system 
management controller that can detect the system operating conditions 
and notify the user to take necessary action to avert system failure. The 
SNMP-1000-B1 is web-enabled and supports multiple communication 
protocols. It provides a simple way to manage a number of remote serv-
ers, and also adds a dimension of reliability to critical applications such as 
computer telephony.

Powerful yet Easy to Use

The SNMP-1000-B1 can detect a wide variety of internal system condi-
tions, including temperature, voltage, fan rotation, power supply or CPU 
operations such as watchdog timer output.  Through its I2C interface it 
can monitor CPU temperature and voltages of Advantech's full-sized 
CPU cards. Depending on the alarm severity or user setup, it can generate 
several different alarm outputs, including SNMP trap, e-mail, pager mes-
sage, acoustic signal, system reset, or digital signal output.  Through the 
easy to use web-based user interface users can set the alarm criteria and 
select alarm outputs of each sense input independently to meet user 
requirements.  The board's battery backup enables the SNMP-1000-B1 to 
perform its alarm function even during total system power failure.

Web-enabled, No Driver Needed

The on-board 10/100 Mbps fast Ethernet adapter enables the SNMP-
1000-B1 to be connected to your existing network.  It supports multiple 
network protocols such as TCP/IP, SNMP, HTTP and Telnet, you can 
manage your systems simply using a web browser.  Since it works standa-
lone, no software driver is needed, thus eliminating the compatibility 
issues with different operating systems.

On-line Upgrade and Batch Setup

You can upgrade the firmware on-line by using the setup utility.  There is 
no need to go to remote site, disassemble the chassis to collect each 
SNMP-1000-B1 module for firmware upgrade.  The setup utility also 
supports "batch setup" function, which allows you to save a configuration 
and duplicate it to other modules.  This function saves your time when 
you setup a number of SNMP-1000-B1 modules.

    

Содержание SNMP-1000-B1

Страница 1: ...SNMP 1000 B1 Intelligent SNMP HTTP Remote System Manager User s Manual...

Страница 2: ...part of this manual may be reproduced copied translated or transmit ted in any form or by any means without the prior written permission of Advantech Co Ltd Information provided in this manual is inte...

Страница 3: ...ormance from your products So if you run into technical difficulties we are here to help For the most fre quently asked questions you can easily find answers in your product doc umentation These answe...

Страница 4: ...dealer for more details If you think you have a defective product follow these steps 1 Collect all the information about the problem encountered For example type of PC CPU speed Advantech products us...

Страница 5: ...1000 B1 startup manual One CD contains utility program SNMP MIB file and User s manual in pdf format SNMP 1000 E2B1 One SNMP HTTP system manager kernel board mounted on a carrier board for chassis One...

Страница 6: ...ervice department or your local sales representative immediately Also notify the carrier Retain the shipping carton and packing material for inspection by the carrier After inspec tion we will make ar...

Страница 7: ...4 System SMBus Connector CN3 11 2 2 5 10 100Base T LAN Connectors CN2 CN5 11 2 2 6 Temperature Sensor Connectors CN4 CN7 11 2 2 7 RS 232 Interface CN8 CN9 13 2 2 8 LCM Message Display Connector CN10...

Страница 8: ...32 3 3 12 View Active Alarms 32 3 3 13 View System Status 33 3 3 14 View Fan Speed 34 3 3 15 View Temperature Status 34 3 3 16 View Voltage Status 35 3 3 17 View Power Supply Status 36 3 3 18 View Dig...

Страница 9: ...Connector CN12 69 A 11 Backplane Voltage Input Connector CN13 70 A 12 Digital Input Connectors DI1 DI8 CN14 71 A 13 Digital Output Connectors DO1 DO4 CN15 72 A 14 Alarm Reset Connector CN17 72 A 15 LE...

Страница 10: ...SNMP 1000 B1 User s Manual x...

Страница 11: ...1 CHAPTER 1 Introduction...

Страница 12: ...coustic signal system reset or digital signal output Through the easy to use web based user interface users can set the alarm criteria and select alarm outputs of each sense input independently to mee...

Страница 13: ...M On board 10 100 Mbps Ethernet adapter 1 RS 232 serial port up to 9600 baud rate 1 SM bus interface for PC system healthy status monitoring 1 SM bus interface for up to 8 external temperature sensors...

Страница 14: ...Can set up to 4 addresses to receive e mails Alarm message display on the optional LCD display module SNMP trap Notify up to 8 SNMP administrators Pager notification Dial out through external modem t...

Страница 15: ...s Battery type Li Ion Battery capacity 1800 mA h fully charged for 45 50 minutes oper ation depends on the output used Battery life 1 year 20 C 80 capacity after 500 cycles of charge and discharge Pow...

Страница 16: ...SNMP 1000 B1 User s Manual 6...

Страница 17: ...7 CHAPTER 2 Hardware Installation...

Страница 18: ...not identical as the one depicted in this section please refer to the user s note of your extension module for the detail The kernel module has two 32 pin connectors named as MCN1 and MCN2 The extensi...

Страница 19: ...he username and password is restored to advantech and admin MCN1 and MCH2 Sensor and I O interface Please refer to Appendix A for the pin assignments 2 2 Connecting sensors and I O ports This section...

Страница 20: ...or PCI bus therefore no driver is required Figure 2 3 Connectors on extension board Figure 2 4 Connectors on carrier board CN 9 C N 2 C N 8 C N 5 CN 11 CN 12 FAN 1FAN 2FAN 3 FAN 6 FAN 4FAN 5 FAN 9 FA...

Страница 21: ...ard comes with a special cable P N 1703120900 This cable has a box header at one end and an RJ 45 at the other end An adaptor bracket allows users to fix the RJ 45 at chassis by using an exist ing DB...

Страница 22: ...s used to enable or disable this tem perature sensor Enable Disable Temp 3 Off On Off Temp 4 Off On On Temp 5 On Off Off Temp 6 On Off On Temp 7 On On Off Temp 8 On On On 1 2 3 4 O N 1 2 3 4 O N 1 2 3...

Страница 23: ...Digital Input Connectors DI1 DI8 Up to 8 TTL level digital signals can be monitored by SNMP 1000 B1 You can use these digital inputs to detect external devices or other healthy status such as chassis...

Страница 24: ...Use the 8 pin to 6 pin cable enclosed in the SNMP 1000 B1 package to connect to CPU card 2 2 16 Chassis and Watchdog Timer Connector CN20 Pin 1 and pin 2 of CN20 connect to the ATX power on off butto...

Страница 25: ...03020558 is shipped with the SNMP 1000 B1 to connect to the Watchdog timer output 2 2 17 Power Good Input Connectors CN16 CN21 CN24 Up to four power fail signals can be detected The SNMP 1000 B1 can d...

Страница 26: ...provide 12 V power to fans and receive tachometer signals from fans Notice that the SNMP 1000 B1 can only detect fans with tachometer output This kind of fan generates two pulses per revolu tion 2 2...

Страница 27: ...17 CHAPTER 3 Getting Started...

Страница 28: ...can configure your SNMP 1000 B1 module you need to first install your SNMP 1000 B1 and power it up Please refer to Chapter 2 for installation instruction You can connect it to a network through its L...

Страница 29: ...ou are using to connect to the SNMP 1000 B1 4 Set the serial port of your PC to be 9600 bps 8 data bits no parity 1 stop bit with no flow control 5 Press Enter key of your PC then the SNMP 1000 B1 wil...

Страница 30: ...ult value is SNMP 1000 B1 It is advisable not to change the default model name IP Address The IP address of the SNMP 1000 B1 Gateway Address The network default gateway address Network Mask The sub ne...

Страница 31: ...read and write to SNMP 1000 B1 Default password is admin Community Read Only A general password for read only access Default read only password is public BOOTP DHCP Control Enables disables the BOOTP...

Страница 32: ...le This table allows you to set restrictions to some IP addresses to access the SNMP 1000 B1 You can add IP addresses and set an access control Available choices are NotAccess Read Only or Read Write...

Страница 33: ...e The Severity Level allow you to specify an alarm level Trap will not be sent if the alarm severity is lower than specified level 3 2 1 6 E mail Notification Menu The SNMP 1000 B1 can send e mail to...

Страница 34: ...of the mail server in dotted format Mail Account The account name for the SNMP 1000 B1 to log into the mail server Mail Status Daily at By pressing 5 users can specify the time for the SNMP 1000 B1 t...

Страница 35: ...The severity to send alarm notification This item is use ful when the Mail Condition is set as Alarm or Alarm and Log Status The status of this mail address You can set it as Disable when this addres...

Страница 36: ...will prompt you for entering user name and password same as described in section 3 2 3 3 2 Configuration using a Web Browser Using a web browser is the easiest way to configure the SNMP 1000 B1 Type i...

Страница 37: ...nu When an alarm is detected and the buzzer release warning sounds users may press the alarm reset button to stop the audible alarm The next pages show the flow chart of each function Please notice th...

Страница 38: ...SNMP 1000 B1 User s Manual 28 3 3 5 Main Menu...

Страница 39: ...29 3 3 6 Agent configuration IP Addr 192 168 1 1 Gateway Addr 0 0 0 0 Subnet Mask 255 255 0 0 BOOTP DHCP Disable Main Menu Agent Config Enter Enter ESC ESC ESC ESC Enter Enter Enter...

Страница 40: ...nction IP Addr 192 168 1 1 Enter IP Addr 292 168 1 1 IP Addr 192 168 1 1 IP Addr 192 168 1 1 ESC Agent IP OK 192 168 1 1 Cancel Enter ESC Enter ESC Enter IP Addr 1 2 168 1 1 IP Addr 102 168 1 1 ESC BO...

Страница 41: ...1 31 2001 System Time 13 00 System Up Time 9999Day 14 25 30 Main Menu Agent Info Enter Enter ESC ESC ESC ESC ESC Enter Enter Enter Enter Set Date 01 01 2002 Enter Set Date 11 01 2002 System Date 01 01...

Страница 42: ...Time 13 00 Set Time 13 00 ESC Time OK 13 00 Cancel Enter ESC Enter ESC Enter Set Time 14 00 ESC ALM1 Critical Power0 Fail ALM2 Major CPU2 Vcore Low ALM3 Minor CPU2 Fan Low Main Menu Active Alarm 3 En...

Страница 43: ...tatus Fan Speed System Status Temperature System Status Voltage System Status Power Supply System Status Watchdog Timer Main Menu System Status Enter Enter ESC ESC ESC ESC ESC Enter Enter Enter Enter...

Страница 44: ...4 View Fan Speed 3 3 15 View Temperature Status Fan 1 Norm 12000 RPM Fan 2 Low 1000 RPM System Status Fan Speed Enter Enter ESC ESC Enter Temp 1 118 4 deg F Nor Temp 2 116 6 deg F Hig System Status Te...

Страница 45: ...35 3 3 16 View Voltage Status 12V 10V Low 3 3V 3 32 V Norm 5 V 5 80 V High System Status Voltage Enter Enter ESC ESC Enter 12V 11 92 V Norm ESC Enter ESC Enter...

Страница 46: ...36 3 3 17 View Power Supply Status 3 3 18 View Digital Input Status Power1 Good Power2 Fail System Status Power Supply Enter Enter ESC ESC Enter DI1 High Norm DI2 Low Alarm System Status Digital Input...

Страница 47: ...thy Status 3 3 20 View Watchdog Timer Status Cpumb Status Fan Speed Cpumb Status Temperature Cpumb Status Voltage Main Menu Cpumb Status Enter Enter ESC ESC Enter ESC Enter Watchdog Timer Timeout Syst...

Страница 48: ...SNMP 1000 B1 User s Manual 38...

Страница 49: ...39 Chapter4 CHAPTER 4 Programming the SNMP 1000 B1...

Страница 50: ...NMP 1000 B1 through serial port or Telnet Follow below steps to enter the Pass Through Command mode 1 Turn on SNMP 1000 B1 then SNMP 1000 B1 will send identify string nAdvantech v2 xx SNxxxxxx Ready n...

Страница 51: ...uration Utility Main Menu 1 Agent Configuration 2 Remote Control 3 Restart Agent 4 Reset Configuration To Default 5 Access Agent Command 0 Exit Please Enter Your Choice 6 On host computer side send 5...

Страница 52: ...in ASCII code it could be Done or Invalid in the response from SNMP 1000 B1 Examples 1 Write low limit of Fan 0 to 1000 rpm EX Host computer side sends w1011000 r SNMP 1000 B1 responds w1011000 n Resp...

Страница 53: ...an 3 Fan 4 Fan 5 Fan 6 Fan 7 Fan 8 Code 20 21 22 23 24 25 26 27 28 Device Temp 0 Temp 1 Temp 2 Temp 3 Temp 4 Temp 5 Temp 6 Temp 7 Temp 8 Code 30 31 32 33 34 35 36 37 38 Device 3 3 V 5 V 5 V 5 Vsb 12 V...

Страница 54: ...2 3 4 5 6 7 Fan Low Limit Alarm Level Event Out Current Speed Temp High Limit High Alarm Level High Event Output Low Limit Low Alarm Level Low Event Output Current Temp Voltage High Limit Low Limit Al...

Страница 55: ...Device Code Device Sub Item Device Sub Code r101 Fan 0 10 Low Limit 1 r111 Fan 1 11 r181 Fan 8 18 r102 Fan 0 10 Alarm Level 2 r112 Fan 1 11 r182 Fan 8 18 r103 Fan 0 10 Event Output 3 r113 Fan 1 11 r18...

Страница 56: ...imit 1 1000 9999 RPM in ASCII code w111xxxx Fan 1 11 w181xxxx Fan 8 18 w102x Fan 0 10 Alarm Level 2 1 Not used w112x Fan 1 11 2 No Alarm 3 Critical w172x Fan 7 17 4 Major w182x Fan 8 18 5 Minor w103x...

Страница 57: ...1 r281 Temp 8 28 r202 Temp 0 20 High Alarm Level 2 r212 Temp 1 21 r282 Temp 8 28 r203 Temp 0 20 High Event Output 3 r213 Temp 1 21 r283 Temp 8 28 r204 Temp 0 20 Low Limit 4 r214 Temp 1 21 r284 Temp 8...

Страница 58: ...xxxx Temp 8 28 w202x Temp 0 20 High Alarm Level 2 1 Not used w212x Temp 1 21 2 No Alarm 3 Critical w272x Temp 7 27 4 Major w282x Temp 8 28 5 Minor w203x Temp 0 20 High Event Output 3 1 None w213x Temp...

Страница 59: ...Temp 1 21 2 Power Off 3 DO 0 w266x Temp 6 26 4 DO 1 w276x Temp 7 27 5 DO 2 w286x Temp 8 28 6 DO 3 Command Device Device Code Device Sub Item Device Sub Code r301 3 3V 30 High Limit 1 r311 5V 31 r321...

Страница 60: ...0 Current Voltage 5 r315 5V 31 r325 5V 32 r335 5VSB 33 r345 12V 34 r355 12V 35 Command Device Device Code Device Sub Item Device Sub Code Value xxxx Remark w301xxxxxx 3 3V 30 High Limit 1 15 0 15 0 Vo...

Страница 61: ...3V 30 Alarm Level 3 1 Not used w313x 5V 31 2 No Alarm w323x 5V 32 3 Critical w333x 5VSB 33 w343x 12V 34 w353x 12V 35 4 Major w304x 3 3V 30 5 Minor w314x 5V 31 Event Out put 4 1 None w324x 5V 32 2 Powe...

Страница 62: ...U 1 40 Event Output 3 r413 CPU 2 41 r404 CPU 1 40 Current Speed 4 r414 CPU 2 41 r501 CPU 1 50 High Limit 1 r511 CPU 2 51 r502 CPU 1 50 High Alarm Level 2 r512 CPU 2 51 r503 CPU 1 50 High Event Out put...

Страница 63: ...41 CPU card 5V 64 r651 CPU card 12V 65 r661 CPU card 12V 66 r602 CPU 1 Vcore 60 Low Limit 2 r612 CPU 2 Vcore 61 r622 CPU VI O 62 r632 CPU card 5V 63 r642 CPU card 5V 64 r652 CPU card 12V 65 r662 CPU c...

Страница 64: ...5 r615 CPU 2 Vcore 61 r625 CPU VI O 62 r635 CPU card 5V 63 r645 CPU card 5V 64 r655 CPU card 12V 65 r665 CPU card 12V 66 Command Device Device Code Device Sub Item Device Sub Code Value xxxx Remark w4...

Страница 65: ...s tem setting max 5 charac ters incl w511xxxxx CPU 2 51 w502x CPU 1 50 High Alarm Level 2 1 Not used 2 No Alarm 3 Critical w512x CPU 2 51 4 Major 5 Minor w503x CPU 1 50 High Event Output 3 1 None 2 Po...

Страница 66: ...larm Level 5 1 Not used 2 No Alarm w515x CPU 2 51 3 Critical 4 Major 5 Minor w506x CPU 1 50 High Event Output 6 1 None 2 Power Off 3 DO 0 w516x CPU 2 51 4 DO 1 5 DO 2 6 DO 3 Command Device Device Code...

Страница 67: ...max 6 charac ters incl w611xxxxxx CPU 2 Vcore 61 w621xxxxxx CPU VI O 62 w631xxxxxx CPU card 5V 63 w641xxxxxx CPU card 5V 64 w651xxxxxx CPU card 12V 65 w661xxxxxx CPU card 12V 66 w602xxxxxx CPU 1 Vcore...

Страница 68: ...nor w604x CPU 1 Vcore 60 Event Output 4 1 None w614x CPU 2 Vcore 61 2 Power Off w624x CPU VI O 62 3 DO 0 w634x CPU card 5V 63 w644x CPU card 5V 64 4 DO 1 w654x CPU card 12V 65 5 DO 2 w664x CPU card 12...

Страница 69: ...4 Power 2 71 r724 Power 3 72 r734 Power 4 73 Command Device Device Code Device Sub Item Device Sub Code Value x Remark w701x Power 1 70 Normal Level 1 1 High w711x Power 2 71 w721x Power 3 72 2 Low w7...

Страница 70: ...2 5 DO 3 Command Device Device Code Device Sub Item Device Sub Code r801 DI 1 80 Normal Level 1 r811 DI 2 81 r871 DI 7 87 r802 DI 1 80 Alarm Level 2 r812 DI 2 81 r872 DI 7 87 r803 DI 1 80 Event Output...

Страница 71: ...rm Level 2 1 Not used w812x DI 2 81 2 No Alarm 3 Critical w862x DI 6 86 4 Major w872x DI 7 87 5 Minor w803x DI 1 80 Event Output 3 1 None w813x DI 2 81 2 Reset 3 Power Off w843x DI 4 84 4 DO 0 w853x D...

Страница 72: ...62 Command Device Device Code Device Sub Item Device Sub Code Value x Remark w901x WDT 90 Alarm Level 1 1 Not used 2 No Alarm 3 Critical 4 Major 5 Minor w902x WDT 90 Event Output 2 1 None 2 Power Off...

Страница 73: ...63 AppendixA Appendix A Connector Pin Assign ments...

Страница 74: ...Connector Pin Assignments A 1 External Buzzer Connector J1 A 2 Bypass Password Protection MJ1 A 3 External Power Connector CN1 Pin Signal 1 Buzzer 2 5V Pin Signal 1 PASS_SET 2 GND Pin Signal 1 12 V 2...

Страница 75: ...5 System SMBus Connector CN3 Pin Signal Pin Signal 1 SPLED LAN speed LED 2 TERMPLANE 3 RX 4 RX 5 GND 6 LVCC 7 TX 8 TX 9 LILED LAN link LED 10 TERMPLANE 11 N A 12 GND Pin Signal 1 B_SCLK I2C bus clock...

Страница 76: ...6 Temperature Sensor Connectors CN4 CN7 A 7 RS 232 Connector CN8 Pin Signal 1 5 V 2 T_SCLK 3 T_SDAT 4 GND Pin Signal Pin Signal 1 DCD 2 RX 3 TX 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 9 RI 10 NC 11 NC 12 NA 2 4...

Страница 77: ...data 2 LCM I2C bus clock 3 12 V 4 GND 5 5 V 6 5 V 7 Alarm LED 8 GND Pin Signal Pin Signal 1 SIN 2 SOUT 3 CTS 4 DCD 5 RTS 6 DTR 7 DSR 8 Alarm reset 9 ATX ON 10 DO 4 11 GND 12 DO 3 13 Watchdog IN 14 DO...

Страница 78: ...SNMP 1000 B1 User s Manual 68 23 TX LAN 24 DI 4 25 TX LAN 26 DI 5 27 RX LAN 28 DI 6 29 RX LAN 30 DI 7 31 TERMPLANE 32 DI 8 Pin Signal Pin Signal...

Страница 79: ...Power Good D 7 Alarm LED 8 FAN 1 9 GND 10 FAN 2 11 GND 12 FAN 3 13 VCC 14 FAN 4 15 VCC 16 FAN 5 17 VCC 18 FAN 6 19 BEEP 20 FAN 7 21 5VSB 22 FAN 8 23 5V 24 FAN 9 25 5V 26 B_SCLK Clock of I2C bus to sy...

Страница 80: ...SNMP 1000 B1 User s Manual 70 A 11 Backplane Voltage Input Connector CN13 Pin Signal Pin Signal 1 5 VSB 2 GND 3 GND 4 5 V 5 5 V 6 3 3 V 7 12 V 8 12 V 8 5 7 6 3 2 4 1...

Страница 81: ...ppendixA A 12 Digital Input Connectors DI1 DI8 CN14 Pin Signal Pin Signal 1 DI 1 2 GND 3 DI 2 4 GND 5 DI 3 6 GND 7 DI 4 8 GND 9 DI 5 10 GND 11 DI 6 12 GND 13 DI 7 14 GND 15 DI 8 16 GND 4 3 1 2 15 13 1...

Страница 82: ...ser s Manual 72 A 13 Digital Output Connectors DO1 DO4 CN15 A 14 Alarm Reset Connector CN17 Pin Signal Pin Signal 1 DO 1 2 GND 3 DO 2 4 GND 5 DO 3 6 GND 7 DO 4 8 GND Pin Signal 1 GND 2 ARM_RESET 4 3 1...

Страница 83: ...LED 14 PG 3 3V 15 PG 5VSB Notice The SNMP 1000 B1 uses digital signals DO1 DO2 and DO3 for the power fail LED PF_LED overheating LED TF_LED and fan failure LED FF_LED respectively Users must enable th...

Страница 84: ...CN19 A 17 Chassis and Watchdog Timer Connector CN20 Pin Signal Pin Signal 1 HDD Active 2 ATX IN 3 B_SCLK 4 ATX OUT 5 B_SDAT 6 SYSTEM RESET Pin Signal Pin Signal 1 ATX IN 2 ATX OUT 3 GND 4 System Rese...

Страница 85: ...Connectors CN16 CN21 CN24 A 19 FAN Connectors FAN1 FAN9 Pin Signal Pin Signal CN16 CN21 1 GND 2 Power Good A CN22 1 GND 2 Power Good B CN23 1 GND 2 Power Good C CN24 1 GND 2 Power Good D Pin Signal 1...

Страница 86: ...SNMP 1000 B1 User s Manual 76...

Отзывы: