C.2 Redundant 800W DC PSU
Table C-2: 800W DC Power Supply Specification
Item
Specification
Comment /
Conditions
Input Voltage
-40 - -60dc
Rating
800W
Input Current
25.2-16.8A
Inrush Current
Maximum DC inrush current shall be 100A
peak at an input voltage of -72VDC. Inrush
current shall be measured at an ambient
temperature of 25° C after the input voltage
has been removed from the power supply for
a minimum of 10 minutes.
MTBF
1) 200,000 hours at 100% load and 25
degree C (excluding the Fan MTBF)
2) 100,000 hours at 100% load and 25
degree C (Including the Fan MTBF).
BELL CORE
TR-322
Environment
Temperature:
- Operation: 0 ~
50°C
- Non-Operation: -40 ~70°C
Humidity:
-
Operation: 5~90%RH
-
Non-Operation: 5~95%RH storage.
Altitude:
-
Operation : sea level to 5000m
-
Non-Operation : sea level to 15000m
Vibration:
-
Operatio
n: 0.01g²/Hz at 5 Hz sloping to
0.02g²/Hz at 20 Hz, and maintaining
0.02g²/Hz from 20 Hz to 500 Hz.
-
Non-Operation : 5Hz to 500Hz @
0.5gRMS at 0.5 octave/min