Power Supply Installation
2.9.1
Overview
The switches can be powered by using the same DC source used to power other
devices. A DC voltage range of 12 to 48 VDC (Non PoE) or 48 VDC (PoE) must be
applied between the V1+ terminal and the V1- terminal (PW1), see the following
illustrations. A Class 2 power supply is required to maintain a UL60950 panel listing.
The chassis ground screw terminal should be tied to the panel or chassis ground. A
redundant power configuration is supported through a secondary power supply unit
to reduce network down time as a result of power loss.
Dual power inputs are supported and allow you to connect a backup power source.
Figure 2.12 Power Wiring for EKI-7428 Series
Warning!
Power down and disconnect the power cord before servicing or wiring
the switch.
Caution!
Do not disconnect modules or cabling unless the power is first switched
off.
The device only supports the voltage outlined in the type plate. Do not
use any other power components except those specifically designated
for the switch device.
Caution!
Disconnect the power cord before installation or cable wiring.
P2 P1
Chassis
GND
(pane)
One DC Supply
P2 P1
Chassis
GND
(pane)
Dual DC Supplies
Single DC Power
Redundant DC Power
Содержание EKI-7428 Series
Страница 1: ...User Manual EKI 7428 Series 24GE 4G Combo 24GE PoE 4G Combo Port L2 Managed Switch ...
Страница 14: ...Chapter 1 1Product Overview ...
Страница 20: ...Chapter 2 2Switch Installation ...
Страница 35: ...Chapter 3 3Configuration Utility ...
Страница 41: ...Chapter 4 4Managing Switch ...
Страница 138: ...125 EKI 7428 Series User Manual 4 12 1 Modbus TCP Mapping Table ...
Страница 156: ...Chapter 5 5Troubleshooting ...
Страница 158: ...145 EKI 7428 Series User Manual ...