Advantech B+B SMARTWORX 485LDRC9 Скачать руководство пользователя страница 1

Product Overview

Connect RS-232 Device 

Set RS-422/485 Converter Side

Termination Switch: 

Set to OFF (recommended)

Connect Your Power Supply

Loopback Test

Set the Dipswitch Settings

for Baud Rate

1

+

+

+

+

2

4

5

6

3

External Power 

Supply

Terminal C:

(Ground/V (–)

Terminal F: 

V (+)

Converter uses 0.5 W

• Configure for RS-485 4-wire, 9600 baud.

• Jumper terminals H to L, and G to K.

• Connect a PC to the RS-232 port (see 

Step 1).

• Using HyperTerminal or similar program, 

 

connect to the appropriate COM port 

 

(remember to set the baud rate at 9600). 

 

Turn off HyperTerminal local echo.

• Start typing. If you can see the data 

 

you are typing, you have a good loop-

 

back. If you cannot, contact B+B 

SmartWorx technical support.

• LED Indicators: Power is ON when power 

 

is applied. TD flashes when RS-422/485 

 

data is sent. RD flashes when RS-   

422/485 data is received.

Set DIP 

Switches to:

RS-485 

4-Wire

L

K
H
G

1
2
3
4
5
6
7
8

ON

ON

OFF
OFF
OFF
OFF

OFF
OFF

LED Indicators

7

+

Terminal Block

 

Connectors

A – F

Terminal Block

 

Connectors
G – M

DB9 F Pins

DIP 

Switches

1 – 8

Top View

 

(RS-232 & Power Side)

Bottom View

 

(RS-422/485 Side)

Please Note: 

 

Terminal block and DIP switch settings located on product.

Additional RS-422/485 technical notes on are available 

on the B+B SmartWorx website.

2 Wire 485

4 Wire 485/422

Your Device

Your Device

485LDRC9

485LDRC9

G

K

DATA

B (+)

DATA

A (-)

GND

H

L

J

M

G

TDB 

(+)

TDA 

(-)

RDB 

(+)

RDA 

(-)

GND

K

H

L

J

M

SW-1

SW-2

SW-3

SW-4

RS-485 2-Wire Half-Duplex

ON

ON

ON

ON

RS-485 4-Wire Full-Duplex

ON

OFF

OFF

OFF

 

RS-422 Full-Duplex

OFF

OFF

OFF

OFF

 

Computer

Your Device

485LDRC9

Field Device

Your Device

485LDRC9

DTE

DCE

D

TD

RD

A

E

B

F

C

GND

D

TD

RD

GND

A

E

B

F

C

Additional technical notes on RS-232 DTE DCE connections 

 

are available on the B+B SmartWorx website.

•  Use a straight-through DB9 to DB9 if you are 

 

   connecting to a computer (DTE).

  Use a cross-over (null modem) DB9 to DB9 if you 

are not connecting to a computer. (DCE)

For baud rates not listed above, see the B+B SmartWorx website.

SW-6

SW-7

SW-8

Timeout (MS)

2400

OFF

OFF

ON

4.16

4800

OFF

ON

OFF

2.08

9600

ON

OFF

OFF

1.04

19.2K

ON

ON

ON

0.580

Switch 5

Termination technical notes on are 

available on the B+B SmartWorx website.

Use the 120Ω

 

Built-in Termination

ON

Use External or 

No Termination

OFF

Transmit Data (Red)

Flashing - RS-422/485 data is transmitted

Receive Data (Red)

Flashing - RS-422/485 data is received

Power (Red)

On - when power applied

With no devices attached, LEDs should be Off; Power On.

TIPS:

If LEDs are On 

before

 devices are attached, it may indicate the 

Termination Resistor is On. 
Using termination, with power ON, but no devices connected, may cause 

the Receive LED to turn ON solid. The loading from the termination may 
cause the Receiver Bias to go into an indeterminate state.