background image

1 Startup Manual

Packing List

Before installation, please make sure that you have received 

the following:
•  AIIS-E730 card
•  Quick Start User Manual
If anything is missing or damaged, contact your distributor or 

sales representative immediately.

Specifications

Isolated Digital Input

Number of Channel

16 (bi-directional)

Optical Isolation

2,500 V

DC

Opto-isolator response time

25 μs

Over-voltage Protect

70 V

DC

Input Voltage

VIH (max.) 30 V

DC

VIH (min.) 3 V

DC

VIL (max.) 1 V

DC

Input Current

3 V

DC

 0.5 mA (typical)

12 V

DC

 3.1 mA (typical)

24 V

DC

 6.6 mA (typical)

30 V

DC

 9.73 mA (typical)

Declaration of Conformity

FCC Class A

This equipment has been tested and found to comply with 

the limits for a Class A digital device, pursuant to part 15 

of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference when the 

equipment is operated in a commercial environment. This 

equipment generates, uses, and can radiate radio frequency 

energy and, if not installed and used in accordance with the 

instruction manual, may cause harmful interference to radio 

communications. Operation of this equipment in a residential 

area is likely to cause interference in which case the user is 

required to correct interference at his own expense.

CE

This product has passed the CE test for environmental 

specifications when shielded cables are used for external 

wiring. We recommend the use of shielded cables. This kind 

of cable is available from Advantech. Please contact your 

local supplier for ordering information.

Notes

For more information on this and other Advantech products, 

please visit our websites at:

http://www.advantech.com

For technical support and service:
http://www.advantech.com/support/
This startup manual is for AIIS-E730.

Part No: 2003F73000

1st Edition
January 2016

ST

AR

TUP MANUAL

Overview

AIIS-E730

32-channel Isolated Digital I/O Card

The AIIS-E730 offers isolated digital input channels as well 

as isolated digital output channels with isolation protec-

tion up to 2,500 V

DC

, which makes them ideal for industrial 

applications where high-voltage isolation is required. The 

AIIS-E730 also features a Digital filter on each channel. 

General

I/O Connector Type

37-pin box header

Dimensions

96 mm x 102 mm (3.8” x 4.0”)

Power Consumption

Typical

+3.3 V @ 265 mA
+12 V @ 40 mA

Max

+3.3 V @ 475 mA
+12 V @ 75 mA

Temperature

Operation 0 ~ 50°C (32~ 122 °F )

(refer to IEC 68 -2 - 1 ,2)

Storage

-20 ~ +70°C (-4 ~158°F)

Relative Humidity

5 ~ 95% RH non-condensing 

(refer to IEC 60068-2-3)

 Certification

CE/FCC

Digital Output

Number of Channels

16

Optical Isolation

2,500 V

DC

Output Voltage

Open collector 5 to 40 V

DC

Sink/Source Current

500 mA max./channel

Отзывы: