Besides, following tips just for your reference.
•
The shield of cable can’t be used for signal ground.
The shield is just designed for adhering noise, so the environment
noise will couple and interfere your system when you use the shield as
signal ground.
•
The density of shield is the higher the better, especially for commu-
nication network.
•
Use double isolated cable for communication network / AI / AO.
•
Both sides of shields should be connected to their frame while inside
the device. (for EMI consideration)
•
Don’t strip off too long of plastic cover for soldering.
2.2 System Shielding
Figure G-11: System Shielding
ADAM
4013
ADAM
4017
ADAM
4021
ADAM
4520
Power
Supply
+24V
Terminal Block
RS-232
Connect the shield to Frame-Ground of DC Power Supply.
*
Never stripping too long of the plastic cable cover.
* Cascade those shields together by Soldering
.
Содержание ADAM-5510/P31
Страница 17: ...0 Quick Start...
Страница 38: ...0 22 ADAM 5510 P31 Quick Start...
Страница 39: ...1 Introduction...
Страница 43: ...2 Installation Guidelines...
Страница 52: ...2 10 ADAM 5510 P31 Installation Guideline Figure 2 10 ADAM 5510 P31 network address DIP switch...
Страница 58: ...2 16 ADAM 5510 P31 Installation Guideline...
Страница 59: ...3 System Specifications...
Страница 65: ...4 I O Modules...
Страница 116: ...4 52 ADAM 5510 P31 I O Modules...
Страница 117: ...ADAM 5510 P31 5 1 Chapter 5 5 Troubleshooting...
Страница 129: ...ADAM 5510 P31 A 1 Appendix A A Quick Start Example...
Страница 132: ...A 4 ADAM 5510 P31 Quick Start Example...
Страница 133: ...ADAM 5510 P31 B 1 Appendix B B COM Port Register Structure...
Страница 137: ...ADAM 5510 P31 C 1 Appendix C C Data Formats and I O Ranges...
Страница 147: ...D Performance...
Страница 173: ...E RS 485 Network...
Страница 181: ...ADAM 5510 P31 F 1 Appendix F F ADAM 4000 5000 System Grounding Installation...
Страница 187: ...ADAM 5510 P31 G 1 Appendix G G Grounding Reference...
Страница 202: ...G 16 ADAM 5510 P31 Grounding Reference...