MicroLinx Series L

Electronic Metering Pump

Product Manual

Important Safety Instructions

Read all warnings and instructions in this manual.

Save all instructions.

Advantage Controls

4700 Harold-Abitz Dr.

Muskogee, OK  74403

Phone: 800-743-7431

Fax: 888-686-6212

www.advantagecontrols.com

[email protected]

7/2022

C

US

Содержание MicroLinx L Series

Страница 1: ...ng Pump Product Manual Important Safety Instructions Read all warnings and instructions in this manual Save all instructions Advantage Controls 4700 Harold Abitz Dr Muskogee OK 74403 Phone 800 743 7431 Fax 888 686 6212 www advantagecontrols com support advantagecontrols com 7 2022 C US ...

Страница 2: ...le for damages injuries or expense incurred through the use of its products The above warranty is in lieu of other warranties either expressed or implied No agent of ours is authorized to provide any warranty other than the above 30 Day Billing Memo Policy Advantage Controls maintains a unique factory exchange program to ensure uninterrupted service with minimum downtime If your unit malfunctions ...

Страница 3: ...el Number Example L 30 X 1 K F C 1 Output 05 5 GPD 18 9 LPD at 300 PSI 20 6 bar 12 12 GPD 45 4 LPD at 250 PSI 17 2 bar 15 15 GPD 56 7 LPD at 150 PSI 10 3 bar 30 30 GPD 113 5 LPD at 100 PSI 6 8 bar 45 45 GPD 170 3 LPD at 75 PSI 5 1 bar Control X Speed adjustment with timers pulse mA in Voltage 1 120 vac USA plug and agency approvals 2 120 220 vac no plug Pump Head Material K Kynar D Kynar degassing...

Страница 4: ...to solution s SDS precautions from your solution supplier Water Pre Prime and Testing All pumps are pre primed with water when shipped from the factory and some water may be present All UL electrical safety evaluations performed with water only Tubing and Piping Connections Pumps uses carefully matched components to achieve a predictable metering output This can only be maintained if all fitting s...

Страница 5: ...ry to retighten the head bolts and tubing connections periodically Electrical Connections To reduce the risk of electrical shock the metering pump must be plugged into a properly grounded grounding type receptacle with ratings conforming to the data on the pump control panel The pump must be connected to a good ground DO NOT USE ADAPTERS All wiring must conform to local electrical codes Ground Fau...

Страница 6: ...ptional 3 function injection valve assembly provides anti siphoning for metering of liquids downhill or into the suction side of a circulating pump It provides protection against an accidental application of suction pressure at the fluid injection point Its Teflon coated diaphragm provides a positive anti siphon action It also provides back pressure to permit metering into atmospheric discharge op...

Страница 7: ...30 1440 0 0208 gpm 200 spm 0 000104 With this value and the pump s speed setting strokes per minute you can calculate your pump s output at it s rated pressure A 30 gpd pump set at 50 strokes per minute 50spm x 000104gps x 1440 minutes per day 7 49 gallons per day Optional Features External Auto Stop Pumps with this option are allowed to stroke as long as they see a closed condition from a dry con...

Страница 8: ...tus screen and into the Configure menu The MicroLinx Series L menus are easily navigated by pressing the arrow keys and confirming selection with the Menu Enter key A flashing box is similar to positioning a computer mouse over a link and the Menu Enter button will act as a mouse click FLASHING Highlighted SOLID Selected Some options will have separate screens and some values will change on the sa...

Страница 9: ...pump stops when the input sees Open or Closed regardless of operation mode 2 1 Off OFF TIMERS MANUAL CLOCK SET MULT DIV PASSWORD mA IN WIFI ON OFF Push Enter OFF OFF This is where you select the OFF menu Use the Up Down arrows while selection choice is flashing Press Menu Enter to confirm selection The run mode status screen will change and display OFF and the pump will stop running Press Menu Ent...

Страница 10: ...r light will turn red and will flash with each stroke Choose Config to leave the settings unchanged and return to the config menu Note The pump will stop running if the run mode status screen is not shown 2 4 mA In OFF TIMERS MANUAL CLOCK SET MULT DIV PASSWORD mA IN WIFI ON 4mA 0 20mA 100 CONFIG EXIT SAVE 1 0 2 STROKES MIN mA 4 16 mA This is where you select the mA menu Use the Up Down arrows whil...

Страница 11: ...e Up Down arrows to select the RUN TIME minutes Press Menu Enter to confirm selection Use the Up Down arrows to change the RUN TIME minute values from 0 59 Press Menu Enter to confirm entry Then use the Up Down arrows to go to the RUN TIME seconds Repeat the process to update the RUN TIME seconds This is where you select the WM SET submenu Use the Up Down arrows while selection choice is flashing ...

Страница 12: ...E OPEN options Use the Up Down arrows while selection choice is flashing Press Menu Enter to toggle CLOSE OPEN selection Choose Exit Save to confirm changes and return to the config menu Note External signal cable wiring is shown on page 18 2 5 4 28 Day Timer WM TIMER 28 DAY RECYCLE BATCH STOP CLOSE CONFIG PROGRAM 1 PROGRAM 3 PROGRAM 2 PROGRAM 4 CONFIG EXIT SAVE ALL WEEKS OFF RUN TIME 00 00 H M ST...

Страница 13: ...6 Clock Set OFF TIMERS MANUAL CLOCK SET MULT DIV PASSWORD mA IN WIFI ON TIME 15 49 H M DAY TUESDAY WEEK 3 15 54 43 W 3 TUESDAY EXIT SAVE This is where you select the CLOCK SET menu Use the Up Down arrows while selection choice is flashing Press Menu Enter to confirm selection Note The pump time must be re adjusted if this menu is selected This will display the CLOCK SET submenu Use the Up Down arr...

Страница 14: ...minutes after key press inactivity 2 8 WiFi OFF TIMERS MANUAL CLOCK SET MULT DIV PASSWORD mA IN WIFI ON This is where you select the WIFI menu Use the Up Down arrows while selection choice is flashing Press Menu Enter to toggle between WIFI ON and WIFI OFF Note The Wifi portion of the pump is an Access Point only You must be within 300 feet line of site to connect to the pump To interface and conf...

Страница 15: ...Step 2 Press Add Device or the button Step 3 Enter a custom Name Enter the pump s Wifi SSID in the Serial Number field Press the Submit button Step 4 The pump will be added to the list Press the pump name or right arrow to continue Step 5 Press the Connect button Step 6 Press Join to continue ...

Страница 16: ...tep 7 Connected successfully Press OK to continue Step 8 Pump run screen Press the Configure button to continue Step 9 Configure screen Press a button to make changes as previously described in this manual ...

Страница 17: ...Step 2 Enter the password Note This is located on the pump s Wifi SSID label on top of the pump Step 3 After connection is made click on the information icon Record the router IP address Step 4 Enter the router IP address as the website URL and press enter return go Note The wifi connection will disconnect if the browser is closed ...

Страница 18: ...RED GREEN BLUE BLACK ORANGE WHITE 1 Red 2 Black 3 Blue 4 White 5 Orange 6 Green ML CABLE 7P 6 1 Red External auto stop 2 Black External auto stop 3 Blue Pulse in 4 White 4 20mA input 5 Orange Pulse in 6 Green 4 20mA input MicroLinx Pump Connections ...

Страница 19: ...jection Valve 3 Foot Valve 4 Suction Valve 5 Discharge Valve 6 Priming Valve Assembly 6a Degassing Valve Assembly 7 Pump Head 8 Priming Tube Assembly 9 Priming Tubing 10 Head Bolts 11 Diaphragm 12 Support Ring 13 Shaft Seal 14 Discharge Tubing 15 Suction Tubing 16 Weight Complete Head Kit includes items 4 5 6 7 8 10 and 11 ...

Страница 20: ..._ __ Body Seat Ball Connection D PVDF Degas V Viton C Ceramic 1 3 8 tube R 1 4 FNPT K PVDF F Teflon S Stainless 2 1 4 tube U 3 8 tube S Stainless Steel H Hypalon P 1 4 MNPT V 3 8 tube SS head only All PVDF Assemblies 2 Injection Valve Assembly INJ L K __ __ __ 3 Function Injection Valve 3FV K __ __ __ 3 Foot Valve Assembly FTV L K __ __ __ 4 Suction Valve Assembly SUC L K __ __ __ 5 Discharge Valv...

Страница 21: ...does not fall out 5 Do not allow sharp or abrasive objects to come in contact with pump parts 6 Inspect end of shaft to assure that threads are in good condition Replace shaft bellows if necessary No further disassembly is recommended 7 Screw new diaphragm onto pump shaft until it bottoms out on shoulder of shaft It is not necessary to tighten further 8 Replace fluid end Make sure that screws are ...

Страница 22: ...pect check valves in fluid end for cleanliness Clean or replace as necessary Inspect suction tube through its full length to assure that there are no splits at the connections or other restrictions Move any objects or equipment which impinges upon suction tube or reroute as required to assure a smooth transition from foot valve to pump Check fluid level in chemical supply tank Excessive fluid Fail...

Страница 23: ...23 ...

Страница 24: ... Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Bleed Valves Water Meters Metering Pumps Corrosion Coupon Racks Solution Tanks Solid Feed Systems Bypass Feeders Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage 160 External Pulse Auto Stopped spm MENU ENTER 5 4 3 2 1 ENTER HELP 5 4 3 CHANGE RUN SET UP 0 9 8 2 1 7 6 HOME BACK ENTER ...