www.advancedco.com
49
www.advancedco.com
49
8 Appendix C: D9068P Programming Defaults
This appendix contains the programming defaults
for the D9068P. Use D9068 Program Record
Sheet (P/N: 46086) to record programming entries.
Program Time
• System Date*: 01 01 00
• System Time*: 0000
* Once the user enters the system date and time,
resetting the D9068P to its default settings does
not reset the system date and time. The system
time can be corrupted if the AC & DC power fails
for more than 5 minutes.
Auto Test
• Auto Test Time: 0400
• Auto Test Frequency: 24 hours
Daylight Savings:
No
Timers
• AC Fail Delay:
6 hour
• Display Rate:
1 second
Program Inputs (Configure)
• Point 1:
Waterflow
• Point 2:
Fire
• Point 3:
Supervisory
• Point 4:
Fire
• Point 5:
Fire
Program Inputs (Supervised)
• Point 1:
No
• Point 2:
No
• Point 3:
No
• Point 4:
No
• Point 5:
No
Configure Relay: Release on Trouble
Program Accounts
• Account #1:
0000
• Account #2:
0000
Phone Numbers
• Phone #1:
?????????
• Phone #2:
?????????
• Phone #3:
?????????
Phone Control
• Phone #1 Format:
SIA 300
• Phone #2 Format:
SIA 300
• Phone #1 Tone:
19D, 14A, 10PS
• Phone #2 Tone:
19D, 14A, 10PS
• Phone #1 Text:
No
• Phone #2 Text:
No
Report Steering
• Non-SUP Alarm: Phone 2 Backup
• Supervisory Alarm:
Phone 2 Backup
• Alarm Restor, Reset:
Phone 2 Backup
• Supervisory Restore:
Phone 2 Backup
• Tests:
Phone 2 Backup
• Trbl, Trbl Restore:
Phone 2 Backup
Line Control
• Line 1 Dialing Type:
Tone/Pulse
• Line 2 Dialing Type:
Tone/Pulse
• Line 1 Monitor Line:
Yes
• Line 2 Monitor Line:
Yes
• Line 1 Wait Dial Tone:
Yes
• Line 2 Wait Dial Tone:
Yes
ACK WAIT TIME:
45 seconds
Program Formats (4/2 Point Rpt)
• Fire Alarm Digit 1:
0
• Fire Rstrl Digit 1:
3
• Waterflow Digit 1:
0
• Supervise Digit 1:
0
• Trouble Digit 1:
6
• Trbl Rstrl Digit 1:
3
• Disable Digit 1:
B
• Disable Rtrl Digit 1:
3
• Monitor Digit 1:
0
• Zone 1 Digit 1:
1
• Zone 2 Digit 1:
2
• Zone 3 Digit 1:
3
• Zone 4 Digit 1:
4
• Zone 5 Digit 1:
5
Program Formats (4/2 Rpt Codes Group 1)
• System in Tst:
F1
• Sys Tst Rstrl:
E1
• Silence:
9F
• Fire Drill:
F2
• Fire Drill Rstl:
E2
• Open Reset:
9F
• Low Batt:
F9
• Low Batt Rstrl:
E9
• AC Fail:
F8
• AC Fail Rst:
E8
• Auto Tst Rpt:
EE
• Off Norm Tst:
FD
• Phone 1 Trbl:
FB
• Phone 1 Trbl Rstrl:
EB
• Phone 2 Trbl:
FC
• Phone 2 Trbl Rstrl:
EC
• System Trbl:
FD
• System Trbl Rstrl:
ED