www.advancedco.com
47
www.advancedco.com
47
Table 7: Reporting Summaries Continued
AX Series FACP
Event Type
DACT
Report Description
SIA
Code
Contact ID
Code
System Trouble Reporting
Low/No Battery
Low Battery
*YT aaaa
1 302 nn 000
Low/No Battery Restoral
Low Battery Restore
*YR aaaa
3 302 nn 000
Power Supply Trouble
AC Fail
*AT aaaa
1 301 nn 000
Power Supply Trouble Restoral
AC Fail Restore
*AR aaaa
3 301 nn 000
Activation of:
Corrupt Data
Open Circuit
Short Circuit
Circuit Overload
NAC Internal Trouble
NAC Internal Lost
PSU Input Trouble
System Programming
System Trouble
*IA aaaa
1 300 nn zzz
Restoral of:
Corrupt Data
Open Circuit
Short Circuit
Circuit Overload
NAC Internal Trouble
NAC Internal Lost
PSU Input Trouble
System Programming
System Trouble Restore
*IR aaaa
3 300 nn zzz
Display Error CPU Reset
System Trouble
*IA aaaa
1 300 nn zzz
Display Error CPU Restoral
System Trouble Restore
*IR aaaa
3 300 nn zzz
Program Error Config. Error
EEPROM Failure
*IA aaaa
1 307 nn 000
Program Error Config. Error
Restoral
EEPROM Failure Restore
*IR aaaa
3 307 nn 000
Network Lost, Node Lost, Trbl.
System Trouble Comm Fault
*NT aaaa
1 300 nn zzz
Network Restoral
System Trouble Comm Fault Restore
*NR aaaa
3 300 nn zzz
Switch/Button Activation Reporting
Reset
Open Reset
*OR 0000
1 401 nn 000
Drill
Fire Drill
FI aaaa
1 607 nn 000
Drill Restoral
Fire Drill Restore
FK aaaa
3 607 nn 000
Report Summary Notes:
SIA Reporting –
* = All code numbers reporting include a prefix “RI aaaa” area (zone) parameter. This is only sent when the
area (zone) parameter is greater than zero.
pppp = AX Series device number (device address). (1-9999)
aaaa = AX Series zone number assigned to individual devices and the panel. (1-9999)
Contact ID Reporting –
nn = AX Series network node number (panel, annunciator, ipGateway, etc. number). (1-99)
zzz = AX Series zone number assigned to individual devices and the panel. (1-999)
AX Series Base Card On-board Circuit Addresses
The below information may be required for deciphering certain reports sent to the central station regarding Base