www.advancedco.com
35
www.advancedco.com
35
This option sets the number of hours the D9068P
waits after an AC failure is signaled before sending
an AC Failure Report.
1: WAIT FOR DC
To access
WAIT FOR DC
, select
[0]: PROGRAM
--->
[2]: PROG TIMERS
--->
[1]: AC FAIL DLY
--->
[1]: WAIT FOR DC
.
Once an AC Fail signal is received on the AC Fail
input, the D9068P waits for a low battery signal.
The WAIT FOR DC function causes the D9068P to
wait and then send the AC Fail and Low Batt
Reports simultaneously. The current setting
appears in parentheses on the first line.
To set the D9068P to wait and send AC Fail and
Low Batt Reports simultaneously:
1. Press [1] and then [# Command]. The setting in
parentheses reflects the setting.
2. After programming this feature, press [* Clear] to
return to the Prog Timers Submenu.
2: WAIT DLY TIME
To access
WAIT DLY TIME
, select
[0]: PROGRAM
--->
[2]: PROG TIMERS
--->
[1]: AC FAIL DLY
--->
[2]: WAIT DLY TIME
. This option allows you to
select the length of time to wait after an AC Fail
signal is received before reporting the event over
the phone line.
To choose the length of time to wait after receiving
an AC Fail signal:
1. At the AC Fail Dly Submenu, press [2] to select
2: WAIT DLY TIME
and then press [#
Command]. The window shows:
2. The current setting appears in parentheses on
the first line. Enter the time and the press [#
Command].
3. After programming this feature, press [* Clear] to
return to the Prog Timers Submenu.
2: DISPLAY RATE
To access
DISPLAY RATE
, select
[0]: PROGRAM
--->
[2]: PROG TIMERS
--->
[2]: DISPLAY RATE
.
This option allows you to set the speed (in units of
0.25 sec) at which the menu lines are updated on
the LCD.
To set the speed for updating the LCD menu lines:
1. At the Prog Timers Submenu, press [2] to select
2: DISPLAY RATE
. The window shows:
2. The current setting appears in parentheses on
the first line. Enter the desired value and press
[# Command].
3. After programming this feature, press [* Clear] to
return to the Prog Timers Submenu.
5.4.3 PROG
INPUTS
The D9068P operates via serial communications
from the AX Series Intelligent Fire Alarm Control
Panel, for this reason programming inputs “PROG
INPUTS” should not be performed. The reporting
of point, zone, and network information is handled
by the AX Series FACP.
When a Low Battery input, followed by an
AC Fail input activates, the AC Fail Report is
sent immediately.
When both the AC Fail and Low Battery events
are present, the AC Fail event is reported
regardless of any wait time.
Programming WAIT DLY TIME for 00 allows
the D9068P to send an AC Fail Report without
delay.
PROG INPUTS should not be performed with
the D9068P.
The reporting of point, zone, and
network information is handled by the AX
Series FACP.