Table 5
lists the event history abbreviations.
Table 5: Event History Abbreviations
Abbreviation Meaning
A, ALRM
Alarm
AUTOTST Auto
test
ARST Alarm
restore
BATT:LOW Battery
low
BAT:RSTR Battery
restore
COMM Communication
DATALOST Data
lost
EE2 EEPROM
F Fire
FLT Fault
KEYPD: IN
Keypad installed
KEYPD: RS
Keypad removed
M Monitor
MANULTST Manual
test
SER:FL
Panel communication failure
OFFNORM
Off normal at test
PGMG:FLT Trouble
programming
PH1
Phone Line 1
PH2
Phone Line 2
RS,RST,RSTR Restore
S Supervisory
SYSFLT:F Trouble
input
SYSFLT:R
Trouble input restore
SYS:RSET System
reset
SYSTRB System
trouble
WDOG:RST
Automatic CPU reset
(watchdog)
TRBL Trouble
TRST Trouble
restore
W Waterflow
alarm
SER:RS
Panel communication restore
4.3 Reset
Reset the D9068P in one of four ways:
1. At the DACT-PRG LCD Remote Keypad, press [4] to
select
Reset
from the Main Menu or press [Reset].
Pressing either key resets the D9068P only when off-
normal conditions are present. The system sends an
Open Reset Report with the user ID parameter of 99.
2. Exiting the Test Mode. The system sends an Open
Reset Report with the user ID parameter of 99.
3. Exiting the Programming Mode. The system sends an
Open Reset Report with a user ID parameter of 01.
4. Powering up the D9068P, No Open Reset Report is
sent.
5 Programming
5.1 Using the Keypad
All programming for the D9068P is done using the
DACT-PRG LCD Remote Keypad. To properly program
the D9068P, you must always press the [* Command] and
[* Clear] keys in addition to the key(s) necessary to make
specific programming entries.
• Press [# Command] to accept an entry into the
D9068P.
• Press [* Clear] after pressing [* Command] to return to
the submenu or menu selections.
Refer to
Figure 18
for the complete programming key
sequence for setting the D9068P operational date.
Note: Events received from the AX Series
Intelligent Fire Alarm Control Panel over the
serial connection are not stored in the history
buffer these events are stored in the AX Series
FACP history buffer.