www.advancedco.com
10
1.1.1 AX-SEB Serial Expansion Board Layout
The AX Series Intelligent Fire Alarm Control Panel communicates to the D9068P DACT serially via an AX-SEB
serial expansion board. The AX-SEB Serial Expansion Board plugs into a ten-pin serial expansion port socket
located on the bottom left corner of the
AX-CTL
Base Card. See figure 2. Refer to Section 2.3 regarding AX-SEB
installation
Note: When utilizing the AX-SEB the jumper must be set in the DACT “ON” position. When programming the AX
Series Intelligent Fire Alarm Control Panel via the PC-NeT software tool the jumper must be placed in the DACT
“OFF” position, and upon completion of programming returned to the DACT “ON” position.
PL2 cable to (8) of D9068P
PL4 cable to (9) of D9068P
DACT-PRG
Keypad plug
AX Series
Programming
Jumper
Figure 2 – AX-SEB Serial Expansion Board Layout