ELECTRICAL SPECIFICATIONS
Table 3‑4. Electrical specifications
Description
Specification
Electrical Requirements
AC input line voltage
Type voltage 500 V units: 184 V to 550 V
Type voltage 690 V units: 400 V to 759 V
Auxiliary power supply
input voltage
90 VAC - 265 VAC (230 V 150 mA), or 24 VDC at 1 A
Fan input voltage (type
HF models)
230 V, 50/60 Hz, for fan current and current derating see
on page 3-9
AC line frequency
50/60 Hz nominal; 45 Hz to 65 Hz range
AC current
Type voltage 500 V ... VSC, see
Type voltage 690 V ... VSC units, see
Rated power
Dissipation
Current transformer ratio
Burden Resistor
Fuse
Ground connection
Chassis ground near AC connector suitable for ring lug connection
Clamp for grounding the control cable shields
Load description
Resistive load (minimum 100 W)
Resistive load R
warm
/R
cold
ratio up to 20 (MOSI starting mode)
Transformer load
External transformer
The induction of the load side transformer should not exceed 1.45T
in case of mains overvoltage when using grain-oriented, cold-rolled
plates. This corresponds to a nominal induction of approximately
1.3T.
Analog inputs
0(4) mA - 20 mA Ri = ca. 250 Ω / max. 24 mA. Max open-circuit
voltage = 24 V
0(1) V - 5 V Ri = ca. 6.6 kΩ / max. 12 V
0(2) V - 10 V Ri = ca. 11.1 kΩ / max. 12 V
Analog outputs
Signal level 0 V - 10 V, 0 mA - 20 mA or 4 mA - 20 mA. The
maximum burden voltage is 10 V. Short-circuit proof.
Advanced Energy
®
Thyro-PX® Power Controller
57010148-00B
Specifications
3‑4