17 

3.6 

Supervisory Condition 

When the system registers a supervisory condition, the internal buzzer sounds intermittently and the display 
shows the cause of the fault in more detail. An example of the display is shown below: 

    ZONE 0011               SUPERVISORY  
PLANT ROOM 
SPRINKLER SHUT OFF           (INPUT MON) 

 
< Location Text for First Zone 
< Location Text and Type of Device 

 

   1 Zone  In Supervisory          More> 

 

 
< No. of Zones in Supervisory 

 

To obtain more detailed information about the alarms, press the 

 button. The display then presents a list of all 

zones in an alarm condition. 

Supervisory conditions are typically (although not exclusively) used to indicate the presence of operating 
conditions that could prevent the operation of sprinkler valves such as; frozen water, valve shut-off, low 
pressure, etc. 

 

3.7 

Multiple Conditions 

When the system registers alarm, pre-alarm, fault, disablement, warning, security and supervisory conditions 
simultaneously, the display shows these in the lower half in priority order. The detail of the most recent 
unacknowledged condition to occur, however, is shown at the top of the display. An example of the display is 
shown below: 

    ZONE 0011               SUPERVISORY  
PLANT ROOM 
SPRINKLER SHUT OFF           (INPUT MON) 

 
< Location Text for First Zone 
< Location Text and Type of Device 

   1 Zone  In Alarm              ↓ More> 

   1 Zone  In Supervisory          More> 
   1 Zone  In Fault                More>  

 
< No. of Zones in Supervisory 

 

An arrow is shown on the display to indicate the scroll options. ↓ (first row), ↕, ↑ (last row) are shown depending 
on the row highlighted. 

Press the 



 buttons to scroll through the list to highlight the required condition and then press the 

 button to 

view more detail as described for each condition. 

If the system registers a fire alarm condition, the display is totally devoted to the indication of the fire alarm. Use 
the View Menu option to display these other conditions. 

 

3.8 

Menu Functions 

The following Menu Functions are available at Level 2. The display shows the primary Level 2 Menu and the 
Level 2 User as follows: 

[Level 2 Menu]            User 1 Node  1 
 
    

VIEW

       DISABLE       ENABLE 

    TEST       DELAY         TOOLS 
               STATUS 

 

The following table gives a list of the Level 2 Menu Functions, the sub-functions available within each main 
function and a brief description for each function. 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание MX-5101

Страница 1: ...Fire Alarm Panels User Manual The operation and functions described in this manual are available from Software Version 5000 050 04 onwards www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...2 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com...

Страница 3: ...EMENT CONDITION 15 3 4 1 Disabled Inputs 15 3 4 2 Disabled Outputs 16 3 5 ALARM CONDITION 16 3 6 SUPERVISORY CONDITION 17 3 7 MULTIPLE CONDITIONS 17 3 8 MENU FUNCTIONS 17 3 8 1 Using the Buttons to Na...

Страница 4: ...0 3 12 DELAYS 31 3 12 1 Turn Off Delay Mode 31 3 12 2 Turn On Delay Mode 31 3 12 2 1 Extend Delays 32 3 12 2 2 Holiday Inhibit 32 3 13 TESTING 33 3 13 1 Test Zones 33 3 13 2 Test Display 34 3 13 3 Tes...

Страница 5: ...uts Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input Output EN54 4 1997 A1 2002 A2 2006 Power supply equipment f...

Страница 6: ...ommissioning Manual Document No 680 165 for details of how to install and program the panel All panel models are available in a range of enclosure sizes and with a range of alternative optional featur...

Страница 7: ...E FAULT FIRE ROUTING ACTIVATED FIRE ROUTING FAULT FIRE ROUTING DISABLED PRE ALARM SOUNDER SILENCED SOUNDER FAULT Graphical Liquid Crystal Display Navigation Keys Zone LED Indicators Optional Number Ke...

Страница 8: ...Indicates that the circuit to fire extinguishing or other fire protection equipment has been activated or that the fire protection equipment itself has been activated Sounder Silenced Yellow Indicates...

Страница 9: ...l 2 Access Resound Press to re activate the sounders Only available with Level 2 Access Evacuate Press to initiate a manual evacuation and sound the alarms Only available with Level 2 Access LED Test...

Страница 10: ...Maintenance Engineer Special Tools required A Level 1 Untrained User can view the current operational condition of the system and may MUTE the internal buzzer NOTE Depending on the configuration setti...

Страница 11: ...mber is entered an asterisk is shown on the display For example CONTROLS DISABLED Please Enter Your Password If the password is correct the Level 2 Menu options will be shown If the password is incorr...

Страница 12: ...cation Text for First Zone Location Text and Type of Device 2 Zones in Fire Last Zone 0005 BASEMENT EAST No of Zones in Fire Last Zone Zone Description for Last Zone Press the MUTE button to silence t...

Страница 13: ...Delays The Investigation Delay Function can be disabled or enabled as required by EN54 2 Refer to Section 3 12 If the Investigation Delay Function Stage 1 Stage 2 Investigation Delay is enabled a fire...

Страница 14: ...the current time and date and service centre telephone number along with the indication of the fault FOR SERVICE CALL 01234 567890 LEVEL 2 16 05 04 MAR 2008 Panel access level Service Call Number and...

Страница 15: ...then press the button to view further information 3 4 1 Disabled Inputs The display presents a list of all of the zones in a disabled condition with the first disablement highlighted For example 2 Zo...

Страница 16: ...formation including type value and state etc Outputs in Zone 0100 More Mode Type Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER Disabled SOUNDER Press the buttons to scroll through the list of ind...

Страница 17: ...ondition to occur however is shown at the top of the display An example of the display is shown below ZONE 0011 SUPERVISORY PLANT ROOM SPRINKLER SHUT OFF INPUT MON Location Text for First Zone Locatio...

Страница 18: ...d disablement group ENABLE Zone Inputs Enable a complete zone or an individual input Outputs Enable sounder outputs or other devices Groups Enable a user defined disablement group Remote Permits remot...

Страница 19: ...to the normal operating display Press the Menu button to return directly to the Level 2 Menu display previously shown 3 8 1 2 Selecting Individual Zone Numbers When the display is showing a list of Zo...

Страница 20: ...in a Fault condition The operation of the panel and the information that can be shown is identical to the views available from the main operating display Refer to Section 3 3 for further information...

Страница 21: ...onal condition for all Outputs Outputs More Zone Location 0002 Reception 0003 Ground Floor 0013 First Floor Corridor 0014 First Floor Press the buttons to highlight the required zone and then press th...

Страница 22: ...optional interface cards 3 9 7 1 Software Software PANEL DISPLAY LOOP CARDS NETWORK PSU PERIPHERAL PRINTER Panel Software Software PROGRAM ID MX5000 050 04 CHECKSUM 92879016 Other Software Select the...

Страница 23: ...Earth Volts 0V 30V 2 5V 14 5V 6 Normal Too High Too Low System Volts 19V 30V 28 0V Normal Aux Load 0mA 500mA 5 Normal Too High 1 st Loop Load 7 0mA 500mA 5 Normal Open Circuit Too High Short Circuit...

Страница 24: ...buttons to highlight the required menu option and then press the button to select it The display then shows the appropriate list of events 3 9 8 1 Event Log The display will always show the most recen...

Страница 25: ...502 Pressing 0 allows the stored network status information to be cleared 3 9 10 View Warnings This Option can be used to obtain information about warning conditions on the panel A warning condition...

Страница 26: ...croll through the available zones or key in a specific zone number To disable the entire zone move over to the Mode column and highlight the existing mode Press the button and a pop up window appears...

Страница 27: ...TS FIRE PROTECTION OUTPUTS FAULT ROUTING OUTPUTS ALL OTHER RELAY OUTPUTS ONLY SELECTED OUTPUTS PAGERS 3 10 2 1 All Sounder Outputs Press the buttons to scroll through and highlight the ALL SOUNDERS Op...

Страница 28: ...able Menu 3 10 2 9 Only Selected Outputs Allows selection of a single output 3 10 3 Disable Controls Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation If the pane...

Страница 29: ...Disablement Groups are a means of disabling enabling custom groups of devices The commands are command across the network of panels and can be invoked from any panel The installer will have configured...

Страница 30: ...bled The individual outputs within the zone can then be enabled The display format is virtually identical to the equivalent Disable Menu 3 11 3 Enable Groups This option allows the re enabling of User...

Страница 31: ...ion delays in operation If the investigation delays are in operation then the Delayed LED Indicator is illuminated When the investigation delays are turned off the Delayed LED Indicator is turned off...

Страница 32: ...oliday periods On selection the display shows Inhibit Delay End Date TIME 15 49 DATE 02 07 08 WED 02 JUL 2008 Press the buttons to select the time date fields Enter the required time and date using th...

Страница 33: ...ssioning to define which of the sounders are activated during a test The display then shows a list of the available Zones and their current test status For example 0 Zones in Test Zone Test State Loca...

Страница 34: ...TEST option will cancel all zone tests The Test LED will then extinguish Alternatively it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the KEEP ZONES...

Страница 35: ...OM 0100 MAIN RECEPTION Press the buttons to scroll and highlight the required zone or key in the required zone number and then press the button to show the output devices in that zone For example Outp...

Страница 36: ...to confirm If the current User ID does not have the necessary permission the display prompts for entry of a password to guard against inadvertent changes Enter the password as normal The display then...

Страница 37: ...printed includes Device Text Zone Number Loop and address current status and analogue value 3 14 1 4 Print Outputs To print information on any output highlight the Outputs option and press the button...

Страница 38: ...number keys to change the zone number as required Press the key to start printing The printout will show the location and state of all input and output points in a disabled condition for the zones se...

Страница 39: ...09 To change the settings use the buttons to highlight the required option Directly enter the new time or date using the number buttons As soon as a number button is pressed the display will clear the...

Страница 40: ...40 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com...

Страница 41: ...41 This page is intentionally blank www acornfiresecurity com www acornfiresecurity com...

Страница 42: ...42 USER NOTES www acornfiresecurity com www acornfiresecurity com...

Страница 43: ...www acornfiresecurity com www acornfiresecurity com...

Отзывы: