background image

TCX 126 

Two-Wire Isolated Thermocouple Transmitter 

Instruction Manual 

1.0  INTRODUCTION 

These instructions refer to the above model. Supplementary 

sheets are attached if the unit has special options or features. 

For detailed specifications,  see page 4 or refer to the Data 

Bulletin.  All ADTECH instruments are factory calibrated and 

supplied with a label detailing the calibration. Adjustments are 

normally  not necessary.  A  simple  calibration  should  be 

performed to verify calibration before installation. 

2.0  GENERAL DESCRIPTION 

The  ADTECH  Model  TCX 126  Isolated  Two-Wire 

Thermocouple Transmitter provides high accuracy conversion 

of ISA type J, K, T, E, R, S and B thermocouples and mv to a 

standard 4-20 ma de process signal. 

The TCX 126 provides 350 volts ac or 600 volts de isolation 

from the input to outpuVpower supply. 

The primary features of the TCX 126 are: 

• Wide range - covers the  full  range of  ISA standard

thermocouples and mv.

• Field  adjustable  via  front  accessible  switches  and

potentiometers.

• Zero suppression of up to 100% of the major range with

a16 position switch.

• High accuracy, repeatability, and ambient temperature

effect stability.

• RFI Protection:  Standard.

• NO INTERACTION of zero and span controls.

• Small  size  - universal  mounting  package  provides

integral RFI protection and an environmental seal.

• Options  for  NEMA  4  and  NEMA  7  housings,  SNAP

TRAK and DIN rail mounting (DIN 46 277 standard).

3.0  INSTALLATION 

The  instrument  is  supplied  in  a  sturdy  die  cast  aluminum 

housing with an epoxy paint finish. The housing is gasketed 

providing  an environmental seal for the internal  electronics 

and controls. NEMA 4, NEMA 7 and 12, Snap Track and DIN 

rail  (TS32  and  TS35)  are  optionally  available.  Installation 

area I  location  must  agree  with  the  supplied  instruments 

including operating temperature and ambient conditions. 

Mounting 

Refer to page 3 for outline and mounting dimensions.  The 

standard instrument is surface mounted with integral #6-32 

S.S. thumb screws. 

Electrical Connections 

The 

wire 

used to connect the instrument to the control system 

Input/ Output 

should be twisted pair(s) and sized according 

to normal practice. Shielded cable is not normally necessary 

(if used, the shield must be grounded at the negative input of 

the ADTECH instrument and left floating at the sensor). 

Two barrier terminal  blocks  with  #6-32  screws  and  0.325" 

spacing are provided for I/ 0 connections. 

Controls 

Instrument controls consist of the following: 

• Two 16 position switches for 

COARSE 

ZERO and SPAN

control.

• One 8 position dip switch for selection of thermocouple

and major range.

• Two multiturn potentiometers; 

FINE 

ZERO and SPAN

controls.

All controls are accessible through the front of the instrument. 

An integral gasketed cover provides an environmental seal for 

the controls and internal electronics when the controls are not 

in use. 

4.0  MAINTENANCE 

These instruments are electronic and require no maintenance 

except periodic cleaning and calibration verification. If the unit 

appears to be mis-operating, it should be checked as installed 

per section 6.0 or removed for a bench check per sections 6.0 

and 7.0. MOST problems are traced to field wiring and/ or 

associated  circuits.  If  the  problem  appears  to  be  with  the 

instrument, proceed to sections 6.0 and 7.0. 

5.0  CONNECTIONS 

Standard connections are shown below and on the instrument 

face plate, Data Bulletin or on attached supplementary sheets. 

Q)

®

(Tl 

ljl

�c 

LOOPl+I 

® 

®  © 

HSUPPLY 

®  I 

NOTE 1:  Terminal  #3  should  not  have  any  customer 

connections. 

NOTE 2:  Intrinsically safe when connected per  Installation 

DWG 270-A-000003. 

-1-

190-A-000051-8