Hydraulic pressure drop
The boiler pressure drop depends on the water flow; the maximum ∆T must be 25 ºC:
If you have to stop the boiler pump, it is required that you stop it with a time delay of 3 to 5 minutes once the
boiler has stopped. This can be obtained by installing a timer-disconnect electrical relay.
Pressure drop NEO FIRE 80-280
Nominal ΔT is 20ºC
Maximum ΔT is 25ºC
Flowrate higher than max indicated can damage the heat exchanger
FLOWRATE at maximum power [m
3
/h]
NEO FIRE
80
120 160 200 240 280
nominal
3,44 5,16 6,87 8,59 10,3 12
min
2,75 4,12 5,5 6,87 8,25 9,62
max
6,8 10,3 13,6 16,4 19,1 21,8
Содержание NEO FIRE 120
Страница 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Страница 6: ...NEO FIRE Technical Manual 6 4 BOILER GENERAL VIEW DESCRIPTION OF THE COMPONENTS NEO FIRE 80 280 ...
Страница 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Страница 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Страница 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Страница 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Страница 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Страница 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Страница 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Страница 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Страница 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Страница 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...