User Manual   

DALI / PROFINET

 

 

Document code: MN67848_ENG     Revision 1.001   Pagina 1 di 42

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

 

User Manual 

Revision 1.001 
English 

 

DALI / PROFINET - Converter 

 (Order Code:  HD67848-B2-Y, HD67848-B2-N) 

 
for Website information:  

www.adfweb.com?Product=HD67848

  

 

for Price information: 

www.adfweb.com?Price=HD67848-B2

  

 
 

Benefits and Main Features: 

 

Very easy to configure 

 

Electrical isolation 

 

Temperature range: -40°C/85°C (-40°F/185°F) 

 

For others DALI products, see also the following links: 

 

Converter DALI to  

www.adfweb.com?Product=HD67832

      

(BACnet/IP Master) 

www.adfweb.com?Product=HD67833

       

(BACnet/IP Slave) 

www.adfweb.com?Product=HD67839

      

(Ethernet) 

www.adfweb.com?Product=HD67840

      

(PROFINET) 

www.adfweb.com?Product=HD67844

      

(Modbus TCP Master) 

www.adfweb.com?Product=HD67845

       

(Modbus TCP Slave) 

www.adfweb.com?Product=HD67849

      

(SNMP Manager) 

www.adfweb.com?Product=HD67850

      

(SNMP Agent)

 

 

 

Do you have an your customer protocol? 

www.adfweb.com?Product=HD67003

 

 

Do you need to choose a device? do you want help? 

www.adfweb.com?Cmd=helpme

 

 

User Manual   

 

Содержание HD67848

Страница 1: ...e Electrical isolation Temperature range 40 C 85 C 40 F 185 F For others DALI products see also the following links Converter DALI to www adfweb com Product HD67832 BACnet IP Master www adfweb com Pro...

Страница 2: ...OTHER REGULATIONS AND STANDARDS 41 WARRANTIES AND TECHNICAL SUPPORT 42 RETURN POLICY 42 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check tha...

Страница 3: ...tc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly...

Страница 4: ...ial Electronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 4 di 42 EXAMPLE OF CON...

Страница 5: ...ces ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 5 di 42 CONNECTION SCHEME Figure 1 Connec...

Страница 6: ...et Additional isolation Power Supply DALI for HD67848 B2 N version Two directional information between DALI bus and PROFINET bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12...

Страница 7: ...PROFINET Document code MN67848_ENG Revision 1 001 Pagina 7 di 42 POWER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vma...

Страница 8: ...o functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Swit...

Страница 9: ...uickly Boot state Blinks very slowly 0 5Hz update in progress 2 Ethernet communication yellow Blinks when Ethernet communication is running Blinks quickly Boot state Blinks very slowly 0 5Hz update in...

Страница 10: ...he lighting system from a simple light switch to lighting management systems for entire office complexes with thousands of light sources Using ADFweb com s DALI converters any light source including i...

Страница 11: ...for programming DALI network and for programming the device The Ethernet connection must be made using Connector2 of HD67848 B2 with at least a Category 5E cable The maximum length of the cable should...

Страница 12: ...the available software that runs with Windows called SW67848 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last versio...

Страница 13: ...contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a Programmable DALI PROFINET Converter in order to configure another...

Страница 14: ...s the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connect...

Страница 15: ...one 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 15 di 42 In the section Software Settings it is possible to enable disable some keyboard s commands for a...

Страница 16: ...eld GATEWAY the default gateway of the Ethernet network is defined This feature can be enabled or disabled pressing the Check Box field This feature is used for going out of the net In the field Port...

Страница 17: ...ct the DALI Device Present in the Network appears Fig 4 This section is used to define the DALI devices connected to the converter It is enough to check uncheck the connected unconnected DALI devices...

Страница 18: ...ton Device Found must appear Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn off the Devic...

Страница 19: ...ing Try with another PC Try to restart the PC Check the LAN settings Check the Wi Fi settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are u...

Страница 20: ...est the communication it is possible to use the available software that runs with Windows called DALI Console It is downloadable on the site www adfweb com and its operation is described in this docum...

Страница 21: ...uctured in this way Menu bar Fig 8 Point 1 it is possible to open the setup window and see the informations about the DALI Console software Network view Fig 8 Point 2 it is possible to see all the DAL...

Страница 22: ...the SETUP window are In the field DEVICE IP ADDRESS insert the IP address set inside the converter In the field PRG PORT insert the communication port used for the Ethernet communication with the con...

Страница 23: ...the single scene or the entire DALI network it is possible to manage and test the functioning of the network DEVICES The means of the fields for DEVICE INFO are In the field Device Type the type of D...

Страница 24: ...mum ADV value In the GROUP MEMBERSHIP section it is possible to see the Groups which the selected DALI device is in The checked checkboxes mean that the device is in the correspondent groups the unche...

Страница 25: ...group For set commands it is possible to insert the value to set in the field xx As soon as the command to send is selected the command is sent in order to send the same command more times it is possi...

Страница 26: ...Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 26 di 42 SCENES By selecting a DALI scene from the Network view it is possible to see the devices that have programmed the selecte...

Страница 27: ...nds it is possible to insert the value to set in the field xx As soon as the command to send is selected the command is sent in order to send the same command more times it is possible to press the SE...

Страница 28: ...OUT data that the PROFINET Master can read For each DALI node configured the converter will reserve 8 bytes The map is generated dynamically in relation to the number of nodes defined using the SW6784...

Страница 29: ...value of DALI node 6 Each bit has a different meaning 0 means Group not configured 1 means Group configured Bit 0 less significant Group 0 Bit 1 Group 1 Bit 2 Group 2 Bit 3 Group 3 Bit 4 Group 4 Bit 5...

Страница 30: ...on DALI node 1 2 ADV to set on DALI node 2 3 ADV to set on DALI node 3 4 ADV to set on DALI node 4 5 ADV to set on DALI node 5 6 ADV to set on DALI node 6 7 ADV to set on DALI node 7 8 ADV to set on...

Страница 31: ...on DALI node 26 27 ADV to set on DALI node 27 28 ADV to set on DALI node 28 29 ADV to set on DALI node 29 30 ADV to set on DALI node 30 31 ADV to set on DALI node 31 32 ADV to set on DALI node 32 33...

Страница 32: ...7 48 ADV to set on DALI node 48 49 ADV to set on DALI node 49 50 ADV to set on DALI node 50 51 ADV to set on DALI node 51 52 ADV to set on DALI node 52 53 ADV to set on DALI node 53 54 ADV to set on D...

Страница 33: ...T byte Description 64 ADV to set on Group 0 65 ADV to set on Group 1 66 ADV to set on Group 2 67 ADV to set on Group 3 68 ADV to set on Group 4 69 ADV to set on Group 5 70 ADV to set on Group 6 71 ADV...

Страница 34: ...FINET Document code MN67848_ENG Revision 1 001 Pagina 34 di 42 ADV SETTING BROADCAST PROFINET byte Description 80 ADV to set Note The range of ADV can be from 0 to 255 The minimum and the maximum valu...

Страница 35: ...e increased of 1 every times that the command must be sent on DALI 129 ID of DALI device to command for commands most significant bit must be set to 1 as DALI specifications 0 63 Single DALI device 64...

Страница 36: ...Pagina 36 di 42 PLC CONFIGURATION The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the TIA Portal software of Siemens...

Страница 37: ...no Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 37 di 42 2 Import the module in the network connect the device to the PL...

Страница 38: ...ronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 38 di 42 3 Load the configurati...

Страница 39: ...com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual DALI PROFINET Document code MN67848_ENG Revision 1 001 Pagina 39 di 42 MECHANICAL DIMENSIONS Figure 14 Mechanical...

Страница 40: ...the converter feeds the DALI bus N not present the converter doesn t feed the DALI bus Connectors Type 2 Fixed 5mm Screw Terminal Enclosure Type B 2M 35mm DIN Rail mounting Device Family HD67848 DALI...

Страница 41: ...ntries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable c...

Страница 42: ...xchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the...