Document code: MN67801_ENG Revision 1.100 Pagina 25 di 31
In the field “
D Adr
” the address of the endpoint is defined. If “D Len” is ‘1’ it is possible to insert a number from 1 to 255; if “D Len”
is ‘2’ it is possible to insert a number from 1 to 65535; if “D Len” is ‘6’ it is possible to insert an IP and port in this format
“192.168.2.188:47808”;
By checking the field “
Change
” the BACnet write request is made only if KNX data are changed; otherwise (if is selected the field
“
Timer
”) is sent cyclically, using the “Poll Time”;
In the field “
Poll Time
” define the frequency of the request;
In the field “
Max Error
” insert the number of consecutive errors that the Master waits before discard the row from the cycle of
requests;
In the field “
Position
” is possible to select the position where take the data to write in the request from a 1440 bytes array;
The field “
Start Bit
” is used for the “Binary Output” BACnet objects. Is possible to select the position in the byte where save the
data;
In the field “
Mnemonic
” is possible to insert a description of the data inserted in the row.