background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l.           

 

User Manual   

Modbus TCP Slave / Modbus Master

 

 

Document code: MN67507_ENG     Revision 2.400    Page 9 of 45

 

 

Figure 1d: Connection scheme for HD67507-Slim-232

 

 

Содержание HD67507-A1

Страница 1: ...vanic Isolation Temperature range 40 C 85 C 40 F 185 F For others products see also the following links RS232 RS485 USB Ethernet www adfweb com Product HD67118 RS232 RS485 Converter www adfweb com Pro...

Страница 2: ...RETURN POLICY 45 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To...

Страница 3: ...ED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissio...

Страница 4: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 4 of 45 EXAMPLES OF CONNECTION...

Страница 5: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 5 of 45...

Страница 6: ...dustrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 6 of 45 CONNECTION SCHEME Figure 1a Connection scheme for HD67507...

Страница 7: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 7 of 45 Figure 1b Connection scheme for HD67507 A1 422...

Страница 8: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 8 of 45 Figure 1c Connection scheme for HD67507 B2...

Страница 9: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 9 of 45 Figure 1d Connection scheme for HD67507 Slim 232...

Страница 10: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 10 of 45 Figure 1e Connection scheme for HD67507 Slim 485...

Страница 11: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 11 of 45 Figure 1f Connection scheme for HD67507 WiFi B2 232...

Страница 12: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 12 of 45 Figure 1g Connection scheme for HD67507 WiFi B2 485...

Страница 13: ...on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F This HD67507 A1 B2 is able to manage a maximum of ten simultaneous connections from Et...

Страница 14: ...n be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at 24V DC Device Consumption W VA HD67507 A1 3 5 HD67507 A1 422...

Страница 15: ...g on the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Switch A at ON position is us...

Страница 16: ...s when Modbus frame RS232 RS485 RS422 are received Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Ethernet Link ON Ethernet cable connected OFF Ethernet cable disconnected ON...

Страница 17: ...ks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Modbus comm Blinks when Modbus frame RS232 RS485 are received Blinks quickly Boot state Blinks very slowly 0 5Hz u...

Страница 18: ...ks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Modbus comm Blinks when Modbus frame RS232 RS485 are received Blinks quickly Boot state Blinks very slowly 0 5Hz u...

Страница 19: ...he T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to a Hub Switch the use of a straight cable is recommended To connect the device to a PC PLC other the use of a cros...

Страница 20: ...able a serial cable where the pins 2 and 3 are crossed It is recommended that the RS232 cable not exceed 15 meters The HD67507 A1 B2 is provided with a D sub connector type DE 9 Male also called DB 9...

Страница 21: ...evices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 21 of 45 RS485 To terminate the RS485 line with a 120 resistor it is necessary to put d...

Страница 22: ...irs conductor foil shield braid shield Belden p n 82842 2x 24AWG stranded twisted pairs conductor foil shield braid shield Tasker p n C521 1x 24AWG twisted pair conductor foil shield braid shield Task...

Страница 23: ...at runs with Windows called SW67507 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present...

Страница 24: ...iguration A device s configuration can also be imported or exported To clone the configurations of a programmable Modbus TCP Slave Modbus Master Converter in order to configure another device in the s...

Страница 25: ...nge the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possib...

Страница 26: ...CATION By Pressing the Set Communication button from the main window for SW67507 Fig 2 the window Set Communication appears Fig 3 The window is divided in different sections in order to define the dif...

Страница 27: ...i ETHERNET CONNECTION The means of the fields for Ethernet Connection are In the field Device Name Hostname the Hostname to assign to the converter is defined If the field Obtain an IP Address Automat...

Страница 28: ...e The means of the fields are In the field Serial the serial port to use is defined In the field Baudrate the baudrate for the serial line is defined In the field Parity the parity of the serial line...

Страница 29: ...made at Port 64223 FADF with these six byte of data 53 45 41 52 43 48 Each device in response sends a total of 10 Bytes These bytes are four for the IP and the other for the MAC address Example of re...

Страница 30: ...nabled or disabled pressing the Check Box field This feature is used for going out of the net In the field SSID the name of the Wi Fi network to create is defined In the field Password the password us...

Страница 31: ...ess using DHCP Otherwise the IP Address is defined as static In the field IP Address the IP address of the converter is defined In the field Subnet Mask the SubNet Mask of the converter is defined In...

Страница 32: ...de of the converter is defined In the field Subnet Mask the SubNet Mask of Modbus TCP side of the converter is defined In the fields GATEWAY the default gateway of the net is defined This feature can...

Страница 33: ...sing the last byte of the MBAP header it is possible to carry out the routing from a requested Modbus TCP toward a serial line using the address from the slave which is specified by the byte unit iden...

Страница 34: ...Table appears Fig 4 The data of the columns have the following meanings In the field Data Type the type of data for the Modbus translation is defined In the field Slave ID TCP the address of the virtu...

Страница 35: ...een Coil Status bit in read write Input Status bit in read Holding Register word in read and write Input Register word in read From the side of the MODBUS TCP Address of data to read From the side of...

Страница 36: ...ear Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip2 of Dip Switch...

Страница 37: ...ing Try with another PC Try to restart the PC Check the LAN settings Check the Wi Fi settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are u...

Страница 38: ...m S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 38 of 45 MECHANICAL DIMENSIONS Figure 7a Mechanical dimensions scheme for HD67507 A1 Figure 7b Mechanic...

Страница 39: ...Industrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 39 of 45 Figure 7c Mechanical dimensions scheme for HD67507 B2...

Страница 40: ...strial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 40 of 45 Figure 7d Mechanical dimensions scheme for HD67507 WiFi B2...

Страница 41: ...dustrial Electronic Devices ADFweb com S r l User Manual Modbus TCP Slave Modbus Master Document code MN67507_ENG Revision 2 400 Page 41 of 45 Figure 7e Mechanical dimensions scheme for HD67507 Slim x...

Страница 42: ...07 A1 and HD67507 B2 232 RS232 only for HD67507 WiFi B2 xxx and HD67507 Slim xxx 485 RS485 only for HD67507 WiFi B2 xxx and HD67507 Slim xxx 422 RS422 only for HD67507 A1 Connectors Type 1 Removable 5...

Страница 43: ...232 Modbus TCP Slave Modbus Master Converter Modbus TCP Ethernet Modbus RTU RS232 Order Code HD67507 Slim 485 Modbus TCP Slave Modbus Master Converter Modbus TCP Ethernet Modbus RTU RS485 Order Code...

Страница 44: ...lection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the...

Страница 45: ...se do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product...

Отзывы: