Connecting 200-240 VAC Power to Robot
Adept Cobra i600/i800 Robot User’s Guide, Rev E
51
Facility Overvoltage Protection
The user must protect the robot from excessive overvoltages and voltage spikes. If the
country of installation requires a CE-certified installation, or compliance with
IEC
1131-2,
the following information may be helpful:
IEC
1131-2 requires that the installation must
ensure that Category II overvoltages (i.e., line spikes not directly due to lightning strikes)
are not exceeded. Transient overvoltages at the point of connection to the power source
shall be controlled not to exceed overvoltage Category II, i.e., not higher than the impulse
voltage corresponding to the rated voltage for the basic insulation. The user-supplied
equipment or transient suppressor shall be capable of absorbing the energy in the
transient.
In the industrial environment, non-periodic overvoltage peaks may appear on mains
power supply lines as a result of power interruptions to high-energy equipment (such as a
blown fuse on one branch in a 3-phase system). This will cause high current pulses at
relatively low voltage levels. The user shall take the necessary steps to prevent damage to
the robot system (such as by interposing a transformer). See
IEC
1131-4 for additional
information.
AC Power Diagrams
Figure 4-8. Typical AC Power Installation with Single-Phase Supply
DANGER:
AC power installation must be performed by a
skilled and instructed person - see
. During installation, unauthorized third parties
must be prevented from turning on power through the use
of fail-safe lockout measures.
E
E
N
L
L
F1 10 A
Adept Cobra
s600/s800 and
i600/i800 Robots
1 Ø 200–240 VAC
User-Supplied
AC Power Cable
Note: F1 is user-supplied, must be slow blow.
1 Ø
200–240 VAC
L = Line
N = Neutral
E = Earth Ground
N
20 A
Содержание Adept Cobra i600
Страница 1: ...Adept Cobra i600 i800 Robot User s Guide ...
Страница 2: ......
Страница 10: ......
Страница 14: ......
Страница 34: ......
Страница 56: ...Chapter 4 System Installation 56 Adept Cobra i600 i800 Robot User s Guide Rev E ...
Страница 76: ...Chapter 5 Optional Equipment Installation 76 Adept Cobra i600 i800 Robot User s Guide Rev E ...
Страница 104: ...Chapter 6 System Operation 104 Adept Cobra i600 i800 Robot User s Guide Rev E ...
Страница 116: ...Chapter 7 Maintenance 116 Adept Cobra i600 i800 Robot User s Guide Rev E ...
Страница 147: ...Index Adept Cobra i600 i800 Robot User s Guide Rev E 147 ...
Страница 148: ......
Страница 149: ......
Страница 150: ...5960 Inglewood Drive Pleasanton CA 94588 925 245 3400 P N 03589 000 Rev E ...