background image

N7227V6  7/01 

9

9

,

,

6

6

7

7

$

$

6

6

(

(

6HFXULW\6\VWHP

 

 

 

 

 

 

,QVWDOODWLRQDQG6HWXS*XLGH

 

 

 

 

 

ARMED

READY

PANIC

OFF

AWAY

STAY

MAX

TEST

BYPASS

INSTANT

CODE

CHIME

READY

1

2

3

6

5

4

8

9

7

0

*

#

ON

OFF

*

 

 

 
 
 
 
 

®

 

 

 

 

Содержание VISTA-10ES

Страница 1: ...N7227V6 7 01 9 9 6 67 7 6 6 6HFXULW 6 VWHP QVWDOODWLRQ DQG 6HWXS XLGH ARMED READY PANIC OFF AWAY STAY MAX TEST BYPASS INSTANT CODE CHIME READY 1 2 3 6 5 4 8 9 7 0 ON OFF...

Страница 2: ...n the hallway outside may not wake up the sleeper if the door is closed DINING KITCHEN BEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOM BEDROOM BDRM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM...

Страница 3: ...lling a 4285 or 4286 VIP Module 2 9 Standard Phone Line Connections 2 10 Long Range Radio Connections 2 11 Audio Alarm Verification AAV Connections 2 11 Section 3 Programming Overview 3 1 About Progra...

Страница 4: ...arm Displays if programmed 10 2 Section 11 Testing the System 11 1 Local Tests 11 1 Communication Tests 11 1 Transmitter Sniffer Mode 11 1 Go No Go Test Mode 11 2 Automatic Standby Battery Tests 11 2...

Страница 5: ...ector Connections Zone 5 2 6 Figure 2 9 5881 5882 RF Receiver 2 7 Figure 2 10 4204 Connections to Control 2 9 Figure 2 11 4285 4286 VIP Module Wiring Connections 2 10 Figure 2 12 Standard Telephone Li...

Страница 6: ...onal difficulties This symbol warns of conditions that could seriously affect the operation of the system or cause damage to the system Please read each warning carefully This symbol also denotes warn...

Страница 7: ...e to the central station Keypad Panic Keys Up to 3 programmable panic key functions are provided Designated as Zones 7 95 96 Activated by wired and wireless keypads Reported separately Paging Feature...

Страница 8: ...rrupts for smoke detector reset if 4 wire smoke detectors are used Programming Programmed options are stored in electrically erasable nonvolatile EEPROM memory information can be reprogrammed at any t...

Страница 9: ...the door is closed 4 When correctly positioned push the lock until it is held securely by its snap tabs Notes Use an ADEMCO No N4445 Lock The cabinet can be closed and secured without a lock by using...

Страница 10: ...o the cabinet with the screws provided as shown in Detail B 8 Insert the receiver s antennas through the top of the cabinet into the blocks right hand terminals and tighten the screws Refer to setup a...

Страница 11: ...24m 18 1300 ft 396m 650 ft 198m 220 ft 67m 130 ft 39 6m 16 1500 ft 457m 1000 ft 305m 330 ft 100 5m 200 ft 70m Includes keypads RF receivers relay units and 4285 4286 VIP Modules The length of all wir...

Страница 12: ...ARD ALARM OUTPUT TERMINALS CUT RED JUMPER ON CONTROL BOARD TO ENABLE BELL SOUNDER SUPERVISION IF BELL SUPERVISION IS ENABLED RED JUMPER ON CONTROL BOARD IS CUT CONNECT A 1000 OHM RESISTOR ACROSS THE E...

Страница 13: ...fornia State Fire Marshal and UL Residential Fire requirements statement below if applicable UL Only use a 17 2AH battery for UL installations OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP RE...

Страница 14: ...he loop The EOL resistor must be connected in series with the devices following the last device See the Summary of Connections diagram Connect open circuit devices in parallel across the loop The 1000...

Страница 15: ...in a nominal range of 200 feet Take this into consideration when determining mounting location 3 Connect the receiver s wire harness to the control s keypad terminals 4 5 6 and 7 Plug the connector at...

Страница 16: ...ived from each supervised transmitter within a 12 hour period the missing transmitter number s and the message CHECK is displayed NOTE Refer to the listing of compatible devices in SECTION 13 Specific...

Страница 17: ...module is disconnected from the control s terminals or if the module cover is removed and the tamper jumper is installed Alpha keypads DEV xx Wire Expansion Fault Fixed Word keypads lxx where xx is th...

Страница 18: ...AUX term 5 BLACK TO AUX GROUND term 4 GREEN TO DATA IN term 6 CONNECTOR WITH FLYING LEADS TO CONTROL PANEL TERMINALS USED FOR KEYPAD CONNECTIONS PREMISES ANSWERING MACHINE AND PHONES Handset Incoming...

Страница 19: ...sent in Contact ID format not affected by entry in field 46 You must enable field 27 OUTPUT TO LONG RANGE RADIO if this feature is to function UL For UL installations Long Range Radio must be disabled...

Страница 20: ...NC C TO PREMISES HANDSET AAV_conn V0 Figure 2 13 Connection of AAV Unit When Not Using a 4285 4286 VIP Module CONTROL DIALER HEADER NOTE REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEA...

Страница 21: ...zone type to each zone which defines the way in which the system responds to faults in that zone Zone types are defined below Zone Type Description Characteristics Type 00 Zone Not Used Program a zone...

Страница 22: ...Supervised Fire Zone type 09 can be assigned to any wireless zone used as a fire zone This zone type is always active and cannot be bypassed Bell output will pulse when this zone type is alarmed Type...

Страница 23: ...mber and download telephone number fields Interactive Mode Programming 56 58 80 81 and 82 Enter Interactive Mode Press Interactive Mode No for example 56 while in Program Mode The Alphanumeric display...

Страница 24: ...VISTA 10SE Installation and Setup Guide 3 4...

Страница 25: ...ystem However the user code is always needed to disarm the system 22 RF Jam Option 0 if no receiver is being used 2 5800 system receiver no jam detection 4 5800 system receiver with jam detection This...

Страница 26: ...This field determines whether the external sounder will shut off after time allotted or continue until manually turned off UL installations must be set for a minimum of 4 min option 1 38 Entry Delay...

Страница 27: ...g is to be used See field 27 which may override this field s selection NOTE The maximum number of alarm and alarm restore reports during one armed period is determined by field 92 47 Split Dual Report...

Страница 28: ...ding when RF arming this works with either a button RF unit or a 5827 52 Zone 3 Response Time To Open 0 400 milliseconds nominal 1 10 milliseconds nominal Selects response time of sensor in zone 3 to...

Страница 29: ...ith up to a 48 minute delay The AC RESTORE report has a random delay of about 12 minutes If AC restores before the report goes out there is no AC RESTORE report 63 LOW BAT Report Code 0 no report For...

Страница 30: ...able on previous page for method of programming report codes This is a 2 digit entry field This is sent in the event that a wireless transmitter low battery condition exists 68 Cancel Report Code 0 no...

Страница 31: ...n system 4 AAV unit is being used 8 Exit Delay Restart 12 AAV Exit Delay Restart AAV should not be used when Paging or Alarm Reports are being sent to a secondary number If this is done the call to th...

Страница 32: ...nd program this field accordingly VIP Module Answering Machine Downloading Field 95 Yes No No Set for value other than 0 1 14 This will enable the control panel to answer the phone call Otherwise it w...

Страница 33: ...t use if previously programmed with other values TO EXIT PROGRAMMING MODE 98 or 99 98 EXITS PROGRAMMING MODE Prevents reentry by INSTALLER Code 8 0 To enter the Programming mode if 98 was used to exit...

Страница 34: ...VISTA 10SE Installation and Setup Guide 4 10...

Страница 35: ...ng control panels of this type NOTE Alpha display prompts are shown in a double line box 56 Zone Programming Procedure Zone Programming involves 1 Entering the programming mode by pressing 20 2 Pressi...

Страница 36: ...unsupervised RF transmitter 5 BR Button type RF transmitter unsupervised to continue For the built in hardwired zones 01 06 the Input Device type is automatically displayed as HW and cannot be edited...

Страница 37: ...t obtained i e summary display does not appear press the key twice and enter the correct loop input or if correct press the key again and then enter the correct serial number Zn ZT RC In L 10 03 10 RF...

Страница 38: ...RF 5816 ENROLL AS RF LOOP 2 REED LOOP 1 TERMINALS 5827 SET HOUSE CODE 5827BD SET HOUSE CODE 5816MN ENROLL AS RF LOOP 2 REED LOOP 1 TERMINALS 5819 ENROLL AS RF LOOP 2 REED LOOP 1 TERMINALS ALTERNATE PO...

Страница 39: ...Wireless Keys paragraph on a following page in this section When D is pressed you can choose from a series of preset templates for easy programming of wireless key zones When all zones have been prog...

Страница 40: ...ntinue If the serial number transmitted matches the serial number entered the keypad beeps 3 times and advances to the Summary display of the next zone to be programmed NOTE Following the successful e...

Страница 41: ...Example zone number 10 10 INPUT S N L A022 4064 1 4 Press repeatedly until the prompt at left appears This is the transmitter serial number and loop number that is presently programmed for this zone 5...

Страница 42: ...mber 5a TKH V VWHP VHDUFKHV IRU WKH KLJKHVW RQH QXPEHU DYDLODEOH VXEWUDFWV WKH QXPEHU RI FRQVHFXWLYH RQHV UHTXLUHG IRU WKH GHYLFH IRXU RQHV LQ WKH FDVH RI WKH DQG DQG GLVSOD V WKH ORZHVW RQH QXPEHU RI...

Страница 43: ...relevant to that device This information will be useful if any troubleshooting is needed later on The installer may want to consider leaving this worksheet at the site in the panel cabinet Wireless K...

Страница 44: ...VISTA 10SE Installation and Setup Guide 5 10...

Страница 45: ...that must occur to a zone or group of zones zone list in order to activate the relay These conditions apply only when a zone list is used The different choices for EVENT are listed below and in the P...

Страница 46: ...ally activate or de activate the relay s for starting or stopping some action such as turning lights on or off etc These entries are Security Code 7 and Security Code 8 NOTE Whichever entry is used to...

Страница 47: ...t Not Used 0 START Event to continue Enter the event to START the relay 0 Not used 2 Fault 1 Alarm 3 Trouble A zone list must be used in conjunction with an event If a zone type system operation is to...

Страница 48: ...ns This is a review mode only and data cannot be changed Example of Relay Programming A lamp is to be turned on when any one of three specific zones are faulted or when any 24 hour auxiliary zone is f...

Страница 49: ...Zone List number 01 02 or 03 you want to program or 00 to end these entries In the following displays zone list 01 has been selected for programming 01Enter Zn Num 00 Quit 00 Zone Number 01 25 zone l...

Страница 50: ...igned to more than one output relay If you only want to review what has been programmed previously press 81 The review can be advanced by using the key When finished press 00 to quit No programmed val...

Страница 51: ...memory see the list on a following page In addition up to 5 installer defined custom words can be added to those already in memory Thus when an alarm or trouble occurs in a zone an appropriate descrip...

Страница 52: ...NOTE If you accidentally enter the wrong word simply press plus the correct 3 digit number for the word you want ZN 01 B ACK Flashing Cursor if 6 is pressed system is ready for next word 8 Press 6 to...

Страница 53: ...ustom word enter 2 etc A flashing cursor will now appear at the beginning of the second line on the display C u s t o m 1 Flashing Cursor 3 To enter the custom word characters refer to the CHARACTER A...

Страница 54: ...TOR N 134 NORTH 135 NURSERY O 136 OFFICE 138 OPEN 139 OPENING 140 OUTSIDE 142 OVERHEAD P 143 PAINTING 144 PANIC 145 PASSIVE 146 PATIO 147 PERIMETER 148 PHONE 150 POINT 151 POLICE 152 POOL 153 POWER R...

Страница 55: ...hone number and eight attempts to the secondary telephone number if programmed to get a valid message through If the panel is not successful after its numerous attempts the keypad will display Communi...

Страница 56: ...RZ AC Restore SSS S RA SSS S RA RARARA RA Ac SSSSRA Ac LoBat Res SSS S RL SSS S RL RLRLRL RL LB SSSSRLLB Trouble Res SSS S RT SSS S RT RTRTRT RT t SSSS RTt Bypass Res SSS S RB SSS S RB RBRBRB RB b SS...

Страница 57: ...132 Alarm Interior Burg 134 Alarm Entry Exit Burg 135 Alarm Day Night Burg 150 Alarm 24 Hour Auxiliary 301 AC Power 302 Low System Battery Battery Test Fail 321 Bell Siren Trouble 333 Expansion Modul...

Страница 58: ...VISTA 10SE Installation and Setup Guide 9 4...

Страница 59: ...e a Duress code enter Master code 8 key 8 key desired 4 digit Duress Code To delete a Duress code enter Master code 8 key 8 key and stop The Duress Code must differ from the Master Code or any other U...

Страница 60: ...anually activate or deactivate the relay s for starting or stopping some action such as turning lights on or off etc These keypad entries are Security Code 7 and Security Code 8 NOTE The keypad entry...

Страница 61: ...ault one or more perimeter zones After 15 seconds silence alarm sounder s by entering the security code and pressing the OFF 1 key Arm the system AWAY and check the Entry Exit zones for the programmed...

Страница 62: ...rs indicates that a problem exists with the displayed zone s and requires attention A display of CHECK and 09 indicates that communication between control and a zone expander or wireless receiver is i...

Страница 63: ...E CAUSE REMEDY 1 AC POWER light off or NO AC displayed 1a Interrupted primary AC power 1a Check transformer connection and power line circuit breaker 2 Digital communicator message not being received...

Страница 64: ...ears during Transmitter Sniffer test but does not clear 2a Transmitter zone type ZT is set to 00 Not Used 2b Transmitter battery not installed 2a Set ZT to a valid active zone type in field 56 or 58 2...

Страница 65: ...nsmitters with nonreplaceable batteries 8c Transmitter malfunctioning 8c Replace faulty transmitter 9 Local bell and keypad sound continuously after arming 9 Exit or interior zone contained a fault at...

Страница 66: ...VISTA 10SE Installation and Setup Guide 11 6...

Страница 67: ...ce to initiate the download call The control hangs up and then calls back the PC via the pre programmed telephone number The unit can then be uploaded downloaded or controlled from your office The con...

Страница 68: ...VISTA 10SE Installation and Setup Guide 12 2...

Страница 69: ...Auxiliary Power currents must not exceed 600mA total FUSE Battery 3A No 90 12 3 COMMUNICATION FORMATS SUPPORTED ADEMCO Contact ID Reporting 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK...

Страница 70: ...ltage Input 12VDC Current Drain 100mA 3 Interface Wiring Refer to 6127 keypad 5800 System RF Receivers 5881L 5881M 5881H 1 Physical 7 3 8 W x 4 3 8 H x 1 7 16 D 188mm x 112mm x 37mm NOTE 10 7 8 H 277m...

Страница 71: ...ctric smoke detector w 135 F 57 C heat detector A77 716B EOL relay module supervisory module for wired 4 wire fire zone 2112 24T Low profile 4 wire photoelectric smoke detector w 135 F 57 C heat detec...

Страница 72: ...Use with 8 ohm speaker UL Listed 1100mA current drain NOTE Requires special power wiring using additional components ADEMCO 705 820 5 inch Round Speaker 20 watt 8 ohm indoor or outdoor speaker Requir...

Страница 73: ...rt 68 of the FCC rules On the front cover of this equipment is a label that contains among other information the FCC registration number and ringer equivalence number REN for this equipment If request...

Страница 74: ...re alarm control panels to be provided with a backup battery that has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition follow...

Страница 75: ...ind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical syste...

Страница 76: ...cases the company s inside wiring associated with a single line individual service may be extended by means of certified connector assembly telephone extension cord The customer should be aware that...

Страница 77: ...ests 11 1 Compatible 4 Wire Smoke Combustion Detectors 13 3 CSFM A 2 Custom Words 8 3 Data Field Programming 3 3 4 1 Device Current Drain Worksheet 2 5 Dialer Programming 40 50 4 2 DIP Switches 2 8 Di...

Страница 78: ...tection 1 1 RF Receiver 2 7 RJ31X Jack 2 10 Security Codes 1 1 10 1 Sounder Bell Connections 2 4 Specifications and Accessories 13 1 Split Dual Reporting 4 3 Summary of Arming Modes 10 1 Supervised Fi...

Страница 79: ...THIS SYSTEM TIP BROWN RING GRAY TIP GREEN RING RED INCOMING PHONE LINE HANDSET BLACK RED 1000 OHMS EOLR 1000 OHMS EOLR ZONE 1 ZONE 2 HI LO HI LO 1000 OHMS EOLR 1000 OHMS EOLR ZONE 3 ZONE 4 HI LO HI LO...

Страница 80: ...1 9 l N7227V6 7 01 165 Eileen Way Syosset New York 11791 Copyright 2001 PITTWAY CORPORATION...

Отзывы: