background image

20

LST700 SERIES INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002012 Rev 4

LST700 SERIES FIRE ALARM PANEL

The primary mains fuse (F1) is ruptured.

Symptoms: the panel runs on batteries, but not on mains.  The red hazardous voltages present
light on the Power Supply PCB is off.

Suggested action:

(a) Isolate the mains supply, remove the Main Control PCB and check the PSU’s primary
mains fuse (F1) for continuity.

(b) If the fuse is ruptured it will be due to an excessive mains surge or a PSU fault.

Check the components on the PSU for damage.  If none is found replace the fuse with the
correct type and reconnect the mains supply. If the red lethal voltages present light does not
come on then the PSU is faulty and should be replaced.

The battery fuse (F2) is ruptured.

Symptoms: the panel runs on mains, but not on batteries.

Suggested action:

(a) Isolate the mains supply and disconnect the batteries.

(b) Remove the Main Control PCB and check the Battery Fuse (F2) on the Power Supply PCB
for continuity.

(c) If the fuse is ruptured check the Power Supply PCB and Main Control PCB for signs of
damage. If none is found, replace the fuse with the correct type, ensuring that the fuse clip is
not damaged when re-inserting the fuse.

(d) Refit the Main Control PCB and reconnect the batteries.

If the green ‘Supply Present’ light is lit, reconnect the mains supply and check that the power
supply fault has cleared. If the ‘Supply Present’ light is not lit, either the Power Supply
PCB or the Main Control PCB is faulty and should be replaced.

(e) If the Battery Fuse (F2) is intact, proceed to check the battery voltage (see below).

The battery voltage is too low.

Symptoms : the panel runs on mains, but may or may not run on batteries.

If the mains supply has failed and the battery supply has been discharged to the point where
the voltage is too low (i.e less than 21V), the panel will automatically turn off to avoid damaging
the batteries by allowing them to deep discharge. The panel will not restart unless fresh, fully
charged batteries are connected, or the mains supply is restored.

If the mains supply has not failed, but the total battery voltage is less than 21V, the PSU will not
charge the batteries to avoid damage to the charging circuit.  If the batteries can be charged, the
panel will still show a power supply fault until they have sufficient charge, at which point the power
supply fault will automatically be cleared.  Depending on battery size and the depth of discharge,
this may take several hours.  If the batteries are in poor condition they must be replaced.

Please note that the charging circuit is set up during manufacturing, and is temperature
compensated. There is no need to adjust the voltage.

If the batteries are in good condition and all the other checks have been performed and no
faults found, the Power Supply PCB is faulty and should be replaced.

NB: batteries that are not connected, connected in reverse or with opposite polarities will also
cause a power supply fault condition.

Supply Present light not lit

If the supply present light is not lit one of the following faults has occurred:

(1) Both the mains supply and the standby batteries have failed. This could be because the
mains supply has failed and the batteries have been exhausted.

Suggested action:

 Restore the mains supply and the ‘Supply Present’ light should come back

on.  However, if the batteries are discharged this will be recognised as a fault by the panel and
indicated as such. See “Battery voltage too low” above.

(2) The Power Supply PCB, the Main Control PCB and/or the cable that connects them is faulty.

If the mains supply is present (indicated by the red lethal voltages light being lit on the Power
Supply PCB), check that the connector cable between the Power Supply PCB and the Main
Control PCB is fully inserted at both ends. If so, either the Power Supply PCB and/or the Main
Control PCB and/or the connector cable are faulty and should be replaced.

Содержание LST700 Series

Страница 1: ...ES INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002012 Rev 4 LST700 SERIES FIRE ALARM PANEL LST700 SERIES FIRE ALARM CONTROL PANEL installation maintenance manual approved document no DFU7...

Страница 2: ...nputs and outputs 13 Programming the Panel 14 An overview of the panel s controls 14 Engineer functions 14 Accessing the engineer controls 16 Programming Coincidence Non latching Zones Delays and Zone...

Страница 3: ...tem functions as specified in EN54 A common negative volt line allowing optional three wire connection of detectors and sounders a useful retrofit solution when replacing many older mains based system...

Страница 4: ...system design is beyond the scope of this document A basic understanding of general fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent...

Страница 5: ...ro static handling precautions are taken immediately prior to handling the panel s PCBs or any other static sensitive components Before handling any static sensitive items operators should rid themsel...

Страница 6: ...iver Use of excessive force will damage the enclosure around the knock out Do not drill any additional holes for cable entry in this shaded area as this is where the PCBs and backup batteries will be...

Страница 7: ...e standby time of the system and this should be taken into consideration when selecting the standy battery See page 23 for more information Figure 4 Typical detector circuit wring An end of line capac...

Страница 8: ...ounder circuits share a common 0V return wire Figure 6 Typical three wire detector sounder circuit wiring The advantages of the three wire method are that it utilises standard system components can so...

Страница 9: ...the panel is reset This output does not turn on if the Class Change or Alert inputs are asserted or if the panel s Silence Activate Sounders button is pressed to manually evacuate the building unless...

Страница 10: ...gure 9 on page 11 The incoming mains cable should be brought into the panel at the top right hand side of the enclosure and terminated at the connector block CONN1 on the Power Supply PCB Make sure th...

Страница 11: ...tery leads supplied in the Panel s accessory pack See below for connection details Battery fuse F2 20 x 5mm 1A6 F to IEC 127 EN60127 Part 2 Do not use any other type or size of fuse in this position P...

Страница 12: ...ULT ALERT REM CONN5 CONN6 CONN7 CONN8 CONN9 Z1 DETECTOR CIRCUITS Installing the Main Control PCB The panel s Main Control PCB provides all the connections for the system s detector circuits sounder ci...

Страница 13: ...insulated and connected between the nut and washers on the base earth post see inset using eyed crimp connectors as per the detector and sounder circuit examples shown in Figure 12 For a full descript...

Страница 14: ...ed information on how to use the general and authorised user controls please refer to the User Manual Log Book Engineer controls access level three The following controls are available to competent se...

Страница 15: ...m to be investigated by the user During the delay period the output delays light on the front of the panel pulses to indicate the delay is operative Pressing the SILENCE RESOUND SOUNDERS button will o...

Страница 16: ...S LEVEL THREE FUNCTIONS button is pressed for the first time the accessed light will be lit steady and the first function coincidence will be selected and indicated by its yellow light flashing see ri...

Страница 17: ...t the Remote Output for editing The output s current status will be shown by the Remote Output Status light in the same way as for the zones 7 If required toggle between the two states by pressing the...

Страница 18: ...oms and advice on how to correct the above see page 19 section 1 2 Sounder Fault All sounder circuits are monitored periodi cally for open and short circuit faults unless disabled or in an alarm condi...

Страница 19: ...t the Panel If the fault condition clears this confirms there is a wiring fault b Double check and refit the wiring and the end of line capacitor on the zone Trace the fault with consideration for the...

Страница 20: ...omatically turn off to avoid damaging the batteries by allowing them to deep discharge The panel will not restart unless fresh fully charged batteries are connected or the mains supply is restored If...

Страница 21: ...rol A common symptom of this is the panel s controls locking up Suggested action Press the panel s RESET button and if still in access level three the ESCAPE ACCESS button This should clear the fault...

Страница 22: ...he two wires A good circuit will present only the end of line resistor value Any other resistance value shows a fault b If the readings from all sounder circuits are correct take their End of Line res...

Страница 23: ...ideline the quiescent current of most modern detectors is typically 0 00005A 50 A and that of manual call points is zero To obtain accurate figures consult the device manufacturers own specifications...

Страница 24: ...lue 6800 5 Tol 0 25W blue grey red gold Each circuit monitored for open and short circuit YES indicated by common fault Alarm voltage 27V maximum 20V minimum final battery voltage Sounder circuit fuse...

Отзывы: