N7627V2 5/98
®
5816TEMP
LOW TEMPERATURE TRANSMITTER
INSTALLATION INSTRUCTIONS
For use with QED control panels ONLY!
GENERAL
INFORMATION
The 5816TEMP Low Temperature Transmitter contains a low temperature detector that transmits a message
(alarm or trouble depending on the installer's programming entry) to a 5800 wireless receiver that is connected
to a QED control panel. The message is sent when the Temperature Sensor thermostat temperature reaches
+45
°
F
±
5
°
F (+4
°
C
±
3
°
C). The device resets after a temperature rise of about 9
°
F (5
°
C) for 5 minutes. At that
time, a restore message is sent to the receiver and the QED control panel.
ENROLLING THE
TRANSMITTER
SERIAL NUMBER
Each 5816TEMP is permanently assigned its own serial number. The QED control panel is required to "enroll"
the transmitter's serial number prior to the transmitter's usage.
Refer to the QED control panel's Installation Instructions for general information on the "enrolling" procedure.
The information given herein is specific to the 5816TEMP.
1. Place a battery in the battery holder, as described later in BATTERY INSTALLATION/REPLACEMENT
and as shown in Diagram 2. Observe polarity!
2. While in the zone programming mode, as described in the QED control panel's instructions, program this
device as the input type, “supervised RF,” and enter “1” as its loop number. Transmit from the device
(press the tamper switch, move the magnet, etc.).
NOTE: The polarity of the magnet must be correct; if the device is not enrolled as indicated on the keypad,
reverse the magnet's direction and redo step 2.
MOUNTING
For proper orientation of the unit in relation to its wall mounting plate and the loop wiring, read all of this section
before installing the unit.
Installing within close proximity to iron, steel and magnetic materials will affect the activation
temperature. Do not mount the unit within 1 ft. of these types of materials.
The description that follows assumes that the unit will be mounted as shown in the diagrams. The unit may,
however, be installed in
any direction, as long as the relationship of the unit to its mounting plate is maintained.
Although two holes are provided in the unit that would permit mounting directly to a surface (holes 'A' in
Diagram 2), it is recommended that the mounting plate be used, as described below, for ease in removing the
unit for servicing should it become necessary.
Before mounting the transmitter permanently, conduct Go/No Go tests (see QED control's instructions) to
verify adequate signal strength and reorient or relocate the transmitter if necessary. When a satisfactory
location is found, remove the battery and proceed with installation.
1. Disengage the supplied wall mounting plate from the unit by inserting the blade of a small screwdriver
into the locking tab release window (Diag. 2) and pressing it against the locking tab (Diag. 1) while sliding
the plate downward along the case back.
2. Install the mounting plate, with its case holding posts pointing up, in the location selected as described in
the QED control panel's Installation Instructions. Use the screws supplied. The word TOP is molded along
the upper edge of the plate.
3. Remove the transmitter's cover by inserting the flat blade of a small screwdriver into the closed pry-off
slot at the end of the unit farthest from the cover's decorative ribs, and twisting the blade.
4. Attach the case back to the mounting plate by sliding the keyhole slots in the case back down onto the
mounting plate's case holding posts.
5. Install the battery as described in BATTERY INSTALLATION procedure on the next page.
6. Replace unit's cover by engaging the case holding posts along the edge and snap shut.
+
–
COVER PRY-OFF POINT
ANTENNA
HOLES "A" (2)
(SEE TEXT)
LOCKING TAB
RELEASE WINDOW
BATTERY
COVER
TAMPER
SWITCH
COVER
HOLDING
HOOKS (2)
A
A
TEMPERATURE
SENSOR
MAGNET
@@@@@@@@e?
@@@@@@@@e?
@@h?
@@h?
@@h?
@@h?
@@h?
@@h?
@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e
@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e
@@@@@@@@
@@@@@@@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
@@
?@@
?@@
?@@
?@@
?@@
?@@
?@@@@@@@@
?@@@@@@@@
?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@
?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@e?@@@@@@@@?e@@@@@@@@
@@g
@@g
@@g
@@g
@@g
@@g
@@@@@@@@
@@@@@@@@
@@
@@
@@
@@
@@
@@
@@
@@
MAGNET
▲
▲
▲
▲
FOR ENROLLING, BRING
MAGNET PARALLEL TO
SENSOR AND REMOVE.
DO THIS TWICE.
CASE
HOLDING
POSTS (2)
PLATE
MOUNTING
HOLES (2)
ALIGNMENT
GUIDE STRIP
CASE LOCKING TAB
EXPLODED
VIEW
Diagram 1. MOUNTING PLATE
Diagram 2. No. 5816TEMP (Shown With Cover Removed)