ADC AD-333 Скачать руководство пользователя страница 9

112175 - 9

www.adclaundry.com

9

IMPORTANT:

 Make-up air openings should not be

located in an area directly near where exhaust vents exit
the building.

Allowances must be made for remote or constricting
passageways or where dryers are located at higher altitudes
or predominantly low pressure areas.

IMPORTANT: 

Make-up air must be provided from a

source free of dry cleaning solvent fumes.  Make-up air
that is contaminated by dry cleaning solvent fumes will
result in irreparable damage to the motors and other dryer
components.

NOTE: 

Component failure due to dry cleaning solvent

fumes will void the warranty.

Exhaust Requirements _______________

IMPORTANT:

 Dryer should be located where a minimum

amount of exhaust duct will be necessary.

CAUTION: This dryer produces combustible lint and
must be exhausted to the outdoors.  Every six months,
inspect the exhaust ducting and remove any lint
buildup.

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, overheating of the dryer, and
shutdown of the burner by the airflow (sail) switches, burner
hi-limits, or tumbler hi-limit thermostats.  (Refer to the
illustrations on the following page for details.)  The dryer
must be installed with a proper exhaust duct connection to
the outside.

CAUTION: This dryer produces combustible lint and
must be exhausted to the outdoors.

Improperly sized or installed exhaust ductwork can
create a potential fire hazard.

When possible, it is desirable to provide a separate exhaust
air duct for each dryer.  The duct should go as directly as
possible to the outside air.  Avoid sharp 90° right-angle turns
in ducting; use 30° or 45° angles instead.  The radius of the
elbows should preferably be a minimum of 1-1/2 times the
diameter of the duct.  To protect the outside end of the duct
from the weather, it may be bent downwards as indicated
on the following page.  Leave at least twice the diameter of
the duct as clearance between the duct opening and the
nearest obstruction.  If the exhaust duct goes through the
roof, it may be protected from the weather by using a 180°
turn to point the opening down.  Allow at least twice the
diameter of the duct as clearance from the nearest
obstruction.

Do not use screens, louvers, or caps on the outside opening
of the exhaust ductwork.  The ducting should be smooth
inside with no projections from sheet metal screws or other
obstructions, which will collect lint.  Additionally, inspection
doors should be installed at strategic points in the exhaust
ductwork for periodic inspection and cleaning.

Inadequate exhaust facilities may cause high temperature
limit switches or airflow switches to shut off the dryers.  Do
not disable the switches, which are provided for your safety.
Instead, investigate the exhaust ducting.  Any obstruction or
air friction due to numerous elbows/fittings in the ducting
will slow the passage of air through the system with resulting
inefficiency and potential fire hazard.

IMPORTANT: 

Exhaust back pressure measured by a

manometer at the dryer’s exhaust duct area must be no
less than 0 and must not exceed 0.3 in WC (0.74 mb).

NOTE: 

When the exhaust ductwork passes through a wall,

ceiling, or roof made of combustible materials, the
opening must be 2-inches (5.08 cm) larger than the duct
(all the way around).  The duct must be centered within
this opening.

IMPORTANT: 

The dryer exhaust duct must not be

connected to any gas vent, chimney, wall, ceiling, or
concealing space of a building.

It is recommended that exhaust or booster fans not be
used in the exhaust ductwork system.

As per the National Fuel Gas Code, “Exhaust ducts for
type 2 clothes dryers shall be constructed of sheet metal
or other noncombustible material.  Such ducts shall be
equivalent in strength and corrosion resistance to ducts
made of galvanized sheet steel not less than 26 gauge
(0.0195-inches [0.50 mm]) thick.”

Fresh Air Supply Requirements ______

This appliance may only be installed in a room that meets
the appropriate ventilation requirements specified in the
national installation regulations.

Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  The dryer must
be installed with provisions for adequate combustion and
make-up air supply.  An unrestricted source of air is
necessary for each dryer.  An airflow of 800 cfm (cubic feet
per minute) (22.6 cmm [cubic meters per minutes]) must
be supplied to each gas dryer.  As a general rule, an
unrestricted air entrance from the outdoors (atmosphere)
of a minimum of 1-1/2 square feet (0.14 square meters) is
required for each dryer.  If registers or louvers are installed
over the openings, then the area must be increased by at
least 33%.  It is not necessary to have separate make-up air
openings for each dryer.  Common make-up air openings
are acceptable.  However, they must be set up in such a
manner that the make-up air is distributed equally to the
dryers.

EXAMPLE: For a bank of eight dryers, two unrestricted openings measuring
3 feet by 2 feet (0.91 meters by 0.61 meters) are acceptable.

Содержание AD-333

Страница 1: ...s de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils ...

Страница 2: ...__________________________________________ ____________________________________________________________________________________________________ Replacement parts can be obtained from your reseller or the ADC factory When ordering replacement parts from the factory you can FAX your order to ADC at 1 508 678 9447 or telephone your order directly to the ADC Parts Department at 1 508 678 9000 Please s...

Страница 3: ...and or weather The wiring diagram for the dryer is located in the front electrical control box area Table of Contents _________________ Proposition 65 Use of this product could expose you to substances from fuel combustion that contain chemicals known to the State of California to cause cancer birth defects and other reproductive harm In the State of Massachusetts the following installation instru...

Страница 4: ...rubber and also may be a fire hazard The possible presence of residual quantities of aggressive or decomposed chemicals in the load may produce damage to the machine and harmful fumes A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from e...

Страница 5: ..._____________________________________________________________________________________ _________________________________________________________________________________________________________________________________ _________________________________________________________________________________________________________________________________ ______________________________________________________...

Страница 6: ...TRUCK 30 33 VOLTAGE AVAILABLE 120 240V 1 3ø 2 3w 50 60 Hz APPROXIMATE NET WEIGHT 675 lb 306 kg APPROXIMATE SHIPPING WEIGHT 710 lb 322 kg AIRFLOW PER POCKET 60 Hz 400 cfm 11 3 cmm 50 Hz 340 cfm 9 6 cmm HEAT INPUT PER POCKET 72 000 Btu hr 18 143 kcal hr EXHAUST CONNECTION DIAMETER 8 20 3 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 1 2 F N P T Specifica...

Страница 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Страница 8: ...e installed on noncombustible floors only The dryer must not be installed or stored in an area where it will be exposed to water and or weather The dryer is for use in noncombustible locations The dryer must be installed with provisions for adequate air supply as noted in this manual refer to Fresh Air Supply Requirements section Clearance provisions must be made from noncombustible construction a...

Страница 9: ...ews or other obstructions which will collect lint Additionally inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning Inadequate exhaust facilities may cause high temperature limit switches or airflow switches to shut off the dryers Do not disable the switches which are provided for your safety Instead investigate the exhaust ducting A...

Страница 10: ...ain duct run from the last dryer to where it exhausts to the outdoors is unusually long over 30 feet 9 1 meters or has numerous elbows more than one in it Single Dryer Venting 8 Inch Duct IMPORTANT A minimum exhaust duct size of 8 inches 20 3 cm must be used For an 8 inch 20 3 cm run where a maximum of two elbows are used refer to the illustration below the ductwork from the dryer outlet must not ...

Страница 11: ...es grounding must conform to applicable requirements of the National Electrical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the installation must conform to applicable Canada Standards Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel For added personal safety when possible it is suggested t...

Страница 12: ...a The dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1 2 psig 3 5 kPa Type of Gas Manifold Pressure In Line Pressure Natural 3 5 in wc 6 0 12 0 in wc 8 7 mb 14 92 29 9 mb Liquid Propane 10 5 in wc 11 0 in wc 26 1 mb 27 4 mb WARNING Fire or explosion ...

Страница 13: ... All components materials must conform to National Fuel Gas Code Specifications ANSI Z223 1 LATEST EDITION or in Canada CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 L P Gas or LATEST EDITION for General Installation and Gas Plumbing as well as local codes and ordinances and must be done by a qualified professional It is important that gas pressure regulators meet applicable pressure requir...

Страница 14: ...dels be sure that all gas shutoff valves are in the open position Be sure all back guard panels and service box covers have been replaced Check the lint door to ensure that it is closed and secured in place Rotate the tumbler by hand to be sure it moves freely Preoperational Test __________________ All dryers are thoroughly tested and inspected before leaving the factory However a preoperational t...

Страница 15: ...f service for a period of time the following must be performed Discontinue power to the dryer either at the external disconnect switch or the circuit breaker Discontinue the gas supply for gas models only Shut off external gas supply shutoff valve Service Parts Information __________ Service Service must be performed by a qualified trained technician service agency or gas supplier If service is re...

Страница 16: ... frequency of cleaning can best be determined from experience at each location Maximum operating efficiency is dependent upon proper air circulation The accumulation of lint can restrict this airflow If the guidelines in this section are met an ADC dryer will provide many years of efficient trouble free and most importantly safe operation WARNING Lint from most fabrics is highly combustible The ac...

Страница 17: ... on the data label affixed to the right side panel area at the rear of the dryer When contacting ADC please have the model number and serial number available 1 Model Number This describes the style of dryer and type of heat gas electric or steam 2 Serial Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular ...

Страница 18: ...ADC Part No 112175 9 06 05 14 ...

Отзывы: