TYPE OF GAS (PER POCKET)

Btu/hr

Rating

kcal/hr

Rating

Natural

Liquid Propane

Qty. D.M.S.

*

Part No.

Qty. D.M.S.

*

Part No.

72,000

18,143

1

#20

140908

1

#41

140909

Liquid Propane Conversion Kit Part Number 884399

Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal
regulator.  Incoming supply pressure must be consistent
between a minimum of 6.0 in WC (14.92 mb) and a maximum
of 12.0 in WC (29.9 mb) pressure.

L.P. Gas

Dryers made for use with L.P. gas have the gas valve’s
internal pressure regulator blocked open so that the gas
pressure must be regulated upstream of the dryer.  The
pressure measured at each gas valve pressure tap must
be a consistent 10.5 in WC (26.1 mb).  There is no regulator
or regulation provided in an L.P. dryer.  The water column
pressure must be regulated at the source (L.P. tank) or an
external regulator must be added to each dryer.

TYPICAL GAS CONNECTIONS

Piping Connections

All components/materials must conform to National Fuel
Gas Code Specifications ANSI Z223.1-LATEST EDITION, or
in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/
CGA-B149.2-M91 (L.P. Gas) or LATEST EDITION (for General
Installation and Gas Plumbing), as well as local codes and
ordinances and must be done by a qualified professional.
It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for
the total amount of all the appliance Btu being supplied.

The dryer is provided with two 1/2” N.P.T. inlet pipe
connections extending out the rear of the dryer (refer to page
7).

If a separate feed is provided for each tumbler from the
main supply line (header), then a 1/2” (12.7 mm) line
connection is sufficient.  However, if the top and bottom
tumbler connections are connected together, the supply
from the header must be increased to 3/4-inch (19.05 mm).
It is recommended that a gas shutoff valve be provided to
the gas supply line of each dryer for ease in servicing.

Shaded area is stated in metric equivalent

* D.M.S. equivalents are as follows:

Natural Gas ............... #20  =  0.161” (4.089 mm).
L.P. Gas ..................... #41  =  0.096” (2.438 mm).

Содержание AD-333

Страница 1: ...s de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils ...

Страница 2: ...__________________________________________ ____________________________________________________________________________________________________ Replacement parts can be obtained from your reseller or the ADC factory When ordering replacement parts from the factory you can FAX your order to ADC at 1 508 678 9447 or telephone your order directly to the ADC Parts Department at 1 508 678 9000 Please s...

Страница 3: ...and or weather The wiring diagram for the dryer is located in the front electrical control box area Table of Contents _________________ Proposition 65 Use of this product could expose you to substances from fuel combustion that contain chemicals known to the State of California to cause cancer birth defects and other reproductive harm In the State of Massachusetts the following installation instru...

Страница 4: ...rubber and also may be a fire hazard The possible presence of residual quantities of aggressive or decomposed chemicals in the load may produce damage to the machine and harmful fumes A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from e...

Страница 5: ..._____________________________________________________________________________________ _________________________________________________________________________________________________________________________________ _________________________________________________________________________________________________________________________________ ______________________________________________________...

Страница 6: ...TRUCK 30 33 VOLTAGE AVAILABLE 120 240V 1 3ø 2 3w 50 60 Hz APPROXIMATE NET WEIGHT 675 lb 306 kg APPROXIMATE SHIPPING WEIGHT 710 lb 322 kg AIRFLOW PER POCKET 60 Hz 400 cfm 11 3 cmm 50 Hz 340 cfm 9 6 cmm HEAT INPUT PER POCKET 72 000 Btu hr 18 143 kcal hr EXHAUST CONNECTION DIAMETER 8 20 3 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 1 2 F N P T Specifica...

Страница 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Страница 8: ...e installed on noncombustible floors only The dryer must not be installed or stored in an area where it will be exposed to water and or weather The dryer is for use in noncombustible locations The dryer must be installed with provisions for adequate air supply as noted in this manual refer to Fresh Air Supply Requirements section Clearance provisions must be made from noncombustible construction a...

Страница 9: ...ews or other obstructions which will collect lint Additionally inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning Inadequate exhaust facilities may cause high temperature limit switches or airflow switches to shut off the dryers Do not disable the switches which are provided for your safety Instead investigate the exhaust ducting A...

Страница 10: ...ain duct run from the last dryer to where it exhausts to the outdoors is unusually long over 30 feet 9 1 meters or has numerous elbows more than one in it Single Dryer Venting 8 Inch Duct IMPORTANT A minimum exhaust duct size of 8 inches 20 3 cm must be used For an 8 inch 20 3 cm run where a maximum of two elbows are used refer to the illustration below the ductwork from the dryer outlet must not ...

Страница 11: ...es grounding must conform to applicable requirements of the National Electrical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the installation must conform to applicable Canada Standards Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel For added personal safety when possible it is suggested t...

Страница 12: ...a The dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply system at test pressures equal to or less than 1 2 psig 3 5 kPa Type of Gas Manifold Pressure In Line Pressure Natural 3 5 in wc 6 0 12 0 in wc 8 7 mb 14 92 29 9 mb Liquid Propane 10 5 in wc 11 0 in wc 26 1 mb 27 4 mb WARNING Fire or explosion ...

Страница 13: ... All components materials must conform to National Fuel Gas Code Specifications ANSI Z223 1 LATEST EDITION or in Canada CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 L P Gas or LATEST EDITION for General Installation and Gas Plumbing as well as local codes and ordinances and must be done by a qualified professional It is important that gas pressure regulators meet applicable pressure requir...

Страница 14: ...dels be sure that all gas shutoff valves are in the open position Be sure all back guard panels and service box covers have been replaced Check the lint door to ensure that it is closed and secured in place Rotate the tumbler by hand to be sure it moves freely Preoperational Test __________________ All dryers are thoroughly tested and inspected before leaving the factory However a preoperational t...

Страница 15: ...f service for a period of time the following must be performed Discontinue power to the dryer either at the external disconnect switch or the circuit breaker Discontinue the gas supply for gas models only Shut off external gas supply shutoff valve Service Parts Information __________ Service Service must be performed by a qualified trained technician service agency or gas supplier If service is re...

Страница 16: ... frequency of cleaning can best be determined from experience at each location Maximum operating efficiency is dependent upon proper air circulation The accumulation of lint can restrict this airflow If the guidelines in this section are met an ADC dryer will provide many years of efficient trouble free and most importantly safe operation WARNING Lint from most fabrics is highly combustible The ac...

Страница 17: ... on the data label affixed to the right side panel area at the rear of the dryer When contacting ADC please have the model number and serial number available 1 Model Number This describes the style of dryer and type of heat gas electric or steam 2 Serial Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular ...

Страница 18: ...ADC Part No 112175 9 06 05 14 ...

Отзывы: