4.1.3 Commissioning of a Series Circuit equipped with the RELIANCE IL using lucDMC
This section does not explain how a series circuit without RELIANCE IL is commissioned. For further information about
commissioning of a series circuit in general contact the ADB SAFEGATE Service team. This section explains how the regulator
parameters can be adapted with lucDMC to be suitable for RELIANCE IL use. Follow the following steps in the indicated order
to commission the Individual Light Control and Monitoring System RELIANCE IL:
1. Balance the signals by parameterizing the "symmetry correction factor " in advanced settings tab as follows:
Figure 30: Symmetry correction factor — regulator parameters
a) Set the parameter Interval to "4".
When the interval is set to 4, the regulator can change the correction value for the balancing of the signal
automatically every 400 ms.
b) Set the brightness rate for the CCRE to approximately 30 % (which equals 5,2 A).
c) Watch the view for correction and difference in lucDMC.
The CCRE automatically changes the correction factor so that the difference approximates 0. The difference will never
be exactly 0 and keep this value. In a well-balanced circuit the differences varies between -20 and +20. The balancing
process can last up to 2 minutes. The balancing process has been successful when the regulator has stopped changing
the correction factor and the difference value is varying b0 and -0.
d) Hit the green arrow button and press Apply.
e) Hit the send button below the brightness level fields on the right.
The CCRE balanced the signals for the thyristor control. The correction values have been stored on the memory card.
NOTICE
You should check if the current flow direction of the primary cable is correct when the balancing of the signals
by the CCRE has not been successful. The K and L sensor cable might be mixed up with each other.
2. Check the current flow direction of the sensor cables and the external circuit
Operability of the RELIANCE IL depends on a properly planned and commissioned series circuit. The right orientation of
the in- and out-going cables also belongs to a properly planned and commissioned series circuit. The entire series circuit
must have the right orientation, which includes also winding directions of the coils inside the lamp transformers and the
orientation of the sensor cables. Follow the steps described below to test if the orientation is correct:
a) Switch on the series circuit and set ist to a brightness level of 10 %.
b) Wait at least 10 seconds for the remotes to go into fail-safe mode, which means all lights are lighted.
UM-5005, Rev. 004, 2020/08/06
47
Copyright
©
ADB SAFEGATE, All Rights Reserved
Содержание RELIANCE Intelligent Lighting Platform III
Страница 1: ...RELIANCE Intelligent Lighting Platform III User Manual UM 5005 Rev 004 2020 08 06 ...
Страница 2: ......
Страница 10: ...RELIANCE Intelligent Lighting List of Figures x Copyright ADB SAFEGATE All Rights Reserved ...
Страница 12: ...RELIANCE Intelligent Lighting List of Tables xii Copyright ADB SAFEGATE All Rights Reserved ...
Страница 18: ...RELIANCE Intelligent Lighting Safety 6 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 52: ...RELIANCE Intelligent Lighting Introduction 40 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 56: ...RELIANCE Intelligent Lighting Installation 44 Copyright ADB SAFEGATE All Rights Reserved ...
Страница 118: ......