3.3.7 Parallel control interface
Parallel control interface is used with traditional multi-wire control systems. The interface is designed to match with most
control system types and allows configuring. This interface is standard for all 8000 range CCRs (normal/direction changer/
circuit selector).
Parallel interface unit is custom designed E1 size plug in card with D37 / F communication connector installed on the face of
the card. The card is located in the RM-slot next to the power unit of the control rack.
Figure 1: Parallel control unit IDM 8000-03 layout and HW settings
Interface
Type
Data
Input / controls
Relay coil
Ucont = 0.8 – 1.6xUdcnom / R=3840
ohm
Output / indications
Relay contact
1A/30V DC, 0.3A/60V DC, 0.5A/125V AC
PARALLEL REMOTE CONTROL HARDWARE SETTINGS
Setting
Description
Factor setting
Allowed range
Control voltage
Control DC-voltage selection
60V
24 / 48 / 60V DC
Failsafe step
One step (dec)
Binary code(bin)
In case of control DC voltage or cable fault failsafe control status is taken.
Control relays contacts are inverted with jumpers. Inverted control must be
given by the control system
Off
Any step
Indication group
C, PI, FI
Enables galvanic isolation between control, positive indications and fault
indication groups
Remote control
Dip switch SW1 settings on mother board. For more information, see
Hardware system settings on page 44.
PARALLEL REMOTE CONTROL HARDWARE SETTING STEPS
Step
Task
Remarks
1
Turn the main switch off
2
Remove RCP unit
3
Set jumper switches to desired positions
4
Insert RCP and turn the main switch on
UM_IDM-8000, Rev. 1.7, 2021/05/06
17
Copyright
©
ADB Safegate, All Rights Reserved
Содержание IDM 8000
Страница 1: ...IDM 8000 CCR User Manual UM_IDM 8000 Rev 1 7 2021 05 06 ...
Страница 2: ......
Страница 8: ...IDM 8000 TABLE OF CONTENTS viii Copyright ADB Safegate All Rights Reserved ...
Страница 10: ...IDM 8000 List of Figures x Copyright ADB Safegate All Rights Reserved ...
Страница 12: ...IDM 8000 List of Tables xii Copyright ADB Safegate All Rights Reserved ...
Страница 18: ...IDM 8000 Safety 6 Copyright ADB Safegate All Rights Reserved ...
Страница 20: ...IDM 8000 About this Manual 8 Copyright ADB Safegate All Rights Reserved ...
Страница 76: ...IDM 8000 Troubleshooting 64 Copyright ADB Safegate All Rights Reserved ...
Страница 92: ...IDM 8000 Appendix F Parallel remote control example 80 Copyright ADB Safegate All Rights Reserved ...
Страница 100: ...IDM 8000 Appendix I Commissioning test report form 88 Copyright ADB Safegate All Rights Reserved ...
Страница 104: ...IDM 8000 Appendix J Spare part list 92 Copyright ADB Safegate All Rights Reserved ...
Страница 106: ...IDM 8000 Appendix K Components of electronics 94 Copyright ADB Safegate All Rights Reserved ...
Страница 107: ...Appendix L Appendix L CCR components UM_IDM 8000 Rev 1 7 2021 05 06 95 Copyright ADB Safegate All Rights Reserved ...
Страница 113: ...UM_IDM 8000 Rev 1 7 2021 05 06 101 Copyright ADB Safegate All Rights Reserved ...
Страница 114: ...IDM 8000 Appendix M Output Terminals 102 Copyright ADB Safegate All Rights Reserved ...
Страница 118: ......