![ADB Safegate CRE 10 Скачать руководство пользователя страница 71](http://html1.mh-extra.com/html/adb-safegate/cre-10/cre-10_installation-manual_2847401071.webp)
A.07.370e - Edition 2.0
71
Technical data
7.6.2
Substation layout, big and small cabinets
Table: 7.8
Clearance specifications
If necessary, the distances can be increased for maintenance purposes.
7.7 Protection devices
Table: 7.9
Protection devices specifications
X
Y
Clearance specification
Distance [mm]
Front clearance
Approximately 500
Between the rear of the machine and the wall, X
Approximately 500
Between two machines (side by side) or between
another machine, Y
Minimum 150
Equipment
type [kVA]
Equipment voltage
[V]
Main fuse rating [A] Manual switch type
C rating [A]
Maximum line input
current [A]
2.5
208 to 230
16
16
14.7
380 to 400
16
10
8.0
4
208 to 230
32
25
23.4
380 to 400
20
16
12.8
5
208 to 230
50
40
29.3
380 to 400
32
20
16.0
7.5
208 to 230
50
50
44.0
380 to 400
32
25
24.1