PROGRAMMING INSTRUCTIONS
Please read all 3 steps before programming
1.
Enter a programming function by pressing button the number
of times as the desired function number from the tables below
(e.g., press twice for function 2, occupancy time delay).
2.
LED will flash back the selected function’s current setting
(e.g., 5 flashes for 10 minute time delay). To change setting,
proceed to step 3 before flash back sequence repeats 3 times.
To exit the current function or to change to a different function,
wait for sequence to repeat 3 times then return to step 1.
3.
Press button the number of times indicated in the particular
function’s detailed table for the NEW desired setting (e.g.,
press 3 times for 5 min). As confirmation of setting change,
LED flashes back the NEW setting 3 times before exiting.
DETAILED FUNCTION TABLES
2
= Occupancy Time Delay
1
30 sec
4
7.5 min**
7
15.0 min
2
2.5 min
5
10.0 min*
8
17.5 min
3
5.0 min
6
12.5 min
9
20.0 min
3
= Dim to Off Time Delay
1
30 sec
4
7.5 min
7
15.0 min
10
0 sec
2
2.5 min**
5
10.0 min
8
17.5 min
11
Infinite
3
5.0 min
6
12.5 min
9
20.0 min
4
= Test Mode / 100hr Burn-In / Auto Set-Point
1
Normal*
4
Run Auto Set-Point
2
Run 100 hr Burn-In
5
Blink back Set-Point
2
3
Run 100 hr then Auto-Setpoint
6
Test Mode
3
2
The LED will blink back the ten’s digit, then pause, then blink back
the one’s digit. For a “0” the LED will blink very rapidly. The sequence
is repeated 3 times.
3
Test Mode will disable Minimum On Time, set Occupancy Time Delay
to 30 sec, and shorten all photocell transitions and dimming rates.
Mode will expire after 10 min or if function 4 is set back to Normal.
5
= Ten’s Digit of Set-Point
1
10 fc
4
40 fc
7
200 fc
2
20 fc
5
50 fc
8
Disable
3
30 fc
6
100 fc
10
0
fc*
6
= One’s Digit of Set-Point
1
1 fc
4
4 fc
7
7 fc
10
0 fc
2
2 fc
5
5 fc*
8
8 fc
3
3 fc
6
6 fc
9
9 fc
7
= Sunlight Discount Factor
1
x/1***
4
x/4*
7
x/7
10
x/10
2
x/2
5
x/5
8
x/8
3
x/3
6
x/6
9
x/9
8
= Incremental Set-Point Adjustment
1
Decrease 1 fc
2
Increase 1 fc
10
= Minimum On Time
1
0 min
3
30 min
5
60 min
2
15 min*
4
45 min
11
= Photocell Mode
P
Option:
1
Full On/Off Ctrl*
2
Inhibit Only Ctrl
ADC
Option:
1
Normal**
2
Dim Only (No Off)
12
= Dual Technology (Microphonics
TM
)
1
Normal*
2
Off
3
Medium
4
Low
14
= Lamp Information
1
Enable LampMa
2
Disable LampMa*
3
Total Switches / 1000
4
4
Total Time On (khrs)
4
5
Reset Total Switch and Total Time On Statistics
6
Reset LampMa Value
4
The LED will blink back a two digit value; the first digit, then pause,
then blink back the second digit. For a “0” the LED will blink rapidly.
15
= Dimming Range (High Trim)
1
Off
4
3 Volts
7
6 Volts
10
9 Volts
2
1 Volt
5
4 Volts
8
7 Volts
11
10 Volts*
3
2 Volts
6
5 Volts
9
8 Volts
16
= Dimming Range (Low Trim)
1
Off
4
3 Volts
7
6 Volts
10
9 Volts
2
1 Volt*
5
4 Volts
8
7 Volts
11
10 Volts
3
2 Volts
6
5 Volts
9
8 Volts
*** SPECIAL DEFAULT SETTING FOR CM(R)B 6, CM(R)B 50,
CM(R) 6, RM(R) 6, RM(R) 50, SB(R) 6, & SB(R) 50 SERIES UNITS
2
Occupancy Time Delay
•
•
•
•
3
Dim to Off Time Delay
•
•
4
Test Mode & 100 hr Burn-In
•
•
•
•
4
Auto Set-Point
•
•
5
Ten’s Digit of Set-Point
•
•
6
One’s Digit of Set-Point
•
•
7
Sunlight Discount Factor
•
•
8
Incremental Set-Point Adjust.
•
•
10
Minimum On Time
•
•
•
•
11
Photocell Mode
•
•
12
Dual Tech. (Microphonics
TM
)
1
•
•
•
•
14
Lamp Information
•
•
•
15
Dimming Range (High Trim)
•
•
16
Dimming Range (Low Trim)
•
•
1
PDT SENSORS ONLY
* DEFAULT SETTING
** SPECIAL DEFAULT SETTING FOR -ADC, -D UNITS
PROGRAMMING
STD. OPTIONS
FUNCTIONS
UNIT P ADC D